background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The Integra, INT-2270 and Integra INT-2170, are a multifunction 
digital meter for the measurement of power quality. They provide 
measurement isolation and conversion of all main electrical 
parameters. Both INT-2270 and INT-2170 can be used in single 
and three-phase balanced or unbalanced, 3 or 4 wire electrical 
systems. 
The INT-2270 has an accuracy of CL0.2S. 
The INT-2170 has an accuracy of CL0.5S. 
Both include RS485 Modbus RTU communications protocol and 
Pulse/Alarm input/outputs as standard. 

 
Measurement 

The device is supplied programmed to the users requirements 
but can be easily reprogrammed to suit any application. 

 
Setup 

The Integra, INT-2*70, is individually calibrated to full accuracy. No 
further adjustments or setup is required. 
Should  the  unit  need  reprogramming  please  refer  to  the 
Programming Guide for further information. 

 

 

 
 
 
 
 
 
 
 
 
 
 

 
Safety 

The unit is designed in accordance with BS EN 61010-1:2001 
(IEC 61010-1:2001) 

– Permanently connected use, Normal 

condition.  Installation category III, pollution degree 2, basic  
insulation for rated voltage.  Measurement Category III. 

 

Maintenance 

In  normal  use,  no  maintenance  is  needed.    As  appropriate  for 
service conditions, isolate from electrical power, inspect the unit, 
and  remove  any  dust  or  other  foreign  material  present.  
Periodically check all connections for freedom from corrosion and 
screw tightness, particularly if vibration is present. 
The front of the case should be wiped with a dry cloth only.  Use 
minimal  pressure,  especially  over  the  viewing  window  area.    If 
necessary wipe the rear case with a dry cloth.  If a cleaning agent 
is  necessary,  isopropyl  alcohol  is  the  only  recommended  agent 
and should be used sparingly.  Water should not be used.  If the 
rear  case  exterior  or  terminals  should  be  contaminated 
accidentally  with  water,  the  unit must  be  thoroughly  dried  before 
further  service.    Should  it  be  suspected  that  water  might  have 
entered  the  unit,  factory  inspection  and  refurbishment  is 
recommended. 

 
WARNING.

 

It is essential that the primary current is isolated BEFORE 
connecting or disconnecting the secondary current connections 

The unit is intended for panel mounting.  Avoid mounting the 
unit where there is excessive vibration; in excessive direct 
sunlight; or outside a reasonably stable ambient 
temperature. 

 
 
 

Connection Diagram

 

 

 

EMC Installation Requirements 

Whilst  this  unit  complies  with  all  relevant  EU  EMC  (electro-
magnetic compatibility) regulations, any additional precautions  
necessary  to  provide  proper  operation  of  this  and  adjacent 
equipment will be installation dependent and so the following can 
only be general guidance: 

 

Avoid routing wiring to this unit alongside cables and products 
that are, or could be, a source of interference. 

 

The  supply  to  the  unit  should  not  be  subject  to  excessive 
interference.    In  some  cases,  a  supply  line  filter  may  be 
required. 

 

To  protect  the  product  against  incorrect  operation  or 
permanent damage, surge transients must be controlled.  It is 
good EMC practice to suppress transients and surges at the 
source.  The unit has been designed to automatically recover 
from  typical  transients;  however  in  extreme  circumstances  it 
may be necessary to temporarily disconnect the supply for a 
period of greater than 10 seconds to restore correct operation. 

 

Screened  communication  leads  are  recommended  and  may 
be required.  These and other connecting leads may require 
the  fitting  of  RF  suppression  components,  such  as  ferrite 
absorbers, line filters etc., if RF fields cause problems. 

 

It  is  good  practice  to  install  sensitive  electronic  instruments 
that  are  performing critical  functions in  EMC enclosures  that 
protect against electrical interference causing a disturbance in 
function. 

Wiring 
Connections are made via shrouded screw-clamp 0.05-4mm wire.  
Choice  of  cable  should  meet  local  regulations  for  the  operating 
voltage.  
Connector plugs are suitable for copper wires only and will accept 
one stranded 0·05 

– 4mm

2

 (30  -  11AWG) stranded  core  cables.  

This  instrument  is  intended  for  panel mounting.    Terminals must 
be enclosed within the panel.  For mains terminals use wire rated 
at 1000V, 60°C minimum temperature.  Terminal screws are fully 
tightened for shipment and must be undone before wire insertion.  
Terminal screws should be tightened to 0·5 Nm (4·4 lbf in) only. 

 
Fusing 

This unit must be installed with external fuses in the voltage supply 
lines of type slow blow 1A maximum.  Choose fuses of a type and 
with  a  breaking  capacity  appropriate  to  the  supply  and  in 
accordance with local regulations. 
A suitable switch or circuit breaker conforming to the relevant parts 
of  IEC  60947-1  and  IEC  60947-3  should  be  included  in  the 
installation.  It should be positioned so as to be easy to operate, in 
close  proximity  to  the  equipment,  and  clearly  identified  as  the 
disconnecting device. 
 

 

Warnings    

 

 

 

During  normal  operation,  voltages  hazardous  to  life 
may be present at some of the terminals of this unit. 

 

At voltages below that specified in the Range of Use 
the  meter  may  shut  down.    However,  voltages 
hazardous to life may still be present at some of the 
terminals of this unit. 

 

Installation  and  servicing  should  be  performed  only 
by  qualified,  properly  trained  personnel  abiding  by 
local regulations. 

 

Ensure  all  supplies  are  de-energised  before 
attempting connection or other procedures. 

 

Terminals  should  not  be  user  accessible  after 
installation and external installation provisions must 
be  sufficient  to  prevent  hazards  under  fault 
conditions. 

 

This  unit  is  not  intended  to  function  as  part  of  a 
system providing the sole means of fault protection - 
good  engineering  practice  dictates  that  any  critical 
function be protected by at least two independent and 
diverse means. 

 

The  unit  does  not  have  internal  fuses  therefore 
external fuses must be used for protection and safety 
under fault conditions. 

 

Never  open-circuit  the  secondary  winding  of  an 
energized current transformer. 

 

This product should only be operated with the CT 
secondary connections earthed. 

 

If this equipment is used in a manner not specified by 
the  manufacturer,  protection  provided  by  the 
equipment may be impaired.

 

 

During  installation  suitable  PPE,  including  eye 
protection MUST be worn at all times

 

 

 

Technical Details and 

Safety Instructions 

Integra INT-2270 

Integra INT-2170 

 

 

Caution: Risk of 
Electric Shock

 