Technibel HKE 189R5I Скачать руководство пользователя страница 1

GB

INSTALLATION    MANUAL

Pub. ??.????.???.?

Inverter split air to water heat pump - Indoor unit

HKE 189R5

I

HKE 259R57

I

HKE 369R57

I

HKE 489R57

I

HKE 609R57

I

HKE 709R7

I

HKE 909R7

I

Содержание HKE 189R5I

Страница 1: ...GB INSTALLATION MANUAL Pub Inverter split air to water heat pump Indoor unit HKE 189R5I HKE 259R57I HKE 369R57I HKE 489R57I HKE 609R57I HKE 709R7I HKE 909R7I...

Страница 2: ...icking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminium fins on the air conditioner can cut...

Страница 3: ...iating maintenance or servicing on the installation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not...

Страница 4: ...12 Flow detector 13 Water inlet connection 14 Water outlet connection 15 Filling drainage of the water system 16 Safety valve drain connection 17 Flare gas connector 18 Flare liquid connector 19 Elect...

Страница 5: ...t board 12 Transformer 2 1 2 ELECTRICAL BOX Hydraulic filter 3 4 FF for HKE 189R and 259R 1 FF for HKE 369R 489R and 609R 1 1 4 for HKE 709R and 909R Outside temperature sensor Installed in a box with...

Страница 6: ...ection 3 4 male 3 4 male 1 male 1 1 4 male 1 1 4 male 3 Water circuit fill drain 1 2 male 1 2 male 1 2 male 1 2 male 1 2 male 4 Safety valve connection and drainage 5 Gas refrigerant connection 1 2 fl...

Страница 7: ...the unit remove the retaining screws 1 on each side and 1 on top 1 Slide the cover upward 2 until the bottom edge of the covers is aligned with the lower part of the rear support then pull it towards...

Страница 8: ...nected on the 2 zone module thus doing away with the need to install the control unit in zone 1 Wall mounting the unit must not be installed in corners on shelves or behind curtains near sources or he...

Страница 9: ...er the value indicated on the unit s identification plate for split systems refer to the installation instructions as the charge must consider the length of the connecting lines 4 In case of leakage d...

Страница 10: ...supplied 4 2 3 SAFETY VALVE CONNECTION The unit is equipped with a safety valve that opens if the pressure in the hydraulic system exceeds 3 bar A flexible hose 4 not supplied can be connected to the...

Страница 11: ...cable between the indoor unit and the outdoor unit Shielding Screws not supplied Metal clamp not supplied screwed to the terminal strip s support plate Grounding of the cable shielding SPW W706 906 N...

Страница 12: ...nstallation is connected Single phase Rsce Three phase Rsce Such that Sc Three phase short circuit power of the network Sc where Unominal nominal voltage between phases Z impedence of the network at t...

Страница 13: ...Indoor unit HKE Power supply amperages and cable sizes The sections are given as an indication only They have to be verified and adapted if necessary according to the installation conditions and the s...

Страница 14: ...ength 25 meters To be connected to the heating board A1 Note This sensor must be located outside in a location that is representative of the temperature to be measured on a wall facing North North wes...

Страница 15: ...NNECTION DIAGRAM Route the control cables on the right side of the board Pass the pilot wire 230 V on the left side of the board 1 2 CN1 230V CN2 CN3 CN4 CN8 CN7 CN6 CN5 3 5 4 3 2 1 4 3 2 1 4 5 3 2 1...

Страница 16: ...f the indoor unit 5 ACCESSORIES 5 1 WATER CONNECTION HOSES Length 1 m insulated female 3 4 code 70600054 for HKE 189R and 259R 1 code 70600055 for HKE 369R 489R and 609R 1 1 4 code 70600027 for HKE 70...

Страница 17: ...good condition of the apparatus No tools or other foreign objects inside the apparatus 6 2 CONFIGURATION AND PARAMETERISATION 6 2 1 AUTO ADDRESSING OF INDOOR AND OUTDOOR UNITS Set the control unit se...

Страница 18: ...ications of the hydraulic circuit force the pump to start as follows installation power ON Set the system control unit to OFF Press and hold the button for 5 seconds The circulator starts The circulat...

Страница 19: ...rate Improperly purged water system If the manual thermostat trips correct the fault then reset the thermostat as follows Turn off and lock out the unit Remove the cover The thermostats are located ag...

Страница 20: ...lacement with other than genuine parts all modifications of the refrigerating circuit all replacement of refrigerant by a fluid other than that indicated on the manufacturer s plate all use of the uni...

Страница 21: ...H2 H3 E1 E2 T T 230V A1 A2 KM2 A1 A2 KM3 A1 A2 KA1 R3 Q4 1 2 3 4 KM3 Q3 Q2 Q1 KM2 PE XA F1 CX6 F2 E1 CX5 4 CX3 2 P BUS CX1 A1 A2 KA2 S1 S2 S3 11 KA1 12 14 J1 11 KA2 12 14 S4 S5 S6 TR A1 M1 1 2 3 4 KM...

Страница 22: ...vent freezing of drainage water in cold weather regions t l o b r o h c n a e h t r o f 4 3 2 1 4 1 1 g i F o t r e f e R dimensions 0 1 M s t l o b r o h c n a h t i w t e e f e h t r o h c n a o t e...

Страница 23: ...ginning You must ensure that installation complies with all relevant rules and regulations 8 To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...polarenergi no P boks 117 9450 Hamnvik...