CONTROL PANEL
Operation Manual
Страница 1: ...1 Scientific Development Center TEKO CONTROL PANEL Operation Manual...
Страница 2: ...2...
Страница 3: ...llation 23 11 Default Settings 25 12 Setting Operating Mode by Jumpers 26 13 Setting Operating Mode via PC 28 14 TM Registration and Deletion 33 15 Extension Line Connections 35 16 Pre Starting Proced...
Страница 4: ...stra TRC or Astra TRC ver M TM Touch Memory Identifier Control button Switch LED Zone x Zone x LED indicator where x is zone number SA Sound Alerter BZ Built in Buzzer LA Light Alerter SC Short Circui...
Страница 5: ...ors and other units Astra 712 4 and Astra 712 8 differ from each other by the following parameters Astra 712 4 Astra 712 8 Number of zones 4 8 Number of indicators 5 9 2 Delivery Set Astra 712 4 Astra...
Страница 6: ...tual information 3 2 The label inside the control panel cover contains the following information device name power supply parameters function of jumpers used for setting operating modes information ab...
Страница 7: ...d values Norm Violation Failure Warning The following devices can be connected to the control panel Zone Detectors control panel NO NC relay outputs of dry contact type Fire type detectors powered via...
Страница 8: ...channel 433 92 MHz GSM channel PC etc functional units relay modules indication modules Power output for detectors and outer load DC supply up to 0 75A Overload protection and protection against malfu...
Страница 9: ...om AC network in stand by mode without regard to outer load and in alarm mode Wt max 15 Current consumption from BAT mA max Astra 712 4 In Stand by mode 150 In Alarm mode 170 Astra 712 8 In Stand by m...
Страница 10: ...8 36 Battery discharge indication voltage without mains voltage V 11 5 0 3 Battery voltage whereby device is switched to sleep mode without mains voltage V 10 5 0 3 Battery voltage whereby device is...
Страница 11: ...om 5 to 12 Warning from 1 5 to 3 Failure more than 12 Zone current for detectors powering mA max 3 Number of TM identifiers max 28 Weight without BAT kg max 0 9 Overall dimensions mm max 165 190 79 Op...
Страница 12: ...ol panel is designed as a block with a removable cover Figure 1 Installed inside a block are printed circuit board PCB with radio elements network transformer and fuse block for mains voltage switch F...
Страница 13: ...tension line In case of battery discharge below 10 5 V and absence of AC voltage the device transmits an alarm notification to central surveillance post and switches to sleeping mode with minimal powe...
Страница 14: ...cation is required only Double event a function for one or group of fire type zones assigned to one relay based on the following tactics on alarm event of one fire type detector Warning notification i...
Страница 15: ...ontrolled zones Arming occurs automatically when the last zone of the group is armed Disarming occurs automatically when at least one zone of the group is disarmed Extension line is 2 wired data line...
Страница 16: ...l response Relay operating mode CSP alarm by default 1 Armed CSP Relay is closed in Armed mode in condition of absence of any event in zones assigned to this relay 2 Alarm CSP Relay is opened in Armed...
Страница 17: ...at transition of Zone x parameters to Failure state in Disarmed mode 6 Armed Lights green at Norm state in Armed mode 7 Alarm Fire Flashes red 1 time per 1s at Violation state in Armed mode 8 Failure...
Страница 18: ...ce of voltage 220V and nor mal BAT voltage 12 BAT discharge power failure Lights red at absence of voltage 220 V and BAT discharge below 11 5 V 13 BAT failure Flashes red 1 time per 1s at absence of B...
Страница 19: ...ype Zone 17 Failure1 Intermittent sound 2 times per 1s at Failure state of fire type Zone 18 Fire danger1 Intermittent sound 2 times per 1s at Warning state of fire type Zone in double event mode 19 P...
Страница 20: ...sound impulse 22 Zone Disarming Double sound impulse 23 TM Identifier cancellation Three successive sound impulses at invalid TM identifier code 24 Delay Intermittent sound 1 time per 1s during entry...
Страница 21: ...ion state of fire type Zone 28 Failure 1 Continuous sound at Failure state of at least one fire type Zone 29 Fire danger 1 Intermittent sound 1 time per 1s at Warning state of fire type Zone in double...
Страница 22: ...onstantly at Norm state of Zone in Armed mode 36 Alarm Fire Failure Fire danger Flashes 1 time per 1s at Violation state of at least one zone in Armed mode ARM_out output 37 Armed Closed to GND in Arm...
Страница 23: ...form mounting marking as per figure 2 3 Mount fixation elements 4 Fix device base to bearing area by screws 5 Connect control button if it is used Drill out a hole in the cover at the place where cont...
Страница 24: ...t 220V 9 Install BAT if it is used connect terminals of red and blue wires to corresponding pole termi nals of BAT 10 Insert fuse holder into socket jack 11 Apply voltage 220V POW indicator lights up...
Страница 25: ...delay for Zone1 and Zone2 0 s 0 s Extension line mode Master Data exchange rate 4800 b s Arming with TM identifier Auto arming Function Allowed Time for automatic arming 240 s Zone1 and Zone2 operati...
Страница 26: ...el switched off only Operating modes set by jumpers Figure 4 are given in the Table 3 Figure 4 Table 3 Plug Name of plug Jumper position Operating mode F1 Way of arming with TM identifiers with contro...
Страница 27: ...type instant All Zones are of intrusion type Zone1 delayed Zone2 24 hours silent alarm Other Zones instant All Zones are of fire type without double event F6 Entry exit delay for Zone1 Deactivated Zon...
Страница 28: ...connection F9 Connection of termi nal resistor Resistor is disconnected for Slave mode Resistor is connected for Master mode jumper is removed or installed on one plug pin jumper is installed on two p...
Страница 29: ...ng terminal from one of its poles 3 Disconnect extension line wires from the control panel 4 Connect Astra 982 or Astra 983 interface adapter to control panel terminals in accordance with Figure 5 6 o...
Страница 30: ...s into the control panel memory Record button 11 Break connection with the control panel Disconnect button 12 Close Pconf 712 software 13 Switch the control panel OFF remove fuse holder out of socket...
Страница 31: ...hours mode for intrusion type zones double event for fire type zones integration time 70 300 ms for intrusion type zones way of arming disarming TM button switch registration of new TM identifiers and...
Страница 32: ...opened at alarm or disarming with tamper switch closed additional tampering control At absence of Zone assignment to the given type of relay it duplicates the state of tamper switch Sound Relay is clo...
Страница 33: ...e fuse holder out of socket jack and disconnect BAT by removing terminal from one of its poles 3 Install jumper on one pin of F1 plug arming by TM identifiers mode 4 Press TM button and switch the con...
Страница 34: ...ts up green Rights for arm disarm all Zones are assigned to this TM In case of failed registration or presence of the given TM identifier in control panel memory Zone1 indicator lights up red 7 If nec...
Страница 35: ...addi tional relay outputs Peculiarities of connection and operation The following parameters should be provided for extension line active wires resistance not ex ceeding 100 Ohm the capacity formed b...
Страница 36: ...tarts flashing red 1 time per 1s BZ generates short signals during 10s e Connect the terminal back f Wait till control panel Zone x switches to Ready state Zone x indicator flashes green 1 time per 1s...
Страница 37: ...TRC 1 Close all windows air vents doors etc 2 Leave secure zone and close entrance door 3 Bring TM identifier to TM reader or press button on TRC 4 Make sure LA switches ON and SA shortly switches ON...
Страница 38: ...Zones are in 24 hours mode by default After powering up Zones are armed automati cally when all Zone parameters are in Norm state Make sure Zone indicators light green and LA lights constantly The de...
Страница 39: ...Switch the control panel OFF remove fuse holder out of socket jack and disconnect BAT by removal of terminals from one of its poles 3 Disconnect extension line wires from LIN GND terminals 4 Connect...
Страница 40: ...am 11 Break connection with the control panel Disconnect button 12 Close Flasher exe software 13 Switch the control panel OFF remove fuse holder from socket jack 14 Install jumper on F7 plug on requir...
Страница 41: ...ry devices at control panel power is OFF 20 EC Conformity Declarations This product is in conformity with the provisions of LVD 73 23 EEC 93 68 EEC EMC 89 336 EEC EN 61000 6 3 2005 Electromagnetic com...
Страница 42: ...m the date of operation startup but no longer than 2 years 6 months from the date of manufacturing 22 5 The manufacturer commits to replace or repair the product during the warranty period 22 6 The wa...
Страница 43: ...43 Appendix A Astra 712 4 Astra 712 8 Control Panel Connection Diagram Figure 1 Astra RVC ver TM connection diagram Astra RVC ver TM ver TM Astra 712 4 8...
Страница 44: ...44 Figure A 2 Connection diagram for detectors with NO NC relay outputs of dry contact type...
Страница 45: ...attery 12 V 7 2 A h 1 sound alerter HL1 light alerter 1 TM reader R1 resistor 3 9 KOhm S1 control button 1 transformer 1 socket with fuse holder FU1 WARNING When installing TM reader with metal housin...
Страница 46: ...46 Figure 3 Connection diagram for active detectors...
Страница 47: ...3 R124 R155 R186 R217 R248 for rating value see table A 1 S1 control button 1 transformer 1 120 active detector 1 socket with fuse holder FU1 Table 1 Number of detectors n Rating value of resistors KO...
Страница 48: ...48 Release 712 8v6_10_en Manufacturer TD Prospekt Pobedy str 19 420138 Kazan Russia Phone 7 843 528 03 69 export teko biz Made in Russia...