INSTALLATION - CONNECTIONS
ELECTRIC CONNECTIONS (to be done after refrigerant connections)
The indoor and external units must
have the electrical connections done as
shown in the wiring diagr ams provided
together with the devices. Use the elec-
tric cables with the features indicated
in this manual.
The unit mains line must be protected
by a thermalmagnetic circuit breaker.
The air conditioners must be po wered
with current 1 ~ 230 V 50 Hz and ha ve
an earth connection, the line v oltage
must remain within an area of tolerance
of ±10% of the nominal v alue. Use a
precabled po wer cable with a Sc huko
plug or an electric cable with
the same features.
To pr otect the units against short
circuits, install a thermalmagnetic
omnipolar circuit breaker (IG) cur ve C
250V with a minimum opening distance
of the contacts of 3mm
Follow the wiring diagr am pro vided
with the equipment.
HOLE IN THE WALL
- Make a hole in the w all with a diameter
big enough for passing the connections
and tilting slightly towards the bottom of
the external side
- Pass the pipes and the electric cables
through the hole, making sure that
no foreign bodies can enter in to the
pipes and that the pipes, the isolating
material and the electric cables cannot
be damaged.
Outdoor
Indoor
Choose the position for installing the
indoor unit in function with the la yout
of the room, an y ar chitectural limits
and needs of the client. Make sure the
position chosen allo ws maintenance
operations and filters cleaning.
When istalling use the fitting plates as a
template in order to identify the correct
position for the expansion plugs and for
the passage hole through the wall
The plastic co ver is pre-cut and if
necessary can be remo ved to allo w
the passage of the refriger ant lines and
cables.
During Cooling and Dehumidification
operating the condensate producing
on the internal heat exchanger is
collected in the container and unloaded
by means of the rubber pipe.
ELECTRIC CONNECTIONS FOR
THE
INDOOR UNIT
- Lift the front panel of the unit
- Unscrew the tting screws of the terminal
block cover.
- Insert the connection cable between the
indoor unit and the outdoor unit in the
back hole corresponding to the terminal
block.
- All cables must be connected as indicated
in the wiring diagram.
- Replace the terminal block cover panel
- Close the front panel.
INSTALLATION OF THE INDOOR UNIT
Pre cut 3
Pre cut 2
Pre cut 1
Left
Right
Rear left
Rear right
gas pipe
Pre cut
External jacket
condensate drain pipe Øest. 16mm
Pre cut
liquid pipes
Electric cablesi
template
template
Leveller
Template
reference
Left
>150 mm
Right
> 150 mm
Wall
Rear connection
hole
Rear connection
hole
Wall
CONDENSATE DRAIN LEFT OR RIGHT