23). High signal level of sensor guide point
Parameter Code number: 23
Parameter range: [0-9], the default value is 5
Read only.
24). Low signal level of sensor guide point
Parameter Code number: 24
Parameter range: [0-99], the default value is 12
Read only.
25).Gain Serve
Parameter code number: 25
Parameter range: [0-30], the default value is 1
The larger this parameter is , the slower this guide responds, reduce this value to speedup reasonse of web guide.
26).reserved for future use
Parameter code number:26
27).reserved for future use
Parameter code number:27
28).End-of-Travel Limit
Parameter Code number: 28
Parameter range: [10-40], the default value is 10
This parameter is used to set the distance that the actuator can drive under manual mode. The higher this value is set,
the farther in or out the actuator will travel before it reaches the Out-of travel limit.
29).reserved for future use
Parameter code number:29