Troubleshooting
53
WARNING
Risk of injuries for persons due to heavy objects!
The components mentioned above are very heavy and bulky.
Always have several persons carry out the installation or dismantling or use
appropriate lifting devices!
Danger to personnel!
There is a risk of injury due to liquid under pressure, rotating parts, and high
electrical voltage in the unit.
•
Do not use the unit when the side panels are removed.
•
Open the side panels only in order to perform maintenance tasks and only
in compliance with the safety instructions.
Risk of injury due to rotating fans!
There is an increased risk of injury due to rotating fans when the unit is switched
on.
•
Keep housing closed during operation.
•
Never reach into the device when it is switched on.
•
Prior to opening the housing, ensure that the device is off and secured
against reactivation.
NOTE
Re-activation is permitted only after a thorough inspection of the cause of the
error and after the device has been tested.
11.2 General malfunctions
Fault
Cause
Note
No flow
The connecting lines and hoses etc.
are kinked.
Lay the connecting lines, hoses, etc. in
such a way that there is a sufficiently
large radius to avoid bending or kinking
of the connecting lines and hoses.
The shut-off valves are closed.
Check and open.
The diameters of the lines and hoses
are insufficient.
Check and replace.
Medium too warm/too
cold.
Temperature sensor removed from
sensor sheath.
Check.
Insert temperature sensor back into
sensor sheath.