Caution Before Connecting Tubes Tightly

(1) Apply a sealing cap or water-proof tape to prevent

dust or water from entering the tubes before they
are used.

(2) Be sure to apply refrigerant lubricant to the match-

ing surfaces of the flare and union before connect-
ing them together. This is effective for reducing
gas leaks. (Fig. 5-4)

(3) For proper connection, align the union tube and

flare tube straight with each other, then screw in
the flare nut lightly at first to obtain a smooth
match. (Fig. 5-5)

Adjust the shape of the narrow tube (liquid tube)
using a tube bender at the installation site and
connect it to the narrow tubing side (liquid tubing
side) valve using a flare.

Cautions During Brazing 

Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during
the brazing process. (Oxygen, carbon dioxide
and Freon are not acceptable.)

Do not allow the tubing to get too hot during
brazing. The nitrogen gas inside the tubing
may overheat, causing refrigerant system
valves to become damaged. Therefore allow
the tubing to cool when brazing.

Use a reducing valve for the nitrogen cylinder.

Do not use agents intended to prevent the for-
mation of oxide film. These agents adversely
affect the refrigerant and refrigerant oil, and
may cause damage or malfunctions.

5-2.  Connecting Tubing Between Indoor and Out-

door Units 

(1) Tightly connect the indoor-side refrigerant tubing

extended from the wall with the outdoor-side tub-
ing.

(2) To fasten the flare nuts, apply specified torque as

at right:

When removing the flare nuts from the tubing con-
nections, or when tightening them after connecting
the tubing, be sure to use 2 monkey wrenches or
spanners as shown. (Fig. 5-6) 
If the flare nuts are over-tightened, the flare may be
damaged, which could result refrigerant leakage
and cause in injury or asphyxiation to room occu-
pants.

When removing or tightening the wide tube flare
nut, use 2 monkey wrenches together: one at the
wide tube flare nut and one at part A.(Fig. 5-7)

For the flare nuts at tubing connections, be sure to
use the flare nuts that were supplied with the unit,
or else flare nuts for R410A (type 2). The refriger-
ant tubing that is used must be of the correct wall
thickness as shown in the table at right. 

Apply refrigerant 
lubricant here and here

Fig. 5-4

Flare nut

Union

Fig. 5-5

Fig. 5-6

Indoor unit

Outdoor unit

Spanner

Torque wrench

Tube diameter

φ

6.35 (1/4")

φ

9.52 (3/8")

φ

12.7 (1/2")

φ

15.88 (5/8")

Tightening torque, 
approximate

14 – 18 N 

·

 m

(140 – 180 kgf 

·

 cm)

34 – 42 N 

·

 m

(340 – 420 kgf 

·

 cm)

49 – 61 N 

·

 m

(490 – 610 kgf 

·

 cm)

68 – 82 N 

·

 m

(680 – 820 kgf 

·

 cm)

0.8 mm

0.8 mm

0.8 mm

1.0 mm

Tube thickness

Because the pressure is approximately 1.6 times
higher than conventional refrigerant pressure, the
use of ordinary flare nuts (type 1) or thin-walled
tubes may result in tube rupture, injury, or asphyxi-
ation caused by refrigerant leakage.

In order to prevent damage to the flare caused by
over-tightening of the flare nuts, use the table
above as a guide when tightening.

When tightening the flare nut on the narrow tube,
use a monkey wrench with a nominal handle length
of 200 mm.

A

Fig. 5-7

Содержание CAFP125R5IA Series

Страница 1: ...37 4163 266 0 INSTALLATION MANUAL MARZO 2005 Split system air conditioner CAFP125R5IA CAFP165R5IA CAFP185R5IA...

Страница 2: ...door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Room...

Страница 3: ...y curtailing heat and carrying power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant com pared to conventional individual air conditioners If a...

Страница 4: ...NERAL 4 1 1 Tools Required for Installation not supplied 1 2 Accessories supplied with the unit 1 3 Type of Copper Tube and Insulation Material 1 4 Additional Materials Required for Installation 2 DIM...

Страница 5: ...Electrical components box Refrigerant tubing side Fresh air intake side Refrigerant tubing joint NARROW tube Refrigerant tubing joint WIDE tube Condensate drain piping 2 DIMENSIONS mm REFRIGERANT TUBI...

Страница 6: ...e piping on the unit side when connecting the drain pipe The pipe should not be allowed to hang unsupported from its con nection to the unit Fasten the pipe to a wall frame or other support as close t...

Страница 7: ...witch with safety fuses Fresh air flow must be about 10 of the total air flow to avoid operating problems and noise Open the knock out hole fix a 70 mm flange on the unit and connect the thermically i...

Страница 8: ...y dangerous The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes 7 Regulations on wire diameters differ from locality to l...

Страница 9: ...Ground C Ground C Ground C Ground 2 1 N L Outdoor unit INV unit 1 2 1 2 1 2 R2 R1 R2 R1 R2 R1 R2 R1 NOTE 1 Refer to Section 5 2 Recommended Wire Length and Wire Diameter for Power Supply System for th...

Страница 10: ...ts except any one of the outdoor units When shipping In shorted condition Otherwise the communication of S net link system is not performed For a system without link no con nection wiring between outd...

Страница 11: ...ensure that all wiring is tightly connected When connecting each power wire to the terminal fol low the instructions on How to connect wiring to the terminal and fasten the wire securely with the fixi...

Страница 12: ...cut approx 30 50 cm longer than the tubing length you esti mate 2 Remove burrs at the end of the copper tube with a tube reamer or file This process is important and should be done carefully to make a...

Страница 13: ...de tub ing 2 To fasten the flare nuts apply specified torque as at right When removing the flare nuts from the tubing con nections or when tightening them after connecting the tubing be sure to use 2...

Страница 14: ...lation tape white supplied Sealer supplied Flare insulator supplied Tube insulator not supplied Heat resistant 120 C or above Vinyl clamps supplied Flare nut The procedure used for installing the insu...

Страница 15: ...all As you wrap the tubing overlap half of each previous tape turn 3 Clamp the tubing bundle to the wall using 1 clamp approx each meter Fig 5 11 Do not wind the armoring tape too tightly since this w...

Страница 16: ...CN2 provided with it fig 1 2 Connect in the same place the wire coming from grille assembly fig 2 3 Close the operation controller and fix it inside the unit Fasten the wires using the provided clamp...

Страница 17: ...with a vacuum cleaner brush or wipe them Indoor unit with a clean soft cloth If these parts are stained use a clean cloth moistened with a mild liquid detergent When clean ing the air outlet side be c...

Страница 18: ...Operation button is turned off 4 Press the button again 5 The wired remote control unit or heat pump is The inspection mark and the letters E F H L P in combination with numbers appear the LCD of the...

Страница 19: ...d air et la sortie de l unit int rieure avec la brosse d un aspirateur ou les essuyer avec un chiffon propre et doux Si ces parties sont sales nettoyez les avec un chiffon propre humect d un d tergen...

Страница 20: ...Cha ne de s curit Filtre air Entretien apr s une p riode d inactivit prolong e Entretien avant une p riode d inactivit prolong e V rifiez l arriv e d air et la sortie d air des unit s int rieure et ex...

Страница 21: ...1 Coupure de courant 1 Apr s une panne de courant appuyez sur le bouton de marche arr t de fonctionnement de la t l commande avec fil 2 Le disjoncteur a fonctionn 2 Prenez contact avec un service apr...

Страница 22: ...lass und auslassseite der Inneneinheit mit einer Staubsauger b rste bzw wischen Sie sie mit einem sauberen weichen Tuch ab Wenn die erw hnten Teile schmutzig sind diese mit einem sauberen Tuch abwisch...

Страница 23: ...ufteinlassgitter Sicherheitskette Luftfilter Pflege Wenn das Ger t ber l ngere Zeit nicht verwendet wurde Pflege Wenn das Ger t ber l ngere Zeit nicht verwendet werden soll berpr fen Sie Lufteinl sse...

Страница 24: ...Das Klimager t l uft berhaupt nicht 1 Keine Stromzufuhr 1 Dr cken Sie nach einem Stromausfall die Betriebstaste ON OFF auf der verdrahteten Fernbedienung 2 Der Fehlerstromschutzschalter wurde ausgel...

Страница 25: ...e il lato della presa d aria e dell uscita d aria dell unit interna con una spazzola aspi rapolvere o con un panno pulito e morbido Rimuovere le eventuali macchie presenti su corpo e griglia dell unit...

Страница 26: ...ivo di bloccaggio Viti Griglia della presa d aria Catena di sicurezza Filtro dell aria Cura dopo un periodo di inattivit prolungato Cura prima di periodo di inattivit prolungato Controllare le prese d...

Страница 27: ...Dopo una mancanza di corrente premere il pulsante di accensione spegnimento ON OFF del telecomando cablato 2 Il salvavita scattato 2 Rivolgersi al centro di assistenza 3 La tensione di rete insufficie...

Страница 28: ...ssion rio ou centro de repara es Limpe o lado de entrada e sa da de ar da unidade interior com um aspirador ou com um pano macio e limpo Se estas partes estiverem muito sujas utilize um pano limpo hum...

Страница 29: ...necess rias Patilha Parafusos Grelha de entrada de ar Cadeia de seguran a Filtro de ar Aten o ap s um per odo de inactividade prolongado Aten o antes de um per odo de inactividade prolongado Verifiqu...

Страница 30: ...Falha de alimenta o 1 Ap s uma falha de corrente el ctrica pressione o bot o de opera o ON OFF na unidade de controlo remoto com fios 2 O disjuntor de fugas foi activado 2 Contacte o servi o de assis...

Страница 31: ...31 Greek...

Страница 32: ...32 Greek...

Страница 33: ...33 Greek...

Страница 34: ...s Limpie los lados de entrada y salida de aire de la unidad interior con el cepillo de una aspi radora o l mpielos con un pa o limpio y suave Si estas partes est n muy sucias utilice un pa o limpio hu...

Страница 35: ...illos Rejilla de entrada de aire Cadena de seguridad Filtro de aire Cuidado despu s de un periodo de inactividad prolongado Cuidado antes de un periodo de inactividad prolongado Compruebe las entradas...

Страница 36: ...ase en contacto con un electricista o con su concesionario 4 El bot n de operaci n est desactivado 4 Pulse el bot n otra vez 5 La unidad de mando a distancia al mbrica o la bomba de calor est funciona...

Отзывы: