MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
________________________________________________________________
TECO – Westinghouse Motor Company
7
Step 6
– Select Start / Stop Method of Control (Sn-04)
•
Before selecting this parameter,
ensure the inverter is in the STOP mode.
•
The
set-point
is selected by the keypad (
Sn-05=0
), and the
start / stop
method can be from the
keypad or external contact (
see Fig. 2a
).
NOTE: The set-point can also be set from an external
source but commonly it is set from the keypad.
•
The parameter
(Sn – 04)
is set to
= 0 (keypad),
as factory default
.
If
external
contact is desired,
follow the navigation procedure below to set
(Sn-04 = 1).