8.3.2 - OPERATING MODES

• The 5 available operating modes:

Standby

(indicated by yellow LED 9)

Automatic

(indicated by red LED 10)

Ventilation only

(indicated by red LED 11)

Cooling only

(indicated by red LED 12)

Heating only

(indicated by red LED 13)

• When powered up, the device is set at "Standby". In this mode, all the controller’s outputs are deactivated and the air-

conditioner is not is service. Only light 9 is lit.

• All mode selections on key 3 (by pressing it successively) are immediately indicated by a LED.

However, the device does not take into account the modification of the mode until after about 3 seconds.
Consequently, when rapidly going through the different modes, the device does not take into account the intermediate modes
and stays at its initial status.

A - AUTOMATIC MODE
• In this mode, the Cooling and Heating functions are selected automatically according to the difference between the set-point

and the ambient temperature (see preceding diagram).

• The set-point corresponds to the point where the compressor stops when in heating mode.
• The activated operating mode is indicated by light 7 for Heating and 8 for Cooling. These lights flash if a safety time delay

is in progress. They change to steady light when the unit is operating.

B - VENTILATION MODE ONLY
• In this mode, only the PA ventilator is in operation.
• The Heating/Cooling control is deactivated.

C - COOLING MODE ONLY
• In this mode, only the Cooling is in operation.
• The device does not heat.
• The cycle inversion valve is not activated.

D - HEATING MODE ONLY
• In this mode, only the Heating is in operation.
• The device does not cool.
• The cycle inversion valve is activated permanently.

8.3.3 - PA VENTILATION OPERATING MODES

• Two operating modes are available:

Automatic

(indicated by red LED 14)

Manual

(indicated by red LEDs 15)

A - AUTOMATIC VENTILATION MODE
• This mode is selected by the control as soon as it switches from "Standby" mode to "Automatic" mode, by pressing key 3.
• In this ventilation mode:

- ventilation speed is selected automatically according to the difference between the set-point and the ambiant temperature,
- ventilation stops when in the neutral zone between cold and hot,
- in HEATING and COOLING only modes, the ventilator is cut off at the point where these two functions are stopped,
- in VENTILATION ONLY, the operation is the same as for Cooling only, i.e. the ventilator is cut-off if the temperature falls

below the SET-POINT + NEUTRAL ZONE value.

B - MANUAL VENTILATION MODE
• This mode is selected by pressing key 4.
• In this mode, the ventilation operates continuously at the speed selected (3 speeds).

• It is possible to switch back to automatic ventilation mode by pressing on key 4 again.

NOTE:

Stopping the ventilation of the PA is delayed by 1 minute after stopping in Heating mode to ensure the evacuation
of residual heat.

8.3.4 - SET-POINT ADJUSTMENT

• The set-point is adjusted by using the + and - keys (references 1 and 2). The adjustment range is from 16 to 30

°

C.

• At each press, the LED display shifts by one position to the right (increase temperature) when pressing the + key or to the

left (decrease temperature) when pressing the - key.

• In STANDBY mode all the LED’s of the scale are off. By selecting any mode by using the push-button on the left, the display

will light and correspond to the last value selected.

• When first powering up and after selecting the operating mode, the value displayed is automatically 22

°

C.

• This is also the case after power has been cut-off for a period of 4 hours.
• As the control is equipped with a back-up accumulator, the display will indicate the last value selected after power

has been restored if the cut-off period is less then 4 hours.

Содержание CP 188 R

Страница 1: ...1 10 11 341 GB 05 February 2003 CP V 188 268 SLIMLINE DUCTABLE SPLIT AIR CONDITIONER CP 188 R CP 268 R CPV 188 L CPV 268 X INSTALLATION INSTRUCTIONS...

Страница 2: ...e with local rules and professional standards 1 1 GENERAL SUPPLY CONDITIONS Generally speaking the material is transported at the consignee s risk The consignee must immediately provide the carrier wi...

Страница 3: ...max outdoor temperature GR 268 R PA 188 C PA 268 X PA 188 R PA 268 R 7 5 9 8 1 Blowing 2 Suction 3 Electrical box 4 Ventilation Materials Sheet metal casing Polyethylene insulation M1 Copper aluminium...

Страница 4: ...low return side PLENUM WITH ROUND SPIGGOTS A mm B mm C mm D mm Weight kg A mm B mm C mm Weight kg 874 174 80 3 5 874 210 36 75 2 5 A B C D A B C Number of spiggots PA 188 3 PA 268 4 1 070 215 310 870...

Страница 5: ...ossible The piping and the electric connections are easily accessible Dimension A If the filter kit is installed on the unit dimension A must be at least 250 mm to facilitate filter removal 3 1 2 POSS...

Страница 6: ...ding AVOID Excessive exposure to salty air or sulfuric gas Heat sources and extraction fans Projections of mud next to a roadway or path for example Areas where there is strong wind blowing against th...

Страница 7: ...oil to the appliance the compressor is filled with polyalcohol oil a special oil which cannot tolerate the presence of other oils 2 The instruments used for filling pressure measurements emptying und...

Страница 8: ...ons are given as an indication only They must be checked and adapted to suit the installation conditions according to existing standards 4 4 ELECTRICAL CONNECTION REMINDER The PA C and X models coolin...

Страница 9: ...cable clamps located under the electrical box Connect the wires to the terminal board according to the connexion diagram paragraph 12 GR 268 R Remove the side panel Connect the wires to the terminal...

Страница 10: ...erference and if the connection cable is over 3 m long you must install an inductor on the cable This inductor supplied with the PA must be installed in the appliance s electric box near the electroni...

Страница 11: ...mply with the minimum standby time of 3 minutes CAUTION Do not confuse Standby with cutting off the power If in doubt test the corresponding wires CAUTION Do not lay this cable near the power supply c...

Страница 12: ...thermostat bulb is intended for units installed horizontally If the unit is installed vertically the bulb must be moved Cut the plastic ties holding the bulb in place Place the bulb on the wire condu...

Страница 13: ...it s sleeve or heater kit using the holes in the plenum as a guide Secure the plenum using the 4 sheet metal screws provided 5 5 DOUBLE DEFLECTOR GRILLE Code K 60 M 029 Z The grille is mounted on the...

Страница 14: ...e box must be easily accessible unobstructed away from curtains cabinet shelving Avoid any direct sunlight on the box for example opposite a window exposure to drafts placing the unit directly in the...

Страница 15: ...00 100 6 1 WALL SUPPORT for GRV 180 L GR 188 R GR 268 R Code K 70 U 001 Z 1 After making sure that the fixing system used is suitable for the wall fix the 2 vertical brackets to the wall Make sure tha...

Страница 16: ...switch Condensing pressure regulator Accessories terminal strip Heat pump models only 8 1 PRINCIPLE The microprocessor manages the operation of the air conditioner It constantly compares the ambient...

Страница 17: ...t off is adjusted in the factory at 1K P2 enables adjustment up to 5 K The difference between the triggering of the thermodynamic heating and the possible make up heating is adjusted in the same way b...

Страница 18: ...utomatic indicated by red LED 14 Manual indicated by red LEDs 15 A AUTOMATIC VENTILATION MODE This mode is selected by the control as soon as it switches from Standby mode to Automatic mode by pressin...

Страница 19: ...storing power the control automatically returns to the previous configuration However to avoid incorrect switching the outputs are activated only 20 seconds afterwards permitting the device to measure...

Страница 20: ...s mode selection key 3 3 Adjust the set point by pressing keys 1 and 2 4 Press mode selection key 3 5 Press ventilation selection key 4 6 Press ventilation selection key 4 7 Press ventilation selectio...

Страница 21: ...exchanger excessively dirty air intake outlet or ducts blocked Correct the malfunction then reset the safety thermostat located under the electrical box by removing the cap and pressing the button as...

Страница 22: ...essure relative bar Inside wet bulb temperature C Low pressure relative bar Inside wet bulb temperature C High pressure relative bar Outside wet bulb temperature C Low pressure relative bar Outside we...

Страница 23: ...Inside temperature 20 C 14 16 18 20 22 24 11 13 15 17 19 21 23 25 14 16 18 20 22 24 3 4 5 6 High pressure relative bar Inside wet bulb temperature C Low pressure relative bar Inside wet bulb temperatu...

Страница 24: ...tancia Fernsteuerung K 60 D 016 Z 2 6 N 3 5 4 Commande distance Remote control Comando a distanza Mando a distancia Fernsteuerung K 60 D 025 Z 6 2 1 N 22 21 20 1 4 L N GRV 180 L 230 1 50 A C 5 1 2 11...

Страница 25: ...nza Mando a distancia Fernsteuerung K 60 D 016 Z 2 6 N 3 5 4 Commande distance Remote control Comando a distanza Mando a distancia Fernsteuerung K 60 D 025 Z 6 2 1 N 22 21 20 1 N GRV 265 X 230 1 50 A...

Страница 26: ...Sonda desescarche Enteisungssonde 4 3 2 1 7 6 5 9 8 4 3 2 1 7 6 5 10 9 8 10 14 12 11 17 16 18 E Sonde distance Remote sensor Sonda a distanza Sonda a distancia Externe Temperatursonde K 60 D 028 Z ou...

Страница 27: ...mote sensor Sonda a distanza Sonda a distancia Externe Temperatursonde K 60 D 028 Z ou or o o oder K 60 D 033 Z Marche Arr t distance hors fourniture Remote On Off not supplied Avviamento Arresto a di...

Страница 28: ...KA1 Auxiliary relay KA2 Auxiliary relay KM1 Fan contactor KM2 Compressor contactor KM3 Heating contactor KM4 Heating contactor NPR Phase sequence relay PCB Electronic card POW CL Filter PR1 Fan relay...

Страница 29: ...A2 O KA1 Sonde distance Remote sensor Sonde d givrage Defrost sensor M A distance Remote ON OFF Alarme Alarm Commande VENTILATION EXTERIEURE OUTDOOR UNIT FAN control Commande VANNE VALVE Control Comma...

Страница 30: ...Connecteur 2P rouge Connector 2P red Connecteur 2P jaune Connector 2P yellow Unit int rieu re Indoor unit Alimentation 400 3N 50 Power supply 400 3N 50 CCH G G N O W G 1 2 4 L N TP JV N JV JV 2 1 2 1...

Страница 31: ...N M NW U V W N 5 3 4 6 T1 T2 T3 Raccordement PA Connection PA Alimentation 400 3N 50 Power supply 400 3N 50 10 05 457 06 GRV 265 X 230 1 50 M2 M2 M1 K2 K2 RO 1 1 N B M S R C JV M N L NW L N M M N M N...

Страница 32: ...2 KM2 R1 KM1 EV1 5 6 3 4 3 4 1 2 1 2 01 12 01 12 01 16 01 16 01 16 U 14 W 01 6 01 8 11 T C1 C2 C5 C4 KA1 1 SD1 R L1 2 3 M L K J I H G F E D C B A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 XA...

Страница 33: ...sor connection Unit int rieure Indoor unit Alimentation prot g e 230V 1 T 50 Power supply 230V 1 Earth 50 10 05 662 00 GR 268 R 230 1 50 1 M1 M2 R S C C3 W P M G N W R KM2 B N KM1 1 R B N XA L XA XA N...

Страница 34: ...W XA PE Alimentation Power supply 400 3 50 230 1 50 W V U N PE 10 05 667 00 KIT CHAUFFAGE ELECTRIQUE ELECTRIC HEATING KIT 6 kW 230 1 50 400 3 50 10 05 678 00 KIT CHAUFFAGE ELECTRIQUE ELECTRIC HEATING...

Страница 35: ...ux BP 131 01601 Tr voux CEDEX France Phone 33 4 74 00 92 92 Fax 33 4 74 00 42 00 R C S Bourg en Bresse B 759 200 728 Due to our policy of continuous development our products are liable to modification...

Отзывы: