VOT 34; Rev 1.81; EN; 11.12.2019
TKT65C
– Installation and maintenance
32
Test 23.03.2011 10:30
Change over board 1-
#OO…..
Change over board 2-
OO…..
Figure 5. Luminaire tests with change over boards
The "1- #OO" symbol for changeover board 1 indicates an error in output circuit 1.
The "2- OO" symbols for changeover board 2 indicate that output circuit 2 has no errors.
If you want to view the data for a particular changeover board, first select the board using the +/-
buttons, then confirm your selection by pressing the SETUP button. To move back to the higher-level
menu from the test log, press the SETUP button for 1.5 s.
You can use the data display for change over boards to view data for any output circuit. You can
browse the output circuits by pressing the +/- buttons. To view the data for luminaires, press the SETUP
button. If the luminaires have been given names using a PC programme, the names are shown on the
last line. To move back to the higher-level menu from the test log, press the SETUP button for 1.5 s.
CHANGE OVER BOARD 1, OUTPUT CIRCUIT>1
HI: OOOOOOOOOOOOOOOO
LO: O#OO…………
Figure 6. Luminaire tests, output circuit data
The dots indicate a vacant address, O = OK and # = ERROR. Twenty luminaires have been
interconnected to provide service in a output circuit, with luminaire 2 malfunctioning (LO 2).
Battery test history
You can browse the battery test log for detailed information on battery tests. You can view battery test
results, if the central battery systems has performed an automatic battery test, or if a manual test has
been carried out. The battery test log contains test dates, test times and test results. If you want to view
the data for a particular battery test, first select the desired date using the +/- buttons, then confirm your
selection by pressing the SETUP button. To move back to the higher-level menu from the test log,
press the SETUP button for 1.5 s.
Figure 7. Main menu Browse battery tests
The log shows the date, time and duration of the test, as well as the voltage of the battery set at the end
of the test. To move back to the higher-level menu from the test log, press the SETUP button for 1.5 s.
Figure 8. Luminaire test log
Error log
In addition to the log of the luminaires and battery tests, the display shows an error log of all errors
detected in the central battery system. The log shows the date and time of each error, as well as a
corresponding error code. If you want to view the data for a particular log, first select the desired log
using the +/- buttons, then confirm your selection by pressing the SETUP button. To move back to the
higher-level menu from the test log, press the SETUP button for 1.5 s.
Browse luminaire tests
Browse battery tests
Browse error log
Setup
Date Time Log
23.03.11 10:30 Error
24.03.11 10:30 OK
End of log
Date Time Log
23.03.11 10:30 Error
Battery test duration 01:25
Battery set voltage 221V
Содержание TAPSA CONTROL TKT65
Страница 37: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 37 TKT65 P cabinet construction...
Страница 38: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 38 TKT65C PP IP54 construction...
Страница 43: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 43...
Страница 44: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 44...
Страница 45: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 45...
Страница 46: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 46...
Страница 47: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 47...
Страница 48: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 48...
Страница 49: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 49...
Страница 50: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 50...
Страница 51: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 51...