USING THE DG-1000 WITH THE MINNEAPOLIS BLOWER DOOR

Before the Test

•  Install the blower door frame, panel and fan into an exterior doorway. For instructions about how to do this, please see 

Chapter 2 of the Minneapolis Blower Door User Manual.

 

•  Prepare the building for the blower door test. For instructions about how to do this, please see 

Chapter 3 of the Minneapolis Blower Door Manual.

Tubing Hookup

1.  Attach one end of the green tube to the Channel A reference tap. Run the other 

end of the tubing outside through one of the holes provided in the lower corner 

of the nylon panel and away from the flow of the fan.

 

2.  Attach one end of the red tube to the Channel B input tap. Attach the other end 

of the red tube to the pressure tap on the blower door fan. 

Note: For help with how to connect the tubing to the DG-1000, please use the 

Tubing Assistant

 on our website.

Conducting the Test

1.  Turn on the DG-1000 gauge by pressing and holding the power button for a few seconds 

2.  After the Home screen loads, touch Gauge to open the Gauge app 

 

 

 

 

 

 

 

 

3.  Touch the mode area to open the Channel B Settings menu. Select Flow @50. Touch device and then select Model 3 Fan. Touch 

the arrow in the upper left of the screen to return to the Gauge app screen.  

 

 

 

 

 

 

 

 

 

 

 

 

Note: In this specialized test mode, Channel A measures building pressure while Channel B displays the estimated building 

leakage at a test pressure of 50 Pascals (CFM50). The leakage estimate shown on Channel B is determined by mathematically 

adjusting the actual air flow from the blower door fan to a test pressure of 50 Pascals, using the real-time Channel A building 

pressure reading and a Can’t Reach 50 factor, which can be found in th

Blower Door Manual

 on page 9.

Power button

Mode

Flow @50

Model 3 Fan

CONDUCTING A ONE-POINT DEPRESSURIZATION TEST

Содержание MINNEAPOLIS BLOWER DOOR 3

Страница 1: ...MODEL 3 MINNEAPOLIS BLOWER DOOR USING THE DG 1000 WITH THE MINNEAPOLIS BLOWER DOOR...

Страница 2: ...e tubing to the DG 1000 please use the Tubing Assistant on our website Conducting the Test 1 Turn on the DG 1000 gauge by pressing and holding the power button for a few seconds 2 After the Home scree...

Страница 3: ...the Blower Door fan and install the flow ring which you think best matches the needed fan flow see table below 8 Check and adjust if necessary the selected test device i e fan and configuration i e fl...

Страница 4: ...a pop up will appear at the bottom of the screen that says Cruise canceled Touch the red stop icon in the bottom right corner of the screen to stop the fan When the fan is stopped a pop up will appear...

Страница 5: ...nnel B in the Flow 50 mode the gauge can not calculate a reliable leakage estimate The messages and LOW appear on Channel B under the following conditions is continuously displayed when the building t...

Страница 6: ...rough one of the holes provided in the lower corner of the nylon panel 3 Attach one end of the clear tube to the Channel B reference tap Run the other end of the tubing outside through one of the hole...

Страница 7: ...energyconservatory com TEC also offers mobile apps for Apple and Android devices that can be found in the Apple App Store or the Google Play Store Instructional Videos The Energy Conservatory TEC offe...

Отзывы: