The installation menu contains the parameters that determine the complexity and typology of the welder
at which the control unit is working. Therefore, due to their importance, the access to this menu is
protected by a code.
INSTALLATION MENU
035
ENTER ACCESS CODE
* * * *
036
ACCESS CODE ERROR
ACCESS DENIED !!
If the user is not authorized and consequently does not know the access code, the following message is
displayed:
Keep in mind that only skilled personnel are permitted to edit the
following parameters to prevent damage to people or equipment.
k
The parameters can be edited only after having typed in the access code.
FIRST INSERTION DELAY FUNCTION
The FIRST INSERTION parameter shows the first insertion delay. This function permits to optimize the
balance of the mains consumption of the welder. After having selected this parameter, the value can be
adjusted from 1 to 99 with keys
a
and
s
. For more information refer to the specific chapter.
SERIAL COMM.
The user may choose whether to activate the serial data transmission port and how it is to be used,
connect a printer (PRT/232) or connect the control unit to a data supervision network (NET/485), or not
use this option (NONE).
NETWORK ADDRESS
This parameter indicates the identifying address of the control unit when connected in the network,
activating the aforesaid option.
PARAMETER DESCRIPTION VALUE
RANGE
FIRST INSERT.
1
st
Insertion delay
01 - 99
SERIAL COM.
Serial communication
PRT/232 - NET/485 - NONE
NETWORK ADDRESS
Network address
01 - 32
COIL RATIO
Rogowski ratio
X1 - X5 - X10
LOCK/END OUT
Output function
END - LOCK
FUNCTION REC.
Recall function 5
RIC5 - ODD - EVEN
LOW FORCE SQ.
Low force squeeze
ON - OFF
FORGE
Forging
ON - OFF
PROPORT. VALVE
Proportional valve
ON - OFF
PRESSURE RATIO
Pressure transducer for proportional 0.1 - 2.0