Astra-4511
Wireless manual fire call point
User Guide
Manufacturer:
ZAO NTC TEKO
420108 Kazan, Russia
Gafuri 71
+7843 528-03-69
[email protected]
www.teko.biz
Made in Russia
Ver. 4511rk2-v3_0_instr_en
1 FUNCTION
The detector is designed to manually turn on
the fire alarm signal by pressing the drive ele-
ment, generate a fire notification and transmit
the notification via radio to the Astra-812 Pro
control panel directly or via the Astra-WE 433
radio extender or to the Security hub.
The detector supports two-way radio exchange.
2 SPECIFICATION
Wieless coverage range,
line-of-sight, m, not less ............................... 300
Operating frequency range, MHz ................. 433
Supply voltage, V ........................ from 2.1 to 3.0
Overall dimensions, mm ............... 110
× 94 × 47
Operation conditions
Temperature range,
°
С ............from - 10 to + 55
Relative air humidity
,
% ........... up to 93 at + 40
°
С
Without moisture condensation
3 DELIVERY SET
Detector delivery set includes:
mounting parts
(
dowel
– 2 pcs., screw – 2 pcs.,
), special key for
opening
– 1 pc., key pusher – 1 pc., battery
(CR123A, 3V) - 2 pcs. (installed), user guide
–
1 copy.
4 INDICATION
Notification
Indication
Boot time
1x red flash then 1x white led
flash
Norm
1x red flash in 60 sec. period
Fire alarm
1x red flash every 2 sec. until
the fire factor is eliminated.
2x flashing in a period of 25
sec. when eliminating the fire
factor before receiving a
command from the controller
Test fire
1x red flash in every 2 sec.
during 30 sec. when receiv-
ing the test command from
the Astra-942 laser remote
control
Power failure
3x red flash in 25 sec. period
Tampering /
Restore tam-
pering
1x red flash
Searching
connection
5x white flash in 1 sec.
No connection
2x white flash in 25 sec.
period
Reset
2
x white flash in 1-2 sec.
Laser tool
command
1x red flash for 2 sec.
Notes
1 When the message “Power failure” appears,
the battery must be replaced within two months.
2 Indication of notifications "Power failure", "No
network", "Search for network" goes off 60
minutes after
turning on the power supply. The
indication turns on again for 60 minutes after
receiving
the "Test" command from the Astra-
942 laser tool.