QM range App Note, document number 260283, rev 15
Page 31 of 48
5.
EFFICIENCY
The following chart shows the measured efficiency of a QM7FSDL 24SCS 24SCS 24SCS configuration.
6.
POWER SUPPLY OPERATION
No Load Operation
No minimum load is required for the power supply to operate within specification.
Remote Sense
Remote sensing is provided on select modules to compensate for voltage drops in the power connections to the
load. The remote sense lines may be connected as follows:
If remote sense is not required, simply do not connect either ‘+sense’ or ‘–sense’
If remote sense is required, connec
t ‘-sense’ and ‘+sense’ to the corresponding point at the load (see
the drawing below for details)
Note
– do not connect remote sense across an output fuse
Care should be taken to ensure that remote sense is connected in the correct polarity and is
disconnected from the load before the power connections are removed