ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 8 -
1.5
INSTALLATION APPROVALS
1.5.1
FIRE SYSTEM INSTALLATIONS
The panel must be installed and configured for operation in accordance with these instructions and the
applicable code of practice or national standard regulations for fire systems installation appropriate to the
country and location of the installation. In South Africa this would be SANS10139.
1.5.2
WIRING REGULATIONS
The panel and system must be installed in accordance with these instructions and the applicable wiring codes
and regulations (for example BS7671) appropriate to the country and location of the installation.
1.6
IDENTIFICATION OF PARTS
Figure 1
Identification of Major Panel Parts
1.7
INSTALLING THE ENCLOSURE
The panel is heavy when the batteries are installed. Use the appropriate fixing hardware to secure
the panel to the wall. Observe recommended lifting practices to guard against spinal injury.
See the table below for maximum weights:
Enclosure
Weight
Maximum
Battery
Overall Maximum Weight
ORYX202 & ORYX204 ABS
2.1 kg
7 Ah 2.5 kg
4.6 kg
ORYX202 & ORYX204 Weatherproof
7.4 kg
7 Ah 2.5 kg
9.9 kg
ORYX208 Standard
5.7 kg
17 Ah 5.5 kg
11.2 kg
ORYX208 Weatherproof
10.7 kg
17 Ah 5.5 kg
16.2 kg
▪
The Standard Enclosure covers are provided with a key lock assembly for securing the hinged door to the
back box. Insert and turn the key anti-clockwise to open the enclosure.