Bypass 

 an option needed in the absence of a buffer, providing the heat pump with an appropriate heat capacity. 

 It relies on sequential opening of subsequent zones every specified time. 

 

 

Floor pump

 

 activate/deactivate floor pump

 

 

Cycle time

 

 determine the operating time of the floor pump with the bypass function active.

 

4.15.

 

FACTORY SETTINGS 

The function allows you to return to the 

fitter’s

 menu settings saved by the manufacturer. 

5.

 

SERVICE MENU 

The driver service menu is only available to authorized persons and is protected by the proprietary code of Tech Sterowniki. 

6.

 

FACTORY SETTINGS 

The function allows you to return to the default settings of the controller, as defined by the manufacturer. 

7.

 

SOFTWARE VERSION 

When this option is activated, the manufacturer's logo will appear on the display, along with the controller software version 
number. The software revision is required when contacting the Tech Sterowniki service. 

VII.

 

ALARM LIST 

 
 

Alarm

 

Possible cause

 

How to fix it

 

Sensor  damaged  (room  sensor,  floor 
sensor) 

Sensor shorted or damaged 

- Check the connection with the sensor 

-  Replace  the  sensor  with  a new  one  or 
contact the service staff if necessary. 

No  communication  with  sensor/ 
wireless regulator 

- No range 

- No battery 

- Flat battery 

- Put  the sensor/regulator in a  different 
place 

- Insert batteries in the sensor/regulator  

The  alarm  deactivates  automatically 
when communication is established.  

No  communication  with  module/ 
control panel / wireless contact 

No range 

- Put the device in a different place or use 
a repeater to extend the range. 

The  alarm  deactivates  automatically 
when communication is established.  

No Open Therm communication 

- Communication cable damaged 

- Gas boiler switched off or damaged 

Check the connection with the gas boiler. 
Contact the service staff if necessary. 

Software update 

System  communication  versions  in 
the two devices are not compatible 

Update  the  software  to  the  latest 
version. 

 

 

STT-868 actuator alarm 

ERROR #0 

Flat battery in the actuator 

 

Replace the batteries 

 

ERROR #1 

Some mechanical or electronic 
parts have been damaged 

 

Contact the service staff 

 

ERROR #2 

- No piston controlling the valve  
- Too big stroke (movement) of the 
valve  
- The actuator has been incorrectly 
mounted on the radiator  

- Install a piston controlling the actuator  
- Check the valve stroke  
- Install the actuator correctly  
- Replace the valve on the radiator 

 

Содержание EU-L-X WiFi

Страница 1: ...EU L X WiFi...

Страница 2: ...4 5 Manual mode 25 4 6 External sensor 25 4 7 heating stopping 25 4 8 Potential free contact 26 4 9 Pump 26 4 10 Heating cooling 26 4 11 Anti stop settings 26 4 12 Maximum humidity 26 4 13 Language 2...

Страница 3: ...The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure the plug is disconnected from the power supply during storm Any use other than spe...

Страница 4: ...number of functions support for EU R 12b EU R 12s and EU F 12b cable regulators support for floor temperature sensors support for external sensors and weather controls support for wireless window sens...

Страница 5: ......

Страница 6: ...connections Before working on the controller disconnect its power supply and secure it against accidental switching on CAUTION Incorrect wiring may damage the controller An illustrative diagram showi...

Страница 7: ...d into the right terminal of the sensor connector as seen from the front of the controller and depicted in attached images The second terminal of the capacitor is screwed into the terminal of the left...

Страница 8: ...r in the ON position in the controller and the last of the regulators When connecting regulators to a controller located in the middle of the transmission line terminate switch the jumper to the ON po...

Страница 9: ...ime can be adjusted from the network automatically Step 4 Configure temperature sensors room regulators In order for the EU L X WiFi controller to support a given zone it must receive information abou...

Страница 10: ...s the operation parameters between the zones 3 button used to browse the menu functions or increase the value of the edited parameters This button also switches the operation parameters between the zo...

Страница 11: ...cooling depending on the mode the digit flashes If an alarm occurs in a given zone an exclamation mark will be displayed instead of a digit To view the current operating parameters of a specific zone...

Страница 12: ...ature The set temperature in the zone results from the settings of a specific mode of operation in the zone i e the weekly schedule However it is possible to turn off the schedule and set a separate t...

Страница 13: ...ing the MENU button Use the MENU button to go to the settings of the time intervals and the set temperature that will be valid for the specified time interval set it using the arrows confirm with the...

Страница 14: ...steresis is 1 C The room sensor will start to indicate room underheating after the temperature drops to 22 C Calibration Room sensor calibration is carried out during assembly or after a longer period...

Страница 15: ...s information to automatically activate the heating in advance of the time required to reach the set temperatures This system does not require any involvement on the part of the user and precisely res...

Страница 16: ...n the zone temperature reaches the set point Once the set point is reached the temperature in the zone will start to drop When it reaches 21 C set temperature minus hysteresis value the actuator will...

Страница 17: ...tration an additional Information function appears where the user can view the sensor parameters e g battery status range etc It is also possible to delete a given sensor or all at the same time 4 1 8...

Страница 18: ...llation from overheating 4 2 ADDITIONAL CONTACTS The function allows you to handle additional contacts First of all it is necessary to register such a contact 1 6 pcs To do this select the Registratio...

Страница 19: ...e Calibration This function can be used to calibrate the built in valve e g after prolonged use During calibration the valve is set to a safe position i e for the CH valve and the Return protection ty...

Страница 20: ...y in a short circuit while the full opening of the valve 100 means that the short circuit is closed and the water flows through the entire central heating system CAUTION If the Boiler Protection is of...

Страница 21: ...When this function is checked the controller will operate according to the Room regulator temperature lower parameter Room regulator temp lower In this setting set the value by which the valve will l...

Страница 22: ...take into account the Self of the valve module or the Main sensor Only in slave mode Boiler protection This provides protection against excessive CH temperature and is intended to prevent dangerous i...

Страница 23: ...e deviations set are in the range of 10 C To enable weekly control select and check Mode 1 or Mode 2 Detailed settings of these modes can be found in the following sections of the submenu Set Mode 1 a...

Страница 24: ...on The user can control the operation of various devices and change some parameters using the emodul pl application The device has a built in Internet module After switching on the Internet module and...

Страница 25: ...to 10 C with a step of 0 1 C In the case of a wireless sensor the subsequent parameters relate to the range and level of the battery 4 7 HEATING STOPPING Function to prevent actuators from turning on...

Страница 26: ...operating mode Heating all zones are heated Cooling all zones are cooled Automatic the controller switches the mode between heating and cooling based on the two state input 4 11 ANTI STOP SETTINGS Thi...

Страница 27: ...sensor Replace the sensor with a new one or contact the service staff if necessary No communication with sensor wireless regulator No range No battery Flat battery Put the sensor regulator in a differ...

Страница 28: ...the controller has been installed properly Replace the batteries Calibrate actuator again by holding the communication button until the third flash of green light Call the service staff ERROR 3 Calib...

Страница 29: ...arried out by a qualified installer After changing the software it is not possible to restore the previous settings Do not turn off the controller while updating the software IX TECHNICAL DATA AC1 loa...

Страница 30: ...equipment implementing provisions of Directive EU 2017 2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011 65 EU on the restriction of the use of certain ha...

Страница 31: ......

Страница 32: ......

Отзывы: