TEC DB-DEP700 Скачать руководство пользователя страница 1

Copyright 2011   The Energy Conservatory (revised 02-11) 

Fan Configuration 

Flow Range (cfm) 

For Series B Duct Blaster

 

Ring 1 

              800 – 225 

Ring 2 

              300 – 90 

Ring 3 

              125 – 10 

 

 

Quick Guide DB-DEP700  

 

One-Point 25 Pascal Total Leakage Duct Depressurization Test 

(pulling air out of the duct system)

  

Using the Minneapolis Duct Blaster

 and DG-700 Digital Gauge 

   

1.

 

Connect the Duct Blaster fan to the duct system. 
a)

 

Choose a location to install the Duct Blaster fan. In single, double or triple returned systems, the largest and closest return to the air 

handler is usually the best choice. 

Note:

 In multi-return systems (a return in every room), installing at the air handler cabinet is often best.  

 

b)

 

Remove any remote filters from the chosen return and then connect the black square transition piece to the return using temporary tape. 

Completely seal the remaining open area of the return with tape.  

 

c)

 

Pull the Duct Blaster fan and flex duct out of the carrying case. Disconnect the flex duct from the fan and insert the white foam flow 

conditioner into the 

round

 transition piece. Connect the flex duct along with one of the Flow Rings to the 

inlet side

 of the fan (i.e. the side 

without the metal guard) using the round transition piece and connect trim. 
When installing the Flow Ring, sandwich it between the round transition piece 
and the fan inlet flange. Use the Flow Ring which you think best matches the 
needed fan flow. Connect the open end of the flex duct to the square transition 
piece using the velcro strap on the flex duct.

 

d)

 

Connect the fan speed controller to the fan and plug it into a grounded 

power outlet.   

e)

 

If your DG-700 gauge and fan speed controller are compatible with Cruise Control, install the fan control cable into the 3.5 mm 

communication jacks located on top of the DG-700 and on the side of the speed controller (otherwise skip this step). ** 

 
 

2.

 

Prepare the duct system and house for the Test. 
a)

 

Adjust the HVAC system controls so that the air handler does not turn on during the Test.  

b)

 

Temporarily seal off all remaining supply and return registers, and combustion or ventilation air inlets which are connected to the duct 

system. Use 

Duct Mask

 temporary register sealing material provided with your Duct Blaster, or use painters tape and paper. 

c)

 

Turn off any exhaust fans, vented dryers, and room air conditioners. 

d)

 

Remove all central filters (i.e. in air handler or return plenum). 

e)

 

Open a door or window between the building and outside to prevent changes in building pressure when the Duct Blaster is running. 

f)

 

If the Duct Blaster is installed in an attic, garage or crawlspace - open vents or access panels or doors from these spaces to the outside. 

 
 

3.

 

Connect tubing to the DG-700 Pressure 
Gauge.  
a)

 

Select a location to measure duct 

pressure. The best location for measuring duct 
pressure is often in the supply trunkline or 
plenum. Drill a small hole (1/4" to 3/8" OD) 
into the duct to allow a static pressure probe 
to be installed. Install the static pressure 
probe with the end of the probe pointing into 
the air flow that will be coming from the Duct 
Blaster fan. If the duct system is reasonably 
airtight (e.g. less than 200 cfm25 of leakage), 
duct pressures can be measured at any supply 
register by inserting a piece of tubing through 
the temporary register seal.   

b)

 

Connect tubing to the DG-700 as shown 

in the illustration to the right.  

 
 
 
 
 
 
 
 
 

**  Your DG-700 gauge is compatible with Cruise Control if the CONFIG, CLEAR, START and ENTER keys have additional red 
lettering below the main black script. Cruise Control also requires a Duct Blaster speed controller with a 3.5 mm communication jack 
installed on the side of the controller box, and a fan control cable. 

Optional fan   
control cable         
(for Cruise Control).

 

Connect the Red 
tubing to the 
Chan B Input tap. 
The other end of 
the Red tubing 
should be 
connected to the 
brass tap in the 
middle of the DB 
fan housing.  

Connect Chan A Ref 
tap to inside of 
building (if gauge is 
located in the 
building, leave this 
tap open). Be sure 
window is open.

 

Connect a piece of 
tubing from the 
Chan B Ref tap to 
the plastic tap on the 
Round Transition 
Piece.  

Connect the Green (or 
Clear) tubing to the 
Chan A Input tap. The 
other end of the Green 
tubing should be 
connected to the duct 
system (by either 
inserting into a sealed 
register, or connecting 
to the end of the 
installed static 
pressure probe). 

Optional fan 
control cable 
(for Cruise 
Control).

 

Отзывы: