HFE2500 Series & HFE2500/S Series (Optional PMBus) Instruction Manual
HFE2500 SERIES SPECIFICATIONS:
HFE2500-12/S
HFE2500-24/S
HFE2500-48/S
1 Rated output voltage
V
12
24
48
2 Output voltage set point
V
12+/-1%
24+/-1%
48+/-1%
3 Output voltage range
V
9.6~13.2
19.2~29.0
38.4~58
4 Rated Output Current at 180 < Vin ≤ 265Vac (*1)
A
200
104
52
5 Rated Output Current at 170 ≤ Vin ≤ 180Vac (*1)
A
200
100
50
6 Rated Output Current at 100 ≤ Vin ≤ 132Vac (*1)
A
125
62.5
31.25
7 Rated Output Current at 85V ≤Vin < 100Vac (*1)
A
Linear derating 1.3% per 1VAC from output current at 100VAC
8 Rated output power 180 < Vin ≤ 265Vac
W
2400
2496
2496
9 Rated output power 170 ≤ Vin ≤ 180Vac
W
2400
10 Rated output power 100 ≤ Vin ≤ 132Vac
W
1500
1500
1500
11 Rated output power 85Vac ≤ Vin < 100Vac
W
Linear derating 1.3% per V
12 Input voltage / frequency range
(*2)
---
85~265Vac continuous, 47~63Hz, Single phase
13 Maximum input current (*3)
A
15/12A
14 Power Factor (Typ) (*3)
---
>0.99/0.98 @ 115/230V and maximum output power
15 Efficiency at 75% rated load (Typ)
(*3)
%
90/92%
90/92%
91/93%
16 Efficiency at 100% rated load (Typ)
(*3)
%
89/91%
89/91%
90/92%
17 Inrush current
(*4)
A
Less than 50A
18 Hold-up time
(*13)
mS
≥ 10mS typical at 115/230Vac input, rated output voltage and
less than 80% of rated load.
19 Maximum line regulation
(*5)
%
0.25%
20 Maximum load regulation
(*6)
%
0.50%
21 Output Ripple and noise P-P
0~+70°C
(*7)
mV
240
240
480
-10~0°C
mV
360
360
780
22 Temperature stability
%
0.05% of rated Vout for 8hrs after 30min warm-up. Constant
line,load and temperature.
23 Temperature coefficient
PPM/°C
+/-200
24 Remote sensing
(*8)
---
Possible. Refer to instruction manual.
25 Parallel operation
(*9)
---
Possible. Single wire current share, 5% accuracy of rated Iout, up
to 8 units of the same voltage and the same current rating.
26 Series operation
---
Possible (with external diodes), 2 units. Refer to instruction manual.
27 Over current protection 85 ≤ Vin ≤ 132Vac
%
Minimum 110% of rated output current.
170 ≤ Vin ≤ 265Vac
105~120% of rated output current.
28 Over voltage protection
(*10)
V
Tracking OVP, range: 1.1xVout, accuracy: +/-3%
29 Over temperature protection
---
Inverter shut down method, automatic reset.
30 Remote On/Off control
---
Two complementary inputs. By electrical signal or dry contact.
Refer to instruction manual.
31 "DC OK" signal
---
Tracking, On when Vout>90+/-5% of set output voltage.
Open collector signal. Max.sink current: 10mA
Refer to Instruction Manual.
32 Over-Temperature warning
---
Refer to instruction manual. Open collector signal, Max. sink
current: 10mA.
33 "AC FAIL" signal
---
On when 270Vac>Vin>85Vac. Open collector signal, Max. sink
current: 10mA.
34 Auxiliary power supply output (*3)
(*11)
---
11.2~12.5V, 0.5A. 240mVp-p ripple and noise.
35 Vout programming by external voltage
---
By 0~5V, equal to Vout min ~ Vout max. Refer to Instruction Manual.
36 Vout programming by external resistor
---
By 1Kohm potentiometer . Refer to Instruction Manual.
37 OCP programming by external voltage
---
By 0~5V. Refer to Instruction Manual.
38 Front panel indicators
---
AC OK, DC OK/FAIL. Refer to Instruction Manual.
39 I²C Interface
---
Optional, PMBus compatible. Refer to Instruction Manual.
40 Operating temperatue
(*14)
---
-10~70°C.
-10~50°C: 100% load. Derate 2%/°C, 50°C to 60°C, Derate
2.5%/°C, 60°C to 70°C.
41 Storage temperature
---
-30~85°C
42 Operating humidity
---
10~90% RH, no condensation.
43 Storage humidity
---
10~95% RH, no condensation.
44 Cooling
---
By internal Fans. Variable speed control by ambient temperature
and power level.
45 Vibration
---
Built to meet IEC60068-2-64 (Basic Transportation)
46 Shock
---
Built to meet IEC60068-2-27 (Basic Transportation)
47 Conducted emission
---
Built to meet EN55022 Class B, FCC part 15 Class-B, VCCI Class-B
48 Radiated emission
---
Built to meet EN55022 Class A, FCC part 15 Class-A, VCCI Class-A
49 Immunity
---
Built to meet IEC61000-4-2 (Level 2,3),
-3 (Level 2), -4 (Level 2), -5 (Level 3,4), -6 (Level 2), -8 (Level 4), -11
50 Applicable safety standards
---
UL60950-1, EN60950-1
51 Withstand voltage
---
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min.
Output - Ground: 500VAC 1min.
Output - Ground:
2250VDC 1min, (POE)
52 Insulation resistance
---
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc
53 Leakage current
(*12)
mA
Less Than 0.75/1.5mA at 115/230Vac range
54 Weight (Typ)
Kg
Max 2.1
55 Size (W*H*D)
---
107x41x325mm Refer to Outline Drawing.