background image

DynaJet

®

 Flex 7140 

OPER

ATION

MENU OPTIONS

INTR

ODUC

TION

APPENDIX

8

www.teejet.com

INITIAL ST

AR

TUP

NO. 5 PREFORM SYSTEM FUNCTIONAL TEST

The following is instructions for performing a functional test of the 

system.

• 

Ensure that current rate control system is operating normally 

prior to attempting to use the DynaJet Flex.

1. On the Work screen, set DynaJet Flex operating mode to 

Manual Mode  .

2. Using the MANUAL ADJUSTMENT buttons    , set 

PWM duty cycle at 100%. This will make the system 

operates as if DynaJet Flex was not present. 

3. 

Use this configuration to verify the rate control system is 

operating normally.

4. Using the MANUAL ADJUSTMENT buttons    , set 

PWM duty cycle to 50%.

5. 

Use this configuration to verify the rate control system is 

operating normally.

• 

Confirm boom section functionality.

1. Continue operating DynaJet Flex in Manual Mode   with 

PWM duty cycle set to 50%.

2. Switch the master switch ON (on rate controller or other 

boom section control switches) 

3. Using the switch box, turn ON each section verifying the 

proper section turns blue on the DynaJet Flex Work screen. 

4. Turn the master switch OFF. On the DynaJet Flex Work 

screen, verify all sections are now grey.

• 

Start pump and ensure no leaks.

• 

Verify pressure on mechanical gauge matches the digital 

pressure display within reason. If not, adjust maximum pressure 

sensor value as previously described.

• 

Confirm e-ChemSaver Solenoids is impulsing

• 

Configure in PWM mode DynaJet Flex at duty cycle of 50%. 

1. On the Work screen, set DynaJet Flex operating mode to 

Manual Mode  .

2. Using the MANUAL ADJUSTMENT buttons    , set 

PWM duty cycle to 50%.

3. 

Use this configuration to verify each of the corresponding 

e-ChemSaver Solenoids is impulsing.

This confirms the basic functionality of the DynaJet Flex system. 

Further details for fine-calibrating the system are in “Calibrate the 

DynaJet Flex System” section of this guide.

NO. 6 CALIBRATE THE RATE CONTROLLER REGULATION

The following procedure determines the most aggressive rate 

controller regulation valve gain that will work over all pressure 

ranges.
Before you begin:

• 

Ensure product pump is providing flow greater than 

the maximum demand of the system. Consult sprayer 

manufacturer specifications.

•  Understand that the most aggressive value will be found 

by increasing valve gain until system oscillates and then 

decreasing the setting until the system is stable at that value. 

 

NOTE: Other rate controller specific settings may apply 

based on your specific rate controller system

•  The rate controller must be operating in automatic mode 

during these tests.

•  To attain the minimum and maximum operating pressures for 

the specific nozzle in use under each test condition the user 

must be able to either: adjust the target application rate, or 

adjust the machine speed 

Flow Impulses Tests

The following tests will confirm that impulse of flow through the 

solenoids will not affect rate controller stability even when duty 

cycle is below 50%.
1. Set DynaJet Flex operating mode to Manual Mode   .
2. Using the MANUAL ADJUSTMENT buttons    , set PWM 

duty cycle as noted in each test.

3. 

Preform tests as specified in the following sections, taking note 

of the pressure levels during each test. 

4. Set rate controller valve gain to the highest value that will work 

with all three of the following tests. This will be the lowest gain 

value found in the 3 tests. Once established, this value should 

not need to be changed again.

If the system does not control acceptably with this gain value 

at all manual duty cycle settings, then something is wrong 

with the system that needs to be resolved before trying to 

calibrate the DynaJet Flex System. For assistance, contact 

TeeJet Technologies Customer Support or an authorised TeeJet 

Technologies dealer if additional support is required.

Содержание DYNAJET FLEX 7140

Страница 1: ...DYNAJET FLEX 7140 INSTALLATION SETUP AND USER GUIDE Software version 1 03 with Optional Dual Nozzle Mode...

Страница 2: ...ct names are trademarks or registered trademarks of their respective companies or organisations Limitation of Liability TEEJET TECHNOLOGIES PROVIDES THIS MATERIAL AS IS WITHOUT WARRANTY OF ANY KIND EI...

Страница 3: ...ASIC SCREEN USE 5 NO 2 SETUP UP MACHINE 6 NO 3 SETUP UP AND SELECT NOZZLE 6 NO 4 GET TO KNOW THE CONTROL MODES 7 NO 5 PREFORM SYSTEM FUNCTIONAL TEST 8 NO 6 CALIBRATE THE RATE CONTROLLER REGULATION 8 N...

Страница 4: ...eneral disassembly and reassembly 23 115880 E CHEMSAVER 24 General Disassembly and Reassembly 24 APPENDIX B DYNAJET APPLICATION CHARTS 25 DYNAJET FLEX NOZZLE SELECTION 25 Application Rates Available a...

Страница 5: ...ase contact a local dealer Keep children away from equipment Do not operate machinery under the influence of alcohol or any illegal substance Some systems include a fan heater Never cover the heater o...

Страница 6: ...that this apparatus is well aligned and that all connections are tight The plumbing supply to the equipment should meet all company and local regulations and must be properly routed and connected to t...

Страница 7: ...s do not hang below the equipment Allow sufficient clearance for harness cables and hoses from implement and machine operational zones When cleaning equipment protect harness cables from high pressure...

Страница 8: ......

Страница 9: ...tic rate controller loop performs the same as it would if the DynaJet Flex controller were not present The DynaJet Flex controller changes flow output to each individual nozzle based upon input provid...

Страница 10: ...24 DynaJet Flex driver G 16 05015 Pressure sensor H 45 10178 to IC18 45 10179 to Raven 440 45 10181 to Raven Envizio 45 10186 to 15 Section Boom Harness Boom harness I 45 05855 CAN terminator START J...

Страница 11: ...ermination 45 04005 06 20 START 6 nozzle 20 50 cm spacing w termination 45 04005 08 20 8 nozzle 20 50 cm spacing 45 04005 08 20 END 8 nozzle 20 50 cm spacing w termination 45 04005 08 20 START 8 nozzl...

Страница 12: ...pecific nozzle spacing Always start with nozzle 1 and work left to right while facing in the machine s forward direction CAN Cables Terminators The Start terminator 45 04006 START must be connected to...

Страница 13: ...Screen Once initialisation is complete the Work screen will appear Prior to operation all settings and configurations must be established Please contact a dealer or TeeJet Customer service representa...

Страница 14: ...ch section This value should match the number of nozzles used on the spray controller When programming is complete values should match and show in green X X Maximum Pressure Sensor Value Verify this v...

Страница 15: ...checkboxes the system will recalculate the desired pressure It will then adjust the PWM duty cycle to attempt to attain the desired pressure in the system Manual Mode PWM The user can manually adjust...

Страница 16: ...calibrating the system are in Calibrate the DynaJet Flex System section of this guide NO 6 CALIBRATE THE RATE CONTROLLER REGULATION The following procedure determines the most aggressive rate controll...

Страница 17: ...default is 30 Test 3A 2 Set rate controller gains values with operating pressure at MINIMUM 3 Reduce target rate or machine speed until system reaches the minimum operating pressure 4 Adjust the gain...

Страница 18: ...he Droplet Size Keys choose the highest pressure smallest droplet size that will typically be used by disabling Droplet Size Keys Example to 2 Run the system and view on the DynaJet Flex the Current N...

Страница 19: ...e current PWM duty cycle as a percentage Active Solenoid Dual Nozzle Mode Only Displays if one or both sets of solenoids are active Actual Pressure Displays the actual pressure Boom Status X X Blue se...

Страница 20: ...ze Engaged Disabled Use these buttons to enable or disable droplet sizes Droplet selection cannot have skips within the size sequence Droplet Size Engaged Indicates the droplet size is included in cal...

Страница 21: ...select an nozzle mode 1 Press the CHANGE NOZZLE MODE button Figure 3 7 Work Screen Dual Nozzle Mode Active Solenoids Change Nozzle Mode Dual Nozzle Active Indicates the droplet size is included in ca...

Страница 22: ...uty Cycle Error the desired pressure is not being maintained by the system X X High Pressure Error the actual pressure is above the high pressure alarm value X X Outside Droplet Size Error droplet siz...

Страница 23: ...and capacity is automatically added to the favourites list X X Diagnostics used to diagnose and observe operating issues of the system and booms While in a menu option press the HOME button to return...

Страница 24: ...ightness level of the display Range is 5 to 100 in 5 increments Units Sets the units to us psi or metric bar Key Beep Enable disable all beeping from console Number of Sections Set the number of boom...

Страница 25: ...uty Cycle Sets the minimum duty cycle to which the DynaJet Flex will control Default is 30 minimum is 20 Higher values reduce the overall control range of the system Control Hold Delay When any boom s...

Страница 26: ...tomatically be added to the Favourites List Figure 4 6 Nozzle Selection Screen Figure 4 7 Current Nozzle on Operation Screen Table 4 1 Nozzle Sizes and Associated Colours Established nozzle capacities...

Страница 27: ...ware version Pressure Sensor Displays pressure sensor status Pressure Sensor Interface Displays pressure sensor interface status Boom Interface Module Symbol indicating the boom interface DynaJet Flex...

Страница 28: ...tion Location is notated with the driver number D and output number N and may include an A or B distinction for the solenoid position when in Dual Nozzle Mode Next Nozzle Press to view the next nozzle...

Страница 29: ...ure 4 13 Driver Module Error Nozzle Sensor Error Indicates which nozzle is in error by displaying the nozzle number nozzle location and current amps Figure 4 14 Nozzle Sensor Error Pressure Sensor Err...

Страница 30: ...psi Minimum Duty Cycle 20 default 30 Control Hold Delay 0 0 10 0 seconds default 1 0 second Coarse Gain 1 20 default 4 Fine Gain 1 20 default 6 OEM Description Default Values Suggested Setting Use Def...

Страница 31: ...4 mm 9 16 or adjustable wrench X X All repairable parts should be accessible at this point The Plunger Sub Assembly 3 Stainless Steel Spring 6 and O rings 8 9 10 can be replaced without further disass...

Страница 32: ...the Tube Sub Assembly 3 using a 14 mm 9 16 or adjustable wrench X X All repairable parts should be accessible at this point The Plunger Sub Assembly 4 stainless steel Spring 5 and O rings 6 8 9 can be...

Страница 33: ...te at a duty cycle of about 70 when running at expected travel speeds In other words choose nozzle capacity and desired pressure droplet size closer to the high end of the speed or rate range than to...

Страница 34: ...below to compensate for higher and lower speeds that may be experienced in the field In this case a TT11006 at 3 4 bar will work very well US If the operator wants to apply 15 GPA at 10 MPH he would...

Страница 35: ...ynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 27 98 05345 EN R2 APPENDIX Application Rates Available at Given Speed and Nozzle Capacity Table 6 4 Application Rates Metric Page 1...

Страница 36: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 28 www teejet com APPENDIX Table 6 5 Application Rates Metric Page 2 TeeJet DynaJet Application Chart v 2 1 115880 DSM 2 25 19...

Страница 37: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 29 98 05345 EN R2 APPENDIX Application Rates Available at Given Speed and Tip Capacity Table 6 8 Application Rates US Page 1...

Страница 38: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 30 www teejet com APPENDIX Table 6 9 Application Rates US Page 2 TeeJet DynaJet Application Chart v 2 1 115880 DSM 2 25 19...

Страница 39: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 31 98 05345 EN R2 APPENDIX Speed Range Available at Given Nozzle Size and Application Rate Table 6 6 Speed Range Metric Page 1...

Страница 40: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 32 www teejet com APPENDIX Table 6 7 Speed Range Metric Page 2 TeeJet DynaJet Application Chart v 2 1 115880 DSM 2 25 19...

Страница 41: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 33 98 05345 EN R2 APPENDIX Speed Range Available at Given Tip Size and Application Rate Table 6 10 Speed Range US Page 1...

Страница 42: ...DynaJet Flex 7140 OPERATION INITIAL STARTUP MENU OPTIONS INTRODUCTION 34 www teejet com APPENDIX Table 6 11 Speed Range US Page 2 TeeJet DynaJet Application Chart v 2 1 115880 DSM 2 25 19...

Страница 43: ......

Страница 44: ...orks along with an existing rate controller and allows the operator to choose specific droplet sizes that will be used for a particular job The rate controller manages application rate and the DynaJet...

Отзывы: