Tech Controllers ST-979 Скачать руководство пользователя страница 25

ST-979 user’s manual 

 

25 

 

VI.a) 

 

Fuel level calibration 

Conducting fuel level calibration properly enables the user to view the current level of fuel on the 
controller screen. The first step involves filling the fuel tank up and selecting the option Fuel tank 
full. 
The controller remembers the level as full (100%).   
 

When there is no fuel left in the tank after a period of CH boiler operation, the user should 

select the option Fuel tank empty. In this way the fuel tank is calibrated and the controller will 
automatically inform the user about the current fuel level. After a fuel level panel is selected in 
the main screen, the display shows the estimated amount of fuel left (%) and the expected time 
needed for the fuel to be used up (days and hours).  
 

Such calibration is  usually performed  only once. When the fuel tank is filled again, it is 

enough to select the option Fuel tank full in the user’s menu. 
 

VI.a) 

 

External temperature correction 

External  sensor  calibration  should  be  performed  during  installation  or  after  a  longer  period  of 
using  the  regulator  when  the  temperature  measured  by  the  sensor  is  different  from  actual 
temperature. The range of regulation is from -10 ºC to +10 ºC. 
Averaging time parameter defines the frequency of sending temperature data from the sensor to 
the controller.  
 

VI.b) 

 

GSM module 

 

NOTE 
This  type  of  control  is  available  only  after  purchasing  and  connecting  an  additional 
controlling module ST-65 which is not included in the standard controller set.

 

 
GSM Module is an optional device which, cooperating with the controller, enables the user remote 
control of the CH boiler operation via mobile phone. The user is sent an SMS each time an alarm 
occurs. Moreover, after sending a certain text message, the user receives feedback on the current 
temperature of all the sensors. Remote change of the set temperatures is also possible after the 
authorisation code is entered.  

GSM Module may operate independently of the CH boiler controller. It has two additional 

inputs with temperature  sensors,  one contact  input to be used  in any configuration (detecting 
closing/opening  of  contacts)  and  one  controlled  output  (e.g.  a  possibility  of  connecting  an 
additional contractor to control any electric circuit)  

When  any  of  the  temperature  sensors  reaches  the  pre-set  maximum  or  minimum 

temperature, the module automatically sends an SMS message with such information. 

A similar procedure is used in the case of opening or closing of the contact input, which 

may be used as a simple means of property protection.  

If ST-979 controller is equipped with GSM module, it should be activated by selecting ON 

option (MENU>Fitter's menu>GSM Module>ON). 
 

VI.c) 

 

Internet module 

 

NOTE  
This  type  of  control  is  available  only  after  purchasing  and  connecting  an  additional 
controlling module ST-505 which is not included in the standard controller set. 

 

Internet module is a device enabling the user remote control of the CH boiler via the Internet at 
www.emodul.pl.  The  user  controls  the  status  of  all  CH  boiler  system  devices  on  the  home 
computer screen and the operation of each device is presented in the form of animation.  

Apart from the possibility to view the temperature of every sensor, the user can change 

the set temperature values for both the pumps and the mixing valves etc.  

The installation process is intuitive. Connect the module and go to Fitter’s menu  of the 

main controller to activate the Internet module (Menu>>Fitter’s menu>>Internet module>>ON).  

Once Registration option is selected, the device generates a code which must be entered 

on the website.  
 

Содержание ST-979

Страница 1: ...ST 979 user s manual 1...

Страница 2: ...ance of the electric motors as well as the insulation resistance of the cables The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure the...

Страница 3: ...Controlling DHW pump Controlling two additional pumps additional CH DHW floor circulating or CH boiler protection pump Weather based control Weekly control Cooperation with a room regulator offering t...

Страница 4: ...ain situations e g after periodical cleaning of the furnace during controller operation There are four stages of the fire up process 1 Blow by In this stage the fan works at full speed in order to cle...

Страница 5: ...operate according to user s settings Main menu Modulation settings 30 modulation Damping Damping process is independent of the current operation algorithm It may be activated by the user in the main...

Страница 6: ...ation settings Operation algorithm Modulation 30 Modulation 60 Modulation100 Manual mode Igniter Blow Blow force Feeder Internal feeder Grate Ash remover Cleaning CH pump DHW pump Additional pump 1 Ad...

Страница 7: ...s 3 C entering sustain mode takes place at the temperature of 60 C whereas returning to the operation mode takes place at 57 C V d 3 Pre set DHW temperature This function is used to define the pre set...

Страница 8: ...boiler operates in sustain mode i e above the pre set temperature V e 5 Pause in sustain mode This option is used to set the feeder pause time when the CH boiler operates in sustain mode operating ab...

Страница 9: ...ds of CH boiler operation on particular days of the week with the accuracy of 30 minutes During the periods of inactivity the CH boiler remains damped regardless of other factors e g signal from the r...

Страница 10: ...ase by 50 C so it will be 650 C NOTE In order for the weekly control to function properly it is necessary to set current time and day of the week in Fitter s menu Time settings Delete This function en...

Страница 11: ...rovided that the pre set buffer temperature bottom has also been reached Pre set temperature bottom This function enables the user to define the pre set temperature for the lower part of the buffer se...

Страница 12: ...bles the user to adjust the brightness of the blank screen within the range of 3 50 V l 4 Blanking time This function enables the user to set the screen blanking time V l 5 Software update USB port en...

Страница 13: ...n module controlling the mixing valve It is possible to connect two additional modules for controlling valves e g ST 431N There is a range of parameters allowing the user to adjust the valve operation...

Страница 14: ...regulator Room reg temp lower Room temperature difference Change in set temperature Weather based control Valve pump Always ON Always OFF ON above threshold Switch on temperature Return protection Mi...

Страница 15: ...ng plate Additional valve 1 2 Registration Valve OFF Valve type CH Floor Opening time Room regulator Control without room regulator Standard TECH regulator Proportional TECH regulator Standard valve r...

Страница 16: ...ropriate plugs for RS socket Standard valve regulator This option should be selected if the valve will be controlled by a two state room regulator without RS communication Room reg temp lower This fun...

Страница 17: ...he pre set switch on temperature If the pump is to be activated above the threshold the user should also define the threshold temperature of pump activation VI a 7 Return protection This function enab...

Страница 18: ...HW valve If the sensor indicates a change in temperature deviation from the pre set value the electric valve will open or close by the pre set stroke in order to return to the pre set temperature VI a...

Страница 19: ...ated It is switched off when the temperature drops to 35 C Sensor selection It allows the user to decide which sensor should provide data for activation of the additional CH pump Room regulator This o...

Страница 20: ...ontrolling the operation of the device connected to the additional contact pre set temperature VI b 3 Circulating pump Once this option is selected the additional pump serves as the circulating pump T...

Страница 21: ...ators to the controller VI c 1 TECH regulator Select this option if you connect a room regulator with RS communication Such a regulator enables the user to view current CH boiler parameters and change...

Страница 22: ...e user to check if the cleaning device works properly by activating it for a specified period of time VI f Ash remover Ash removing procedure is activated once ON option is selected The user defines t...

Страница 23: ...Activated when the external temperature drops to the level defined in Boiler 1 activation temperature minus Hysteresis value 3 Activated when the external temperature drops to the level defined in Boi...

Страница 24: ...ers are active Once the pre set temperature is reached the boilers are selectively disabled every 20 minutes The deactivation procedure is repeated until one of these conditions is met 1 CH temperatur...

Страница 25: ...oreover after sending a certain text message the user receives feedback on the current temperature of all the sensors Remote change of the set temperatures is also possible after the authorisation cod...

Страница 26: ...utomatically unlocks itself In the case when this sensor is damaged or overheated the fan is also disconnected In the case of CH boiler protection in a closed system a STB type temperature limiter is...

Страница 27: ...2 Power consumption W 9 3 Ambient temperature O C 10 50 4 Circulating pump output load A 0 5 5 Fan output load A 0 6 6 Range of temperature measurement O C 0 85 7 Accuracy of measurement O C 1 8 Range...

Страница 28: ...DHW hysteresis 7 V d 5 Pump switch on temperature 7 V e Operation settings 8 V e 1 Operation algorithm 8 V e 2 Feeding pause 8 V e 3 Blow force 8 V e 4 Operation in sustain mode 8 V e 5 Pause in susta...

Страница 29: ...2 Opening time 15 VI a 3 Valve type 16 VI a 4 Room regulator 16 VI a 5 Weather based control 17 VI a 6 Valve pump 17 VI a 7 Return protection 17 VI a 8 CH boiler protection 17 VI a 9 Opening direction...

Страница 30: ...settings 24 VI b 2 Date settings 24 VI a Fuel level calibration 25 VI a External temperature correction 25 VI b GSM module 25 VI c Internet module 25 VI a Factory settings 26 VII Protections 26 VII a...

Страница 31: ...2014 p 357 Directive 2014 30 EU of the European Parliament and of the Council of February 26 2014 on the harmonisation of the laws of Member States relating to electromagnetic compatibility EU Journa...

Страница 32: ...TECH 32...

Отзывы: