Microprocessor Controlled
I G B T Drive
Inverter Motor Speed Regulator
Operating Manual
N310
/E310+
Serise
200V class
400V class
0.4~2.2KW (1.2~4.0KVA)
0.75~55KW (1.7~110KVA)
Страница 1: ...Microprocessor Controlled I G B T Drive Inverter Motor Speed Regulator Operating Manual N310 E310 Serise 200V class 400V class 0 4 2 2KW 1 2 4 0KVA 0 75 55KW 1 7 110KVA...
Страница 2: ...lified personnel have corrected the situation Failure to do so could result in serious injury z Check inverter and motor nameplates to determine that they have the same HP and voltage ratings Ensure t...
Страница 3: ...the drive and check new rotation Step 4 Check Full Speeds at 50Hz 60Hz z Frequency Speed can be changed by pressing the up or down Arrow keys To move right or left for next digit press key Press the R...
Страница 4: ...lified personnel have corrected the situation Failure to do so could result in serious injury z Check inverter and motor nameplates to determine that they have the same HP and voltage ratings Ensure t...
Страница 5: ...the drive and check new rotation Step 4 Check Full Speeds at 50Hz 60Hz z Frequency Speed can be changed by pressing the up or down Arrow keys To move right or left for next digit press key Press the R...
Страница 6: ...e light will fade z Do not make any connections when the inverter is powered on Do not check parts and signals on circuit boards during the inverter operation z Do not disassemble the inverter or modi...
Страница 7: ...be avoided z To avoid the risk of fire do not install the inverter on flammable objects Install on nonflammable objects such as metal surfaces z If several inverters are placed in the same control pa...
Страница 8: ...he operation of the inverter is based on the setup of 00 03 or00 04 and 04 09 and the condition of external switch FWD REV button Attention the start operation will be regardless of 04 03 04 04 04 06...
Страница 9: ...king resistors z The inverter can drive the motor from low speed to high speed Verify the allowable speed range of the motor and the load before operation z Note the settings related to the braking un...
Страница 10: ...Type 2P5 0 5 HP 1 Can be dedicated 001 1 HP 2 high speed motor only 002 2 HP 3 drawbench only 003 3 HP Power supply custom made type 005 5 HP Blank general client 3 Three phase 4 Isobarically water s...
Страница 11: ...40o C z Avoid exposure to rain or moisture z Avoid direct sunlight z Avoid oil mist and salinity z Avoid corrosive liquid and gas z Avoid dust lint fibers and small metal filings z Keep away from rad...
Страница 12: ...Chapter 3 Ambient Environment and Installation 3 2 3 2 Environmental precautions Do not use the inverter in an environment with the following conditions...
Страница 13: ...type is 300V and 400 V class type is 600V C Control Cables Control cables are connected toTM2 control terminal block Choose control cables according to the following criteria 1 Use copper wires only...
Страница 14: ...ively use fuses with current limit function Horsepower power supply standard Fuse types 1 2 15A 600VAC 100KA I R 3 200 240V 20A 600VAC 100KA I R 1 5A 600VAC 100KA I R 2 10A 600VAC 100KA I R 3 15A 600V...
Страница 15: ...ew M2 Signal terminals TM3 1 3 Wire gauge 0 80mm2 18 AWG terminal screw M3 model N310 XXX 4001 4002 4003 4005 4008 4010 4015 Molded case circuit breaker made by Teco 50E 15A 50E 20A 50E 30A 50E 50A Ma...
Страница 16: ...external control and auto restart after power failure or when using a brake controller z Do not use the magnetic contactor as the run stop switch of the inverter AC reactor for power quality improveme...
Страница 17: ...oise interference Refer to the figures below z A noise filter in the output of the main circuit can suppress conducted noise z To prevent radiated noise the wires should be put in a metal pipe and dis...
Страница 18: ...Refer to the figure below The wiring distance should not exceed 50 meters z C Inverter Ground terminal must be connected to installation ground correctly and according to the required local wiring re...
Страница 19: ...4 5 12 6 5 16 11 23 9 12 5 Net Weight KG 1 4 1 4 2 5 4 0 Allowable momentary power loss time second 1 0 1 0 2 0 2 0 Three phase 380 480V model N310 XXX 4001 4002 4003 4005 4008 4010 4015 Horsepower H...
Страница 20: ...peed control or automatic procedure control with multifunctional contacts on the terminal block TM2 Frequency Control Frequency Limit Function Upper lower frequency limits and three programmable skip...
Страница 21: ...he relays to protect the motor the curve can be set and the inverter 150 1min Over Voltage 200V class DC Voltage 410V 400Vclass DC Voltage 820V Under Voltage 200V class DC Voltage 190V 400Vclass DC Vo...
Страница 22: ...M Power input MC relay MC Power output S1 reset GND SYN TR1 output terminals 30VDC 200mA 220V 0 5 3HP 380V 1 15HP 0 10V 1 2 0 10V I V RS485 RS232 JP1 JP2 JP3 2 P P PID input FM Frequency indicator 0 1...
Страница 23: ...C Common contact R1B Normal close contact R1A Normal open contact Multifunctional output terminals Contact rated capacity 250VAC 1A or30VDC 1A Contact using description refer to parameters 01 09 01 10...
Страница 24: ...JUMPER function JP1 Communication mode Remarks RS485 communication RS232 communication Communications applications JP2 JP3 Type of external signal Remarks 1 2 3 0 20mA analog signal 1 2 3 0 10VDC anal...
Страница 25: ...pter 3 Ambient Environment and Installation 3 15 3 7 Outline Dimensions unit mm 1 Frame1 single Three phase N310 20P5 2001 Figure 3 8 Frame size 1 Dimensions Unit mm Tolerance 0 4mm MODEL N310 20P5 20...
Страница 26: ...r 3 Ambient Environment and Installation 3 16 2 Frame2 Single Three phase N310 2002 Three phase N310 4001 4002 4003 Figure 3 9 Frame size 2 Dimensions Unit mm Tolerance 0 4mm MODEL N310 2002 4001 4002...
Страница 27: ...hapter 3 Ambient Environment and Installation 3 17 3 Frame3 single Three phase N310 2003 Three phase N310 4005 4008 Figure 3 10 Frame size 3 Dimensions Unit mm Tolerance 0 4mm MODEL N310 2003 4005 400...
Страница 28: ...Chapter 3 Ambient Environment and Installation 3 18 4 Frame4 Three phase N310 4010 4015 8 Figure 3 11 Frame size 4 Dimensions Unit mm Tolerance 0 4mm MODEL N310 4010 4015...
Страница 29: ...3 FWD LED Forward Direction LED action Flash while stopped solid Lit during operation 4 REV LED Reverse Direction LED action Flash while stopped solid Lit during operation 5 Four actions of FUN mode H...
Страница 30: ...ether output current output voltage DC voltage is displayed or output PID is determined by 11 00 respectively Power On Power Voltage 1 5 seconds later or after Enter operation signal Press DSP to modi...
Страница 31: ...on Instruction of the LED keypad 5 seconds later or after Enter operation signal Press DSP to modify the display Power On LED fully Lit LED flashing HZ RPM HZ RPM HZ RPM FUN FUN FUN FUN VOLT VOLT AMP...
Страница 32: ...Chapter 4 Software Index 4 4 4 1 4 Keypad Operating Example...
Страница 33: ...Chapter 4 Software Index 4 5 Example 5 Operation Control LED Lit LED Flashing LED Off Example4 Modifying the Value of Parameter Figure 4 4 Keypad RUN Sequence 0 5s Later...
Страница 34: ...otors for total inverter current 2 Input correct VF Pattern parameter 05 04 05 09 3 When the nameplate of the motor is unknown the inverter will be set by default to parameters according to the standa...
Страница 35: ...ameter group 13 Auto Run Auto Sequencer function group 0 The basic parameters group Function Code No Description Range Code Factory Setting Remarks 00 00 Control Mode 0 Volts Hz 1 Vector General Purpo...
Страница 36: ...minal digital signal input function group Function Code No Description Range Code Factory Setting Remarks 01 00 Multifunction Input Term S1 0 01 01 Multifunction Input Term S2 1 01 02 Multifunction In...
Страница 37: ...Overload Protection OL2 12 Over torque Threshold Level OL3 13 PID Feedback Signal Loss 0 01 11 Frequency Output Setting Hz 0 00 400 00 0 00 1 01 12 Frequency Detection Range 0 00 30 00 2 00 1 01 13 S...
Страница 38: ...ositive 1 Negative 0 1 02 16 FM Slope 0 Positive 1 Negative 0 1 3 preset Frequency function group Function Code No Description Range Code Factory Setting Remarks 03 00 Preset Speed Control mode Select...
Страница 39: ...0 1 03 29 Preset Speed6 Acctime 0 1 3600 0 second 10 0 1 03 30 Preset Speed6 Dectime 0 1 3600 0 second 10 0 1 03 31 Preset Speed7 Acctime 0 1 3600 0 second 10 0 1 03 32 Preset Speed7 Dectime 0 1 3600...
Страница 40: ...Method 0 Enable Speed Search 1 Normal Start 0 04 06 Auto Restart Delay Time Seconds 0 0 800 0 0 0 04 07 Number of Auto Restart Attempts 0 10 0 04 08 Reset Mode Setting 0 Enable Reset Only when Run Com...
Страница 41: ...ncy Hz 0 10 400 00 0 50 0 60 5 05 09 Minimum Frequency Voltage Ratio 0 0 100 0 1 0 5 05 10 V F Energy Saving Mode 0 Disabled 1 Controlled by MFIT at Energy Saving 0 5 05 11 V F Energy Saving Gain 0 10...
Страница 42: ...g Deceleration 50 200 200 Inverter Rated Current 200 07 03 Trip Prevention Level In Run Mode 50 200 200 Inverter Rated Current 200 07 04 over voltage Prevention Level in Run Mode 350 0 VDC 390 0 VDC 7...
Страница 43: ...3 Disabled 1 08 Communication function group Function Code No Description Range Code Factory Setting Remarks 08 00 Assigned Communication Station Number 0 32 1 2 4 08 01 RTU code ASCII code select 0 R...
Страница 44: ...ime Seconds 0 00 10 00 0 00 1 09 05 PID Offset 0 Positive 1 Negative 0 1 09 06 PID Offset Adjust 0 109 0 1 09 07 PID Output Lag Filter Time Seconds 0 0 2 5 0 0 1 09 08 Feedback Loss Detection Mode 0 D...
Страница 45: ...tion 1 Carrier mode1 2 phase PW M modulation 2 Carrier mode2 2 phase randomized PW M modulation 3 Carrier mode3 randomized PW M modulation 4 Carrier mode4 dual randomized PW M modulation 1 10 05 Accel...
Страница 46: ...Place xxx x 3 Line Speed is Displayed with Two Decimal Places xx xx 4 Line Speed is Displayed with Three Decimal Places x xxx 0 1 11 03 Max PID Feedback Setting 0 999 100 1 11 04 Min PID Feedback Sett...
Страница 47: ...0 13 01 Auto _ Run Mode Frequency Command 1 13 02 Auto _ Run Mode Frequency Command 2 13 03 Auto _ Run Mode Frequency Command 3 13 04 Auto _ Run Mode Frequency Command 4 13 05 Auto _ Run Mode Frequenc...
Страница 48: ...tion 3 13 36 Auto_ Run Mode Running Direction 4 13 37 Auto_ Run Mode Running Direction 5 13 38 Auto_ Run Mode Running Direction 6 13 39 Auto_ Run Mode Running Direction 7 13 40 Auto_ Run Mode Running...
Страница 49: ...ontrolled by the external terminals and the Stop key for emergency stop is operational Refer to 04 02 description Note 00 03 00 04 1 please refer to parameter 04 03 04 04 04 06 04 07 for detailed desc...
Страница 50: ...time 1 second 0 1 3600 0 00 10 Deceleration time 1 second 0 1 3600 0 1 Formula for calculating acceleration and deceleration time The denominator is base on the rated frequency of motor 0 o r p re s...
Страница 51: ...odes for external terminals 0 Forward stop reverse stop 1 Run stop forward reverse 2 3 wire control mode run stop 1 When operation command 00 03 00 04 0 external terminal 00 11is valid 2 When operatio...
Страница 52: ...S2 7 Jog Jog run is controlled by external terminals S1 on is Jog forward S2 on is Jog reverse Group1 External terminal digital signal input function group Multifunction input terminals TM2 S1 S6 cont...
Страница 53: ...and the duration is determined by the time the input is ON The corresponding preset frequency will be according to preset value of parameters 3 01 to 3 16 and in relation to the operation of input ter...
Страница 54: ...accelerates from that present speed to preset speed 8 01 00 05 12 Energy saving operation FAN PUMP or other high inertia loads need greater starting torque but once the operational speed is reached t...
Страница 55: ...aneously pressed are invalid 5 01 07 0 the inverter accelerates to the setting of 03 01 and maintains speed When the UP Down terminal is on setting frequency is the value 03 01 01 07 and the inverter...
Страница 56: ...e less than N the signal will be treated as noise 2 Each scan period is 2ms 3 The user can specify the scan times interval duration according to the noise environment If the noise is serious increase...
Страница 57: ...y the 04 01 It will store the frequency when the run signal is removed UP DOWN keys are idle when the inverter is stopped The keypad is available to modify the preset frequency 03 01 If 1 08 2 the UP...
Страница 58: ...d Level 13 PID Feedback Signal Loss 01 11 Frequency Reached Output Setting 0 00 400 00Hz 01 12 Frequency Detection Range 0 00 30 00Hz 01 09 10 2 The preset frequency is reached 01 12 01 09 10 3 Arbitr...
Страница 59: ...NC xx0xx S3 NO xx1xx NC x0xxx S4 NO x1xxx NC 0xxxx S5 NO 1xxxx NC 01 14 s6 switch type select xxxx0 s6 NO xxxx1 s6 NC Note NO Normal open NC Normal close The switches type is decided by 01 13 01 14 Be...
Страница 60: ...20mA AI2 2 10V 4 20mA 02 00 AI1 AI2 analog Input signal type select refer to P3 14 1 0 10V 0 20mA 2 2 10V 4 20mA 02 01 AI1 signal verification Scan Time 1 200 2mSec 02 02 AI1 Gain 0 1000 02 03 AI1 Bi...
Страница 61: ...10 2 05 2 11 2 09 A 100 50 0 0 100 C 100 50 0 1 100 B 100 0 0 0 100 D 100 0 0 1 100 The setting of figure 4 18C The setting of figure 4 18D 2 02 2 08 2 03 2 09 2 04 2 10 2 05 2 11 2 09 2 02 2 08 2 03...
Страница 62: ...16 FM Slope 0 positive 1 Negative 1 The multifunction analog output terminal of the terminal block TM2 is 0 10Vdc analog output The output type is determined by the02 12 The output voltage level can...
Страница 63: ...lating acceleration and deceleration time The denominator is base on the rated frequency of motor 06 04 Acctime parameter preset frequency Actual Acctime 06 04 Dectime parameter Actual Dectime 06 04 p...
Страница 64: ...20 03 01 03 02 06 04 c 03 21 03 03 03 02 06 04 d 03 24 03 03 06 04 e 03 23 03 04 06 04 f 03 26 03 04 06 04 g 03 25 03 05 06 04 h 03 26 03 05 06 04 a b c d e f g h Time Preset speed1 Preset speed2 Pre...
Страница 65: ...mentary power loss and restart enable while CPU is operating According to the capacity of DC power 04 04 Momentary Power Loss Ride Thru Time Seconds 0 0 2 0 second 1 If the input power supply due to s...
Страница 66: ...when Run Command is Off 1 Enable Reset when Run Command is On or Off 04 08 0 Once the inverter is detected a fault please turn Run switch Off and then On again to perform reset otherwise restarting wi...
Страница 67: ...rter stop 4 IF the power on signal enabled during the KEB function the inverter accelerate to original frequency 04 12 Lower Limit of Power Voltage Detect 150 0 210 0 300 0 420 0 04 13 DC Injection Br...
Страница 68: ...Frequency Voltage Ratio 0 0 100 0 05 06 Medium Frequency Hz 0 10 400 0Hz 05 07 Medium Frequency Voltage Ratio 0 0 100 0 05 08 Minimum Frequency Hz 0 10 400 0Hz 05 09 Minimum Frequency Voltage Ratio 0...
Страница 69: ...start torque 3 High start torque 12 4 13 Decreasing torque 5 Decreasing torque 14 6 15 7 16 50 Hz Constant torque 8 60 Hz Constant torque 17 V 100 B C 1 5 3 0 60 400 Hz V 1 3 2 5 50 400 Hz V 100 B C 1...
Страница 70: ...to boost voltage to improve the precision of the speed Output Current 05 01 Note 06 01 motor rated current Slip frequency boost 06 01 05 01 05 02 05 01 motor no load current 05 02 approximate value M...
Страница 71: ...l not run as the inverter performs auto tuning Once the auto tuning is complete the inverter will write the internal parameter of the motor to06 06 06 10 and auto reset the 06 05 as 0 2 Auto tuning mu...
Страница 72: ...even operation impurities of processed materials etc will cause the inverter to trip thus inconvenience users When the operating torque of the inverter exceeds the setting of 07 03 the inverter will l...
Страница 73: ...Threshold Level 30 300 07 12 Over torque Activation Delay Time Seconds 0 0 25 0 1 Over Torque is detected when the output torque level exceeds the level set in Parameter 07 11 Inverter rated torque i...
Страница 74: ...s of the setting of parameter 08 00 2 RS 232communication RS232 interface is required a One to One communication A controller PC or PLC controls one inverter set 08 00 1 32 b Communication data parame...
Страница 75: ...to the existing speed reference The PID target value can be set by parameter 00 05 006 for example the frequency command target can be set from Operator keypad AI1 Analogue input or multi function an...
Страница 76: ...e deviation of target value detected value in unit time 09 04 Frequency command 6 D is equal to the deviation of detected values in unit time Frequency command 7 D is equal to the deviation of target...
Страница 77: ...dback value reaches the set point reset to 0 in 1 30 seconds and inverter stops The inverter will run again when the feedback value differs from the set point value 09 13 Allowable Integration Error M...
Страница 78: ...6 6KHz 10 10KHz 14 14KHz 3 3KHz 7 7KHz 11 11KHz 15 15KHz 4 4KHz 8 8KHz 12 12KHz Note 1 In applications where there is excessive audible noise from the motor or it is required to reduce electrical int...
Страница 79: ...lectromagnetism noise even lower Note When the inverter is running at high speed and high carrier frequency is selected then please set 10 04 1 this can reduce the IGBT switching losses heat loss 10 0...
Страница 80: ...Enable When inverter is temperature overrun 80 C on keypad display 11 00 01000 Carrier Frequency reduced 4K when inverter is temperature reduced less than 70 C Carrier Frequency resume Group11 keypad...
Страница 81: ...mal Places x xxx When 11 02 1 2 3 4 line speed is displayed while the inverter is running or stopped 11 03 Max PID Feedback Setting 0 999 11 04 Min PID Feedback Setting 0 999 Example 11 03 100 11 04 5...
Страница 82: ...is to23 as the elapsed time 1 is set The next hour will be carried to operation12 04 Meanwhile the recorded value will be cleared to 0000 and the record value of operation duration 2 will be 01 2 Des...
Страница 83: ...Auto _ Run Mode Frequency Command 1 0 400Hz 13 02 Auto _ Run Mode Frequency Command 2 0 400Hz 13 03 Auto _ Run Mode Frequency Command 3 0 400Hz 13 04 Auto _ Run Mode Frequency Command 4 0 400Hz 13 05...
Страница 84: ...13 39 Auto_ Run Mode Running Direction 7 0 STOP 1 forward 2 reverse 13 40 Auto_ Run Mode Running Direction 8 0 STOP 1 forward 2 reverse 13 41 Auto_ Run Mode Running Direction 9 0 STOP 1 forward 2 reve...
Страница 85: ...anel Frequency 3 01 15 Hz 13 01 30Hz 13 02 50Hz 13 03 20Hz 13 16 20s 13 17 25s 13 18 30s 13 19 40s 13 32 1 13 33 1 13 34 1 FWD 13 35 2 REV 13 04 13 15 0Hz 13 20 13 31 0s 13 36 13 47 0 B Periodic cycle...
Страница 86: ...ning from the unfinished step according to the setting of 13 00 4 6 If the inverter stops and re starts it will begin a new cycle and continue running according to the setting of 13 00 13 00 1 3 4 6 O...
Страница 87: ...uto_run function please set as below Example 1 00 03 00 04 1 external terminals 2 00 11 0 Operation modes of external terminals FWD STOP REV STOP Note this section 00 11 do not set 1 or 2 3 01 00 S1 0...
Страница 88: ...voltage too low 2 Pre charge resistor or fuse burnt out 3 Detection circuit malfunction 1 Check if the power voltage is correct 2 Replace the pre charge resistor or the fuse 3 Return the inverter The...
Страница 89: ...motor wiring and ground 5 the IGBT module damaged 1 Set a longer acceleration time 2 Replace inverter with one that has the same rating as that of the motor 3 Check the motor 4 Check the wiring 5 Rep...
Страница 90: ...correct settings for 06 01 07 05 08 1 Increase the motor capacity 2 set 06 01 07 05 08 correctly Inverter overload Excessive Load Increase the inverter capacity Over torque 1 Excessive Load 2 Incorrec...
Страница 91: ...restart the inverter 2 If the inverter is in communication mode and the Stop key is enabled 04 02 0 the inverter will stop in the way set by 04 01 when Stop key is pressed during operation and then f...
Страница 92: ...14 2 00 07 00 08 3 Setting error while Performing Auto tuning e g 00 03 00 04 0 00 05 00 06 0 1 Modify 10 11 10 13 or 10 14 2 Set 00 07 00 08 3 Set 00 03 00 04 0 and 05 00 06 0 during Auto tuning Mod...
Страница 93: ...for output terminals T1 T2 and T3 correct Wiring must match U V and W terminals of the motor Motor runs in wrong direction Are wiring for forward and reverse signals correct Check for correct wiring...
Страница 94: ...y Any fault display 3 fault values in 12 2 YES YES YES YES YES YES YES YES Is the main circuit DM intact Is the main circuit I G B T intact Is the DC input voltage controlling the power correct Replac...
Страница 95: ...lace the control board Replace the control board Replace the control board The inverter is failed Perform detailed check NO NO NO NO YES YES YES YES Is the frequency value displayed in operation unit...
Страница 96: ...ard Replace control board Perform detailed check The inverter is faulted NO NO YES YES YES YES YES YES NO NO NO NO NO NO YES Is the main circuit I G B T working Any visual abnormalities Is FWD LED ill...
Страница 97: ...d Replace the control board Perform detailed check The inverter is failed NO YES YES NO NO YES Is the main circuit fuse intact Any visual abnormalities Is FWD LED still illuminated after flash Connect...
Страница 98: ...Short circuited wiring The power is abnormal Incorrect wiring N310fault The operation switch is set to RUN position N310 fault N310 fault YES within 3 of the normal value YES voltage deviation between...
Страница 99: ...f the motor Motor runs unevenly Is the load fluctuating Does it happen during deceleration Are the output voltages between U V V W W U balanced Any mechanical vibration or gear backlash Is the acceler...
Страница 100: ...circuit correct Measure the voltage with a multi tester Voltage must conform with the specifications Improve input voltage Are secure parts loose Is the terminal base damaged External terminals and i...
Страница 101: ...ored in high capacity capacitors 1 Clean up the accumulation of any dust inside the inverter 2 Check if there are any loose terminal screws and tighten them 3 Insulation tests a Disconnect all leads c...
Страница 102: ...4002 XXX 5 0 4 2 N310 4003 XXX 7 5 3 6 N310 4005 XXX 10 0 2 2 N310 4008 XXX 15 0 1 42 N310 4010 XXX 20 0 1 06 N310 4015 XXX 30 0 0 7 6 2 DC reactor specification at input side DC inductance at input...
Страница 103: ...P5 0 5 0 375 60 200 8 218 2001 1 0 75 60 200 8 119 2002 2 1 5 150 100 10 119 2003 3 2 2 200 70 9 116 4001 1 0 75 60 750 8 125 4002 2 1 5 150 400 10 119 4003 3 2 2 200 250 8 128 4005 5 3 7 300 150 8 12...
Страница 104: ...cable connection B Operation procedure 1 Turn off the power Supply the following procedures should be performed after there is no display on the keypad 2 Remove the keypad 3 Connect the inverter and t...
Страница 105: ...Chapter 6 Peripherals Components 6 4 Extension KEYPAD installation 1 KEYPAD installation Dimensions Unit mm Tolerance 0 2mm...
Страница 106: ...Chapter 6 Peripherals Components 6 5 2 Keypad box Type 4KA82X341W01 installation Dimensions Unit mm Tolerance 0 2mm...
Страница 107: ...Chapter 6 Peripherals Components 6 6 3 Keypad in singles 1 Screw M3 2 N310 KeyPad 3 Fixing panel t 1 6mm 4 Unit mm Tolerance 0 2mm 2 3 5 M3 nut fixation or 2 M3 panel screw thread fixation...
Страница 108: ...s Components 6 7 4 Keypad together with Keypad box 1 Screw M3 2 N310 KeyPad Model 3 Fixing panel t 1 6mm 4 Inner screw M3 5 Keypad box Type 4KA82X341W01 6 Unit mm 2 3 5 M3 nut fixation or 2 M3 panel s...