LOC B

AMP NETCONNECT* Undercarpet 
Communications Cabling System 
4-Pair Unshielded Twisted-Pair (UTP) Cable 
1499119-1 and -5 and 1499539-1 and -5

408-3194

02 MAY

 

11 Rev K

Figure 1

1. INTRODUCTION

Undercarpet 4-pair UTP cables shown in Figure 1 are 

used in undercarpet communications applications. 

Dimensions in this instruction sheet are in metric 

units [with U.S. customary units in brackets]. 

Figures are not drawn to scale.

To obtain information on AMP NETCONNECT 

products, call PRODUCT INFORMATION at the 

number at the bottom of this page, or visit the 

AMP NETCONNECT website at 

www.ampnetconnect.com.

Reasons for reissue of this instruction sheet are 

provided in Section 5, REVISION SUMMARY.

2. DESCRIPTION

The cable is provided on a reel that has a hole in the 

center. The cable unwinds with the printed side of the 

cable on top. The cable has a wing on each edge with 

twisted-pair conductors inside a center rib.

3. INSTALLATION PROCEDURE

IMPORTANT:

  

It is recommended that a qualified 

technician install the undercarpet communications 

cable.

To avoid personal injury, ALWAYS DISCONNECT 

the electrical power before beginning work on any 

circuit.

3.1. Planning

Before starting installation, understand the following:
— The communications cable should be installed after 

the power cabling system is installed and just prior 

to installing the carpet.

— Communications cable runs may cross the power 

cable top shield; however, the crossing should not 

occur where the power cable is tapped, spliced, or 

folded.

— Except at crossings, the communications cable 

should NOT run on top of the power cable top 

shield or run closer than 152.4 mm [6 in.] to the 

power cable top shield.

— DO NOT allow the communications cable to cross 

other communications cable.

— If possible, routing of the communications cable 

should be planned to avoid high traffic areas and 

areas under desk chairs.

3.2. Transition Box, Communications Transition Block, 

and Floor Fitting

Install the transition box, communications transition 

block, and floor fitting according to the instructions 

included with the product. 

Instruction sheet included with product is:
408-10336 — Surface Mount Wall Transition Box
408-10412 — Flush Mount Wall Transition Box
408-3368 — Category 5e Communications

Transition Block

408-10009 — Category 6 Communications

Transition Block

408-3179 — Low-Profile Floor Fitting
408-8843 — Multimedia Dual Data Kit
408-3129 — Conductor Direct Connecting

Receptacle (DCR) Kits

3.3. Prepare Floor Surface

Level or patch all uneven floor surfaces. Fill in and 

smooth all holes and cracks, and remove all 

projections, ensuring a smooth and continuous floor 

surface. Seal all porous floors.

The communications cable must be installed onto a 

clean and level floor surface.

3.4. Communications Cable

1. Cut a notch in the wall to allow the cable to radius 

to the floor.

UNDERCARPET 

COMMUNICATIONS 

CABLE

LENGTH

PERFORMANCE 

LEVEL

1499119-1

0.

76 m [250 ft]

Category 5e

1499119-5

30.5 m [100 ft]

1499539-1

0.

76 m [250 ft]

Category 6

1499539-5

30.5 m [100 ft]

NOTE

i

AMP NETCONNECT logo is a trademark of TE Connectivity.

DANGER

STOP

NOTE

i

!

CAUTION

20.32 mm [.80 in.] 

Internal Diameter

Reel

Printed Side 

of Cable

Wings

Conductors