6-4 Dry Mode Operation
Dry operation remove moisture from indoor air running, in cooling mode, at a low level without reducing the
ambient temperature. This is done cycling ON and OFF indoor and outdoor units according to below.
ROOM
DRY LEVEL
TEMP
≥
SPT+2°C
LEVEL 0
Operation according to COOLING mode
CM on
< SPT+2°C
LEVEL 1
FMO on
≥
SPT-1°C
FMI switches between L and LL (30 seconds)
RV off
CM switches 9 minutes off and 3 minutes on
< SPT-1°C
LEVEL 2
FMO switches 9 minutes off and 3 minutes ON
≥
15°C
FMI switches off and L during CM operation
RV off
CM off
< 15°C
DRY OFF ZONE
FMO off
FMI off
RV off
SPT = Set Point Temperature
6-5 Fan Mode Operation
With this mode, the indoor fan is turned on while CM, FMO and RV stay off all the time. The user can select
between 3 speeds: HIGH, MEDIUM and LOW.
6-6 Auto Fan speed
With this option selected, the indoor fan speed changes automatically according to the difference between
the detected air temperature (RAT sensor) and the set point (SPT):
COOLING MODE
2
≤
(RAT – SPT):
HIGH speed
1
≤
(RAT – SPT)
<
2:
MEDIUM speed
(RAT – SPT)
<
1:
LOW speed
HEATING MODE
2
≤
(SPT - RAT):
HIGH speed
(SPT - RAT)
<
2:
MEDIUM speed
NOTE
SPT = Set Point Temperature
14