background image

TECDrive TEC-3 User Guide Revision 1.20 

 

www.tecmotors.co.uk/tecdrive 

21

 

 

6

 
Pa
ra

m

e

ter

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-46 

PI Feedback Source Select 

Selects the source of the feedback signal to be used by the PI controller. 

0: Analog Input 2

 (Terminal 4) Signal level readable in P00-02. 

1 : Analog Input 1

 (Terminal 6) Signal level readable in P00-01 

2: Motor Current

. Scaled as % of P-08. 

3 : DC Bus Voltage

 Scaled 0 

 1000 Volts = 0 

 100% 

4: Analog 1 

 Analog 2

. The value of Analog Input 2 is subtracted from Analog 1 to give a differential signal. The value is limited to 0. 

5: Largest (Analog 1, Analog 2)

. The larger of the two analog input values is always used for PI feedback. 

P-47 

Analog Input 2 Signal Format 

U0-10 



 = 0 to 10 Volt Signal 



 = 0 to 20mA Signal 



 =  4 to 20mA Signal, the TECDrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 4 to 20mA Signal, the TECDrive will run at Preset Speed 1 (P-20)  if the signal level falls below 3mA 



 = 20 to 4mA Signal, the TECDrive will trip and show the fault code 



 if the signal level falls below 3mA 



 = 20 to 4mA Signal, the TECDrive will run at Preset Speed 1 (P-20)   if the signal level falls below 3mA 



 = Use for motor thermistor measurement, valid with any setting of P-15 that has Input 3 as E-Trip. 

Trip level : 3kΩ, reset 1kΩ

 

P-48 

Standby Mode Timer 

0.0 

25.0 

0.0 

When standby mode is enabled by setting P-48 > 0.0, the drive will enter standby following a period of operating at minimum speed 
(P-02) for the time set in P-48. When in Standby Mode, the drive display shows 



, and the output to the motor is disabled. 

P-49 

PI Control Wake Up Error Level 

0.0 

100.0 

5.0 

When the drive is operating in PI Control Mode (P-12 = 5 or 6), and Standby Mode is enabled (P-48 > 0.0), P-49 can be used to define 
the PI Error Level (E.g. difference between the setpoint and feedback) required before the drive restarts after entering Standby 
Mode. This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficiently. 

P-50 

User Output Relay Hysteresis 

0.0 

100.0 

0.0 

Sets the hysteresis level for P-19 to prevent the output relay chattering when close to the threshold. 

6.3.

 

Advanced Parameters 

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-51 

Motor Control Mode 

0: Vector speed control mode 
1: V/f mode 
2: PM motor vector speed control 
3: BLDC motor vector speed control 
4: Synchronous Reluctance motor vector speed control 
5: LSPM motor vector speed control

 

P-52 

Motor Parameter Autotune 

0 : Disabled 
1: Enabled

. When enabled, the drive immediately measures required data from the motor for optimal operation. Ensure all motor 

related parameters are correctly set first before enabling this parameter. 
This parameter can be used to optimise the performance when P-51 = 0. 
Autotune is not required if P-51 = 1. 
For settings 2 

 5 of P-51, autotune MUST be carried out AFTER all other required motor settings are entered. 

P-53 

Vector Mode Gain 

0.0 

200.0 

50.0 

Single Parameter for Vector speed loop tuning. Affects P & I terms simultaneously. Not active when P-51 = 1. 

P-54 

Maximum Current Limit 

0.0 

175.0 

150.0 

Defines the max current limit in vector control modes 

P-55 

Motor Stator Resistance 

0.00 

655.35 

Ω

 

Motor stator resistance in Ohms. Determined by Autotune, adjustment is not normally required. 

P-56 

Motor Stator d-axis Inductance (Lsd) 

6553.5 

mH 

Determined by Autotune, adjustment is not normally required. 

P-57 

Motor Stator q-axis Inductance (Lsq) 

6553.5 

mH 

Determined by Autotune, adjustment is not normally required. 

P-58 

DC Injection Speed 

0.0 

P-01 

0.0 

Hz / RPM 

Sets the speed at which DC injection current is applied during braking to Stop, allowing DC to be injected before the drive reaches 
zero speed if desired. 

P-59 

DC Injection Current 

0.0 

100.0 

20.0 

Sets the level of DC injection braking current applied according to the conditions set in P-32 and P-58. 

P-60 

Motor Overload Management 

Index 1 : Thermal Overload Retention 

0 : Disabled 
1: Enabled. 

When enabled, the drive calculated motor overload protection information is retained after the mains power is removed 

from the drive. 

Index 2 : Thermal Overload Limit Reaction 

0: It.trp. 

When the overload accumulator reaches the limit, the drive will trip on It.trp to prevent damage to the motor. 

1: Current Limit Reduction. 

When the overload accumulator reaches 90% of, the output current limit is internally reduced to 100% 

of P-08 in order to avoid an It.trp. The current limit will return to the setting in P-54 when the overload accumulator reaches 10% 

Содержание TECDrive TEC -3-120070-101 Series

Страница 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Страница 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Страница 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Страница 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Страница 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Страница 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Страница 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Страница 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Страница 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Страница 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Страница 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Страница 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Страница 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Страница 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Страница 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Страница 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Страница 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Страница 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Страница 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Страница 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Страница 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Страница 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Страница 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Страница 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Страница 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Страница 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Страница 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Страница 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Страница 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Отзывы: