TECDrive TEC-3 User Guide Revision 1.20 

 

www.tecmotors.co.uk/tecdrive 

15

 

 

4

 
Pow

e

r &

 Co
n

trol
 W

iri

n

4.8.1.

 

Analog Output 

The analog output function may be configured using parameter P-25, which is described in section 6.2 Extended Parameters on page 18. 
The output has two operating modes, dependent on the parameter selection. 

 

Analog Mode 

o

 

The output is a 0 

 10 volt DC signal, 20mA max load current 

 

Digital Mode 

o

 

The output is 24 volt DC, 20mA max load current 

4.8.2.

 

Relay Output 

The relay output function may be configured using parameter P-18, which is described in section 6.2 Extended Parameters on page 18. 

4.8.3.

 

Analog Inputs 

Two analog inputs are available, which may also be used as Digital Inputs if required. The signal formats are selected by parameters as follows 

 

Analog Input 1 Format Selection Parameter P-16 

 

Analog Input 2 Format Selection Parameter P-47 

These parameters are described more fully in section 6.2 Extended Parameters on page 18. 
The function of the analog input, e.g. for speed reference or PID feedback for example is defined by parameters P-15. The function of these 
parameters and available options is described in section 7 Analog and Digital Input Macro Configurations on page 23. 

4.8.4.

 

Digital Inputs 

Up to four digital inputs are available. The function of the inputs is defined by parameters P-12 and P-15, which are explained in section 7 
Analog and Digital Input Macro Configurations o
n page 23. 

4.9.

 

Motor Thermal overload Protection 

4.9.1.

 

 Internal Thermal Overload Protection 

The drive has an in-

built motor thermal overload function; this is in the form of an “I.t

-

trP” trip after delivering >100% of the valu

e set in P-08 

for a sustained period of time (e.g. 150% for 60 seconds). 

4.9.2.

 

Motor Thermistor Connection 

Where a motor thermistor is to be used, it should be connected as follows:- 
 

Control Terminal Strip 

Additional Information 

 

Compatible Thermistor : PTC Type, 2.5k

Ω

 trip level 

 

Use a setting of P-15 that has Input 3 function as External Trip, e.g. P-15 = 3. Refer to section 7 for 
further details. 

 

Set P-

47 = “



 
 

 

4.10.

 

EMC Compliant Installation

 

Category 

Supply Cable Type 

Motor Cable Type 

Control Cables 

Maximum Permissible Motor Cable Length 

C1

6

 

Shielded

1

 

Shielded

1,5

 

Shielded

 

1M / 5M

7

 

C2 

Shielded

2

 

Shielded

1, 5

 

5M / 25M

7

 

C3 

Unshielded

3

 

Shielded

2

 

25M / 100M

7

 

1/ A screened (shielded) cable suitable for fixed installation with the relevant mains voltage in use. Braided or twisted type screened cable 
where the screen covers at least 85% of the cable surface area, designed with low impedance to HF signals. Installation of a standard cable 
within a suitable steel or copper tube is also acceptable. 
2/ A cable suitable for fixed installation with relevant mains voltage with a concentric protection wire. Installation of a standard cable within a 
suitable steel or copper tube is also acceptable. 
3/ A cable suitable for fixed installation with relevant mains voltage. A shielded type cable is not necessary. 
4/ A shielded cable with low impedance shield. Twisted pair cable is recommended for analog signals. 
5/ The cable screen should be terminated at the motor end using an EMC type gland allowing connection to the motor body through the largest 
possible surface area. Where drives are mounted in a steel control panel enclosure, the cable screen may be terminated directly to the control 
panel using a suitable EMC clamp or gland, as close to the drive as possible. For IP66 drives, connect the motor cable screen to the internal 
ground clamp. 
6/ Compliance with category C1 conducted emissions only is achieved. For compliance with category C1 radiated emissions, additional 
measures may be required, contact your Sales Partner for further assistance. 
7/ Permissible cable length with additional external EMC filter 

4.11.

 

Optional Brake Resistor 

TECDrive E3 Frame Size 2 and above units have a built in Brake Transistor. This allows an external resistor to be connected to the drive to 
provide improved braking torque in applications that require this.  

The brake resistor should be connected to the “+” and “BR” terminals as shown.

 

 

The voltage level at these terminals may exceed 800VDC 
Stored charge may be present after disconnecting the mains power 
Allow a minimum of 5 minutes discharge after power off before attempting any connection to these terminals 

Suitable resistors and guidance on selection can be obtained from your Invertek Sales Partner. 

 

 

Содержание TECDrive TEC -3-120070-101 Series

Страница 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Страница 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Страница 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Страница 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Страница 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Страница 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Страница 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Страница 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Страница 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Страница 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Страница 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Страница 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Страница 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Страница 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Страница 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Страница 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Страница 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Страница 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Страница 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Страница 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Страница 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Страница 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Страница 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Страница 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Страница 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Страница 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Страница 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Страница 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Страница 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Отзывы: