background image

29

10 05 665 - 00

PA 188 C  /  PA 268 X   -   230/1/50

10 05 666 - 00

PA 188 R  /  PA 268 R   -   230/1/50

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

A

B

C

D

E

F

G

H

I

J

K

L

M

ALIMENTATION 230V/1/50
POWER SUPPLY 230V/1/50

VENTILATION

FAN MOTOR

M1

C1

4

6

5

3

2

1

L

N

R

11

12

13

14

15

16

17

18

3

8

4

9

10

11

13

14

15

12

7

6

5

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

Ventilation  /  Fan

intérieure

indoor

extérieure

outdoor

V

anne

V

alv

e

Compresseur

Compressor

Chauf

fage électrique

Electr

ic heating

B1

KA1

G

T

KA2

1

2

B

M

M

R

PV
LS

MV
MS

GV
HS

(P

A 268)

(P

A 268)

R

W

W

KA2

O

KA1

Sonde  à distance / Remote sensor

Sonde dégivrage / Defrost sensor

M/A à distance / Remote ON/OFF

Alarme / Alarm

Commande VENTILATION EXTERIEURE
OUTDOOR UNIT FAN control

Commande VANNE / VALVE Control

Commande COMPRESSEUR / COMPRESSOR Control

Commande CHAUFFAGE / HEATING Control

COMMANDE A DISTANCE

REMOTE CONTROL

CARTE DE CONTROLE

CONTROL CARD

A1

4

3

(P

A 188)

(P

A 188)

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

A

B

C

D

E

F

G

H

I

J

K

L

M

2

11

6

31

32

33

12

4

T

5

1

PE

XA

XA

XA

XA

XA

XA

XA

XA

XA

XA

XA

F1

B1

M1

C1

4A 250V

5x20

W

(PA 268 )     (PA 188 )

(PA 268 )     (PA 188) 

R

N

N

3

4

PV
LS

MV
MS

GV
HS

1

~

W

M

W

M

ALIMENTATION 230V/1/50

POWER SUPPLY 230V/1/50

VENTILATION

FAN MOTOR

Commande COMPRESSEUR / COMPRESSOR Control

Commande CHAUFFAGE / HEATING Control

Содержание CP 188 R

Страница 1: ...1 10 11 341 GB 05 February 2003 CP V 188 268 SLIMLINE DUCTABLE SPLIT AIR CONDITIONER CP 188 R CP 268 R CPV 188 L CPV 268 X INSTALLATION INSTRUCTIONS...

Страница 2: ...e with local rules and professional standards 1 1 GENERAL SUPPLY CONDITIONS Generally speaking the material is transported at the consignee s risk The consignee must immediately provide the carrier wi...

Страница 3: ...max outdoor temperature GR 268 R PA 188 C PA 268 X PA 188 R PA 268 R 7 5 9 8 1 Blowing 2 Suction 3 Electrical box 4 Ventilation Materials Sheet metal casing Polyethylene insulation M1 Copper aluminium...

Страница 4: ...low return side PLENUM WITH ROUND SPIGGOTS A mm B mm C mm D mm Weight kg A mm B mm C mm Weight kg 874 174 80 3 5 874 210 36 75 2 5 A B C D A B C Number of spiggots PA 188 3 PA 268 4 1 070 215 310 870...

Страница 5: ...ossible The piping and the electric connections are easily accessible Dimension A If the filter kit is installed on the unit dimension A must be at least 250 mm to facilitate filter removal 3 1 2 POSS...

Страница 6: ...ding AVOID Excessive exposure to salty air or sulfuric gas Heat sources and extraction fans Projections of mud next to a roadway or path for example Areas where there is strong wind blowing against th...

Страница 7: ...oil to the appliance the compressor is filled with polyalcohol oil a special oil which cannot tolerate the presence of other oils 2 The instruments used for filling pressure measurements emptying und...

Страница 8: ...ons are given as an indication only They must be checked and adapted to suit the installation conditions according to existing standards 4 4 ELECTRICAL CONNECTION REMINDER The PA C and X models coolin...

Страница 9: ...cable clamps located under the electrical box Connect the wires to the terminal board according to the connexion diagram paragraph 12 GR 268 R Remove the side panel Connect the wires to the terminal...

Страница 10: ...erference and if the connection cable is over 3 m long you must install an inductor on the cable This inductor supplied with the PA must be installed in the appliance s electric box near the electroni...

Страница 11: ...mply with the minimum standby time of 3 minutes CAUTION Do not confuse Standby with cutting off the power If in doubt test the corresponding wires CAUTION Do not lay this cable near the power supply c...

Страница 12: ...thermostat bulb is intended for units installed horizontally If the unit is installed vertically the bulb must be moved Cut the plastic ties holding the bulb in place Place the bulb on the wire condu...

Страница 13: ...it s sleeve or heater kit using the holes in the plenum as a guide Secure the plenum using the 4 sheet metal screws provided 5 5 DOUBLE DEFLECTOR GRILLE Code K 60 M 029 Z The grille is mounted on the...

Страница 14: ...e box must be easily accessible unobstructed away from curtains cabinet shelving Avoid any direct sunlight on the box for example opposite a window exposure to drafts placing the unit directly in the...

Страница 15: ...00 100 6 1 WALL SUPPORT for GRV 180 L GR 188 R GR 268 R Code K 70 U 001 Z 1 After making sure that the fixing system used is suitable for the wall fix the 2 vertical brackets to the wall Make sure tha...

Страница 16: ...switch Condensing pressure regulator Accessories terminal strip Heat pump models only 8 1 PRINCIPLE The microprocessor manages the operation of the air conditioner It constantly compares the ambient...

Страница 17: ...t off is adjusted in the factory at 1K P2 enables adjustment up to 5 K The difference between the triggering of the thermodynamic heating and the possible make up heating is adjusted in the same way b...

Страница 18: ...utomatic indicated by red LED 14 Manual indicated by red LEDs 15 A AUTOMATIC VENTILATION MODE This mode is selected by the control as soon as it switches from Standby mode to Automatic mode by pressin...

Страница 19: ...storing power the control automatically returns to the previous configuration However to avoid incorrect switching the outputs are activated only 20 seconds afterwards permitting the device to measure...

Страница 20: ...s mode selection key 3 3 Adjust the set point by pressing keys 1 and 2 4 Press mode selection key 3 5 Press ventilation selection key 4 6 Press ventilation selection key 4 7 Press ventilation selectio...

Страница 21: ...exchanger excessively dirty air intake outlet or ducts blocked Correct the malfunction then reset the safety thermostat located under the electrical box by removing the cap and pressing the button as...

Страница 22: ...essure relative bar Inside wet bulb temperature C Low pressure relative bar Inside wet bulb temperature C High pressure relative bar Outside wet bulb temperature C Low pressure relative bar Outside we...

Страница 23: ...Inside temperature 20 C 14 16 18 20 22 24 11 13 15 17 19 21 23 25 14 16 18 20 22 24 3 4 5 6 High pressure relative bar Inside wet bulb temperature C Low pressure relative bar Inside wet bulb temperatu...

Страница 24: ...tancia Fernsteuerung K 60 D 016 Z 2 6 N 3 5 4 Commande distance Remote control Comando a distanza Mando a distancia Fernsteuerung K 60 D 025 Z 6 2 1 N 22 21 20 1 4 L N GRV 180 L 230 1 50 A C 5 1 2 11...

Страница 25: ...nza Mando a distancia Fernsteuerung K 60 D 016 Z 2 6 N 3 5 4 Commande distance Remote control Comando a distanza Mando a distancia Fernsteuerung K 60 D 025 Z 6 2 1 N 22 21 20 1 N GRV 265 X 230 1 50 A...

Страница 26: ...Sonda desescarche Enteisungssonde 4 3 2 1 7 6 5 9 8 4 3 2 1 7 6 5 10 9 8 10 14 12 11 17 16 18 E Sonde distance Remote sensor Sonda a distanza Sonda a distancia Externe Temperatursonde K 60 D 028 Z ou...

Страница 27: ...mote sensor Sonda a distanza Sonda a distancia Externe Temperatursonde K 60 D 028 Z ou or o o oder K 60 D 033 Z Marche Arr t distance hors fourniture Remote On Off not supplied Avviamento Arresto a di...

Страница 28: ...KA1 Auxiliary relay KA2 Auxiliary relay KM1 Fan contactor KM2 Compressor contactor KM3 Heating contactor KM4 Heating contactor NPR Phase sequence relay PCB Electronic card POW CL Filter PR1 Fan relay...

Страница 29: ...A2 O KA1 Sonde distance Remote sensor Sonde d givrage Defrost sensor M A distance Remote ON OFF Alarme Alarm Commande VENTILATION EXTERIEURE OUTDOOR UNIT FAN control Commande VANNE VALVE Control Comma...

Страница 30: ...Connecteur 2P rouge Connector 2P red Connecteur 2P jaune Connector 2P yellow Unit int rieu re Indoor unit Alimentation 400 3N 50 Power supply 400 3N 50 CCH G G N O W G 1 2 4 L N TP JV N JV JV 2 1 2 1...

Страница 31: ...N M NW U V W N 5 3 4 6 T1 T2 T3 Raccordement PA Connection PA Alimentation 400 3N 50 Power supply 400 3N 50 10 05 457 06 GRV 265 X 230 1 50 M2 M2 M1 K2 K2 RO 1 1 N B M S R C JV M N L NW L N M M N M N...

Страница 32: ...2 KM2 R1 KM1 EV1 5 6 3 4 3 4 1 2 1 2 01 12 01 12 01 16 01 16 01 16 U 14 W 01 6 01 8 11 T C1 C2 C5 C4 KA1 1 SD1 R L1 2 3 M L K J I H G F E D C B A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 XA...

Страница 33: ...sor connection Unit int rieure Indoor unit Alimentation prot g e 230V 1 T 50 Power supply 230V 1 Earth 50 10 05 662 00 GR 268 R 230 1 50 1 M1 M2 R S C C3 W P M G N W R KM2 B N KM1 1 R B N XA L XA XA N...

Страница 34: ...W XA PE Alimentation Power supply 400 3 50 230 1 50 W V U N PE 10 05 667 00 KIT CHAUFFAGE ELECTRIQUE ELECTRIC HEATING KIT 6 kW 230 1 50 400 3 50 10 05 678 00 KIT CHAUFFAGE ELECTRIQUE ELECTRIC HEATING...

Страница 35: ...ux BP 131 01601 Tr voux CEDEX France Phone 33 4 74 00 92 92 Fax 33 4 74 00 42 00 R C S Bourg en Bresse B 759 200 728 Due to our policy of continuous development our products are liable to modification...

Отзывы: