9-2-3. Only outdoor unit does not run.
A. Check MODE selector switch of remote control unit.
B. Check setting temperature.
C. Check power relay in outdoor unit.
D. Check magnetic contactor in outdoor unit.
OK
NO
Is room temperature too low ?
Try to lower setting temperature by
temperature setting button cooler.
Outdoor unit still does
not run.
Remote control unit is defective.
• Try to run using another remote
control unit.
OK
• Measure coil resistance of power
relay.
Check indoor PCB Ass'y.
(PR)
• Check that MODE selector switch
is not set at "FAN".
If it is set at FAN,
Set to "COOL".
Outdoor unit does not run when air conditioner is in following conditions.
●
During thermo OFF (when the room temperature is below the set temperature).
●
During freeze prevention (for at least 6 minutes).
NOTE
OK
• Measure coil resistance of magnetic
contactor.
Check indoor PCB Ass'y.
(MG)