Tecnologic ‘K’ Series
UK Quick Programming Guide – K38/39 & K49
This guide should be used alongside the full engineering manual, appropriate to the instrument being
used, where more detailed information can be found.
Programming the Instrument
Tecnologic controllers are supplied with default programmable settings that may be suitable for your
application. However we recommend that you go through the programming process, as incorrect
programming could compromise its performance.
Programming level pass numbers:
1381
– Basic menu without 10 second time out
1400
– Advanced menu without 10 second time out
** Minus 1000 to the pass number to add time out function **
Note:
To reset instrument to factory default settings, press
P
for 5 seconds and dial in
-481.
Press
P
to confirm
Key
P button used for entering or moving to the next parameter.
Up & down buttons used for increasing or decreasing values.
U button is used for navigation between menus.
Holding down for 1 second will take you back one step.
Holding down for 2 seconds will take you out of configuration.