40
9-2. Air conditioner does not operate.
9-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
●
There is a possibility of ground fault.
●
Check insulation resistance.
If resistance value is 2M
Ω
or less, insulation is defective (“NO”).
1
Indoor
unit
Ground
Outdoor
unit
2
1
2
4
2
4
1
1
N
L2
L1
L3
N
L2
L1
L3
Power
supply
Power
supply
wiring
Inter-unit
wiring
Circuit
breaker
Measure insulation
resistance of electrical
parts in outdoor unit.
NO
NO
Set circuit breaker to OFF.
*
Measure insulation
resistance of electrical
parts in indoor unit.
1
Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
•
2
Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
•
•
•
Insulation of
outdoor unit
is defective.
Insulation of
indoor unit
is defective.
Содержание GR180C5TAA
Страница 34: ...Indoor Unit MCAV180C5VAA MCAV220C5VAA 31 ...