teko ASTRA-713 Скачать руководство пользователя страница 1

 

 

Research and Development Center TEKO 

 

 

 

CONTROL PANEL 

 

ASTRA-713 

 
 
 

 
 

Operating Manual 

 
 

Содержание ASTRA-713

Страница 1: ...Research and Development Center TEKO CONTROL PANEL ASTRA 713 Operating Manual...

Страница 2: ...ing Mode Via PC 29 12 Registering and Deleting TM Keys for Stand Alone Operating Mode 33 13 Pre Starting Procedure and Operability Test in Stand Alone Mode 35 14 Using the Device in Stand Alone Mode 3...

Страница 3: ...le dry contact type relay output OC Programmable open collector type output SA Sound Alerter LA Light Alerter BZ Built in Buzzer beeper TM Key Touch Memory identifier Reader TM key reader for example...

Страница 4: ...ons to a CSP via relay outputs to alerting equipment via open collector outputs and to BZ 1 3 When controlled by an Astra Dozor control panel the device will monitor the state of 8 eight alarm loops w...

Страница 5: ...performs arming disarming functions as follows using the button connected to the TM key input using TM keys or devices that generate a TM format code for example the Astra RVC the As tra TRC is used a...

Страница 6: ...of operating at supply voltages of 14 21 V 2 6 The device outputs alarm notifications to the CSP even if power to the device is completely turned off 2 7 The device can control external elements usin...

Страница 7: ...ion control system 3 Specifications Power supply voltage V 12 3 2 Current consumption mA maximum in standby mode 180 in alarm mode 230 Number of alarm loops connected to the device 8 Number of relay o...

Страница 8: ...nt mA 500 Maximum loading voltage V 15 Mode selection CSP alarm warning light arm disarm executive alarm siren custom Alarm loop specifications ZONE GND terminals Alarm loop terminals voltage in stand...

Страница 9: ...70 10 fire 300 30 Alarm loop wire resistance without external elements Ohm maximum intrusion 220 fire 150 Leakage resistance between ZONE output wires or wire and Ground kOhm minimum intrusion 20 fir...

Страница 10: ...re range from 30 up to 50 Relative air humidity up to 93 at 40 without moisture condensation 4 Delivery Set Astra 713 Control Panel 1 pcs Resistor 3 9 8 pcs Screw 2 9 25 4 pcs Dowel 5 x 25 4 pcs Stick...

Страница 11: ...11 5 Structure 5 1 The unit s structure is a block consisting of a base and a removable cover Inside the block is a circuit board with radio elements Figure 1 Figure 1 Built in Buzzer...

Страница 12: ...ltage and the status of the RS 458 interface 5 3 Silicon indicator buttons 1 8 are mounted in the device s cover and are used to arm disarm the corresponding alarm loops 5 4 There is a tamper switch o...

Страница 13: ...e relay based on the following tactics on alarm event of one fire type detector Warning notification is transferred at alarm event of two and more fire type detectors in one Zone Fire notification is...

Страница 14: ...Passageway area a function for one or several intrusion type ALs assigned to one relay with group of independently controlled ALs Arming occurs automatically when the last zone of the group is armed...

Страница 15: ...n Relay 1 Relay 2 outputs CSP Alarm mode default settings 1 Armed CSP Relay is closed in Armed mode in condition of absence of any event in AL assigned to this relay 2 Alarm CSP Relay is opened in Arm...

Страница 16: ...Not lit at Violation state in Disarmed mode 6 Armed Lights green at Norm state in Armed mode 7 Alarm Fire Flashes red 1 time per 1s at Violation state in Armed mode 8 Failure Flashes red 2 times per 1...

Страница 17: ...er supply and communications with the master device when operating in the slave mode 11 Power failure Lights up with a continuous red light if supply voltage is too low 11 0 0 3 V 12 Communications in...

Страница 18: ...re 1 Intermittent sound 1 time per 2s at Violation state of fire type AL 15 Failure 1 Intermittent sound 2 times per 1s at Failure state of fire type AL 16 Warning 1 Intermittent sound 2 times per 1s...

Страница 19: ...impulse 19 Alarm loop disarmed Double sound impulse 20 TM Key cancellation Three successive sound impulses at invalid TM identifier code 21 Delay Intermittent sound 1 time per 1s during entry exit del...

Страница 20: ...med mode on expiry of entry delay time for intrusion type AL1 and or AL2 OC2 output Warning light operating mode default settings 25 Disarmed Not lit if even one AL is disarmed 26 Armed Lights constan...

Страница 21: ...security fire alarm systems 8 1 Mounting location selection The device must be mounted on walls or other surfaces at premises protected from rain snow mechanical damage and unauthorized access 8 2 In...

Страница 22: ...the plugs out of selected wire input holes in the device base Run wires from the power supply unit alarm loop RS 485 interface relays OC Astra TM reader if TM keys are being used and Astra RVC if Astr...

Страница 23: ...als of the device is to be carried out in accordance with selected wiring diagrams in Appendices A and B Step 6 Replace the device cover in its position until a click is heard If necessary apply a lab...

Страница 24: ...plug F7 positions of the remaining jumpers are ignored Table 2 Operating mode Parameters AL1 AL4 Intrusion instant 70 ms integration time AL5 AL8 Fire Entry delay for AL1 and AL2 Exit delay for AL1 an...

Страница 25: ...1 AL5 AL8 relay 2 OC1 output operating mode Siren OC1 output assignment to AL Al1 AL8 OC2 output operating mode Warning light OC2 output assignment to AL Al1 AL8 Relay delay for AL1 and AL2 No Notifi...

Страница 26: ...the device may be configured using jumpers Jumper specifiable operating modes Fig 2 are shown in Table 3 Figure 2 ATTENTION Device power must be off when installing or removing jumpers Table 3 Plug Pl...

Страница 27: ...e AL1 with delay Remaining ALs are instant AL1 intrusion type with delay AL2 AL4 intrusion type instant AL5 AL8 fire type without double event All ALs are of intrusion type AL1 with delay AL2 24 h sil...

Страница 28: ...ressed Setting up operation modes using computer to left two pins Setting up operation modes using jumpers to right two pins Firmware update F8 Astra 984 or Terminal resistor connection Astra 984 conn...

Страница 29: ...ww controlex eu Operating procedure 1 turn off power supply 2 remove the cover by inserting a flat screwdriver blade into the cover slot section 8 3 remove jumper from F7 plug 4 install jumper on F1 p...

Страница 30: ...device operating modes per the instructions in the Pconf 713 user manual opens upon clicking the Help button in the program window or pressing the F1 button on the com puter keyboard 11 record settin...

Страница 31: ...a for intrusion type ALs 24 h mode for intrusion type ALs double event for fire type ALs integration time 70 300 ms for intrusion type ALs way of arming disarming TM key buttons registration of new TM...

Страница 32: ...OC are armed and opened when any of the ALs connected to this relay or OC is disarmed Siren The relay closes when there is an alarm and opens when there is no alarm The OC output closes when there is...

Страница 33: ...remove the cover by inserting a flat screwdriver blade into the cover slot section 8 3 install jumper on one pin of F1 plug arming mode while using TM keys 4 press TM button and turn on power supply...

Страница 34: ...e button on the Astra TRC key fob If registration is successful indicator 1 will light up green The TM key can be authorized to arm disarm all alarm loops If the TM key is already present in device me...

Страница 35: ...y state and ALx will automatically transition to the Armed state b bring the device to the Armed state by pressing the control button bringing the TM key to the reader pressing the Astra TRC key fob b...

Страница 36: ...the control button or the AL button of the corresponding protected facility or part of it 3 Exit the premises being secured and close the entrance door 4 At the expiration of the exit time make sure L...

Страница 37: ...specified delay time release the control button or press the AL button If the time from the moment the door opens the AL violation occurs to device disarming exceeds the specified entry delay then th...

Страница 38: ...Reset Fire notification Release the control button touch the TM key to the reader press the Astra TRC button or press the AL button on the device corresponding to the protected facility or part of it...

Страница 39: ...om www controlex eu Operating procedure 1 turn off power supply 2 remove the device cover 3 disconnect the RS 485 interface wires from the device 4 install jumper on the right two pins of F7 plug 5 co...

Страница 40: ...ort sound tone will be heard indicator will change color from red to green and a corresponding message will appear on the computer screen If the firmware update procedure is not successful a correspon...

Страница 41: ...r section 15 16 2 The device up to 16 pcs is connected to the Astra Dozor control panel via RS 485 inter face 16 3 AL types and operating modes are set using the procedure described in the Quick Start...

Страница 42: ...tra Zitadel system AL properties are specified in the system settings which are configured using the Setup Module that is a part of the Astra Z MSS 17 3 Any equipment that outputs 64 bit identificatio...

Страница 43: ...estores default settings and deletes registration attributes It is used in the procedure de scribed in section 8 5 of the Quick Start Guide F2 F6 are not used F7 is used to activate the firmware updat...

Страница 44: ...tions c inspection of conformity with technical parameters and operability in accordance with this manu al 18 2 Inspection of the technical condition of this device should be arranged by laboratories...

Страница 45: ...onformity marks if the certificate of conformity is present a bar code duplicating the textual information 19 2 The label situated inside the device cover displays the device name jumpers function for...

Страница 46: ...from the date of manufacture 21 4 The manufacturer is required to perform repairs or replace the device during their warranty period 21 5 The warranty is not applicable in the following situations non...

Страница 47: ...47 Appendix Astra 713 connection schematic Fig 1 Astra RVC ver TM wiring diagram Astra RVC ver TM...

Страница 48: ...contacts GB1 12V power supply unit 1 sound alerter HL1 light alerter 1 TM key reader R1 resistor 3 9 kOhm S1 control button ATTENTION When a TM key reader is mounted in a metal housing on a metal surf...

Страница 49: ...49 Fig 3 Active detector connection schematic to CSP Rlim Rlim Rlim Rlim Rlim Rlim Rter Rter Rlim Rlim Rlim Rlim Rlim Rlim Rter Rter...

Страница 50: ...stor 2 kOhm Rter rating see Table 3 S1 control button 1 240 active detector Table 3 Number of detectors n Resistor rating kOhm less than 5 3 9 from 6 to 10 4 7 from 11 to 20 5 1 from 21 to 30 6 2 Note...

Страница 51: ...51 Appendix B Astra Dozor control panel connection schematic Fig B 1...

Страница 52: ...v1_6_en Sales technical support and warranty service TD LLC Prospekt Pobedy str 19 420138 Kazan Russia Phone 7 843 261 55 75 Fax 7 843 261 58 08 E mail info teko biz support teko biz Web www teko biz...