HFE2500 SERIES SPECIFICATIONS:

HFE2500-12/S

HFE2500-24/S

HFE2500-48/S

1 Rated output voltage

V

12

24

48

2 Output voltage set point                                         

V

12+/-1%

24+/-1%

48+/-1%

3 Output voltage range

V

9.6~13.2

19.2~29.0

38.4~58

4 Rated Output Current at 180 < Vin ≤ 265Vac        (*1)

A

200

104

52

5 Rated  Output  Current  at  170  ≤ Vin  ≤  180Vac           (*1)

A

200

100

50

6 Rated  Output  Current  at  100  ≤ Vin  ≤  132Vac            (*1)

A

125

62.5

31.25

7 Rated Output Current at 85V ≤Vin < 100Vac           (*1)

A

Linear derating 1.3% per 1VAC from output current at 100VAC

8 Rated output power 180 < Vin ≤ 265Vac

W

2400

2496

2496

9 Rated output power 170 ≤ Vin ≤ 180Vac

W

2400

10 Rated output power 100 ≤ Vin ≤ 132Vac

W

1500

1500

1500

11 Rated output power 85Vac ≤ Vin < 100Vac

W

Linear derating 1.3% per V

12 Input voltage / frequency range 

(*2)

 ---

85~265Vac continuous, 47~63Hz, Single phase

13 Maximum input current                                                 (*3)

A

15/12A

14 Power Factor (Typ)                                                             (*3)

 ---

>0.99/0.98 @ 115/230V and maximum output power 

15 Efficiency at 75% rated load (Typ) 

(*3)

%

90/92%

90/92%

91/93%

16 Efficiency at 100% rated load (Typ)  

(*3)

%

89/91%

89/91%

90/92%

17 Inrush current 

(*4)

A

Less than 50A

18 Hold-up time

(*13)

mS

≥ 10mS typical at 115/230Vac input, rated output voltage and 

less than 80% of rated load.

19 Maximum line regulation 

(*5)

%

0.25%

20 Maximum load regulation 

(*6)

%

0.50%

21 Output Ripple and noise P-P

0~+70°C

(*7)

mV

240

240

480

-10~0°C

mV

360

360

780

22 Temperature stability

%

0.05% of rated Vout for 8hrs after 30min warm-up. Constant 

line,load and temperature.

23 Temperature coefficient 

PPM/°C

+/-200

24 Remote sensing

(*8)

 ---

Possible. Refer to instruction manual.

25 Parallel operation

(*9)

 ---

Possible. Single wire current share, 5% accuracy of rated Iout, up 

to 8 units of the same voltage and the same current rating.

26 Series operation

 ---

Possible (with external diodes), 2 units. Refer to instruction manual.

27 Over current protection  85 ≤ Vin ≤ 132Vac

%

Minimum 110% of rated output current. 

170 ≤ Vin ≤ 265Vac

105~120% of rated output current. 

28 Over voltage protection

(*10)

V

Tracking OVP,  range: 1.1xVout, accuracy: +/-3%

29 Over temperature protection

 ---

Inverter shut down method, automatic reset.

30 Remote On/Off control 

 ---

Two complementary inputs. By electrical signal or dry contact. 

Refer to instruction manual.

31 "DC OK" signal

 ---

 Tracking, On when Vout>90+/-5% of set output voltage.  

Open collector signal. Max.sink current: 10mA  

Refer to Instruction Manual.

32 Over-Temperature warning

 ---

Refer to instruction manual. Open collector signal, Max. sink 

current: 10mA. 

33 "AC FAIL" signal

 ---

 On when 270Vac>Vin>85Vac. Open collector signal, Max. sink 

current: 10mA.

34 Auxiliary power supply output                             (*3) 

(*11)

 ---

11.2~12.5V, 0.5A.  240mVp-p ripple and noise.

35 Vout programming by external voltage

 ---

 By 0~5V, equal to Vout min ~ Vout max. Refer to Instruction Manual.

36 Vout programming by external resistor

 ---

By 1Kohm  potentiometer . Refer to Instruction Manual.

37 OCP programming by external voltage

 ---

 By 0~5V. Refer to Instruction Manual.

38 Front panel indicators

 ---

AC OK, DC OK/FAIL.  Refer to Instruction Manual.

39 I²C Interface

 ---

Optional, PMBus compatible. Refer to Instruction Manual.

40 Operating temperatue                                         

(*14)

 ---

-10~70°C. 

 -10~50°C: 100% load. Derate 2%/°C, 50°C to 60°C, Derate 

2.5%/°C, 60°C to 70°C.

41 Storage temperature

 ---

 -30~85°C   

42 Operating humidity

 ---

10~90% RH, no condensation.

43 Storage humidity

 ---

10~95% RH, no condensation.

44 Cooling

 ---

By internal Fans. Variable speed control by ambient temperature 

and power level.

45 Vibration 

 ---

Built to meet IEC60068-2-64 (Basic Transportation)

46 Shock

 ---

Built to meet IEC60068-2-27 (Basic Transportation)

47 Conducted emission

 ---

Built to meet EN55022 Class B, FCC part 15 Class-B, VCCI Class-B

48 Radiated emission

 ---

Built to meet EN55022 Class A, FCC part 15 Class-A, VCCI Class-A

49 Immunity

 ---

Built to meet IEC61000-4-2 (Level 2,3), 

    -3 (Level 2), -4 (Level 2), -5 (Level 3,4), -6 (Level 2), -8 (Level 4), -11

50 Applicable safety standards

 ---

UL60950-1, EN60950-1 

51 Withstand voltage

 ---

Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. 

Output - Ground:  500VAC  1min. 

Output - Ground:  

2250VDC 1min, (POE)

52 Insulation resistance

 ---

More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc 

53 Leakage current                                               

(*12)

mA

Less Than 0.75/1.5mA  at 115/230Vac range

54 Weight  (Typ)

Kg

Max 2.1

55 Size (W*H*D)

 ---

107x41x325mm  Refer to Outline Drawing.

1

Содержание HFE2500 Series

Страница 1: ...e 1 1xVout accuracy 3 29 Over temperature protection Inverter shut down method automatic reset 30 Remote On Off control Two complementary inputs By electrical signal or dry contact Refer to instructio...

Страница 2: ...stant load 6 From No load to Rated load constant input voltage Measured at the sensing point in Remote sense 7 Measured with JEITA RC9131A 1 1 probe with 4x270uF electrolytic capacitors and 1uF film c...

Страница 3: ...85Vac 100Vac 132Vac 170Vac 265Vac All Output Voltages Pout Vin 85Vac 100Vac 132Vac 170Vac 265Vac All Output Voltages 100Vac 132Vac 170Vac 265Vac HFE 2500 Series HFE 2500 Series HFE2500 Series Fig B Ou...

Страница 4: ...A11 20 VO B15 DC_OK B1 SIGNAL_RTN B16 A0 B2 PS_EXIST B17 SDA B3 12V_AUX_OUT B18 TEMP_ALM_SR B4 SENSE B19 V_REF_EXT B5 A2 B20 SMB_ALERT B6 CS B21 AC_FAIL_OUT B7 ENABLE B22 5V_Trim B8 V_PROG B23 NC B9 S...

Страница 5: ...er Supply or Load side SENSE B11 CURRENT PROGRAMMING Input 0 5V Refferenced to S provides Iout programming by voltage Reffer to Instruction manual Chapter 1 8 1 8 1 1 8 2 B12 INHIBIT Turns OFF the mai...

Страница 6: ...w 90 5 of set Output Voltage 2 AC OK LED indicator GREEN when Input Voltage is 85Vac Vin 270Vac OFF when the Input Voltage is 85Vac Vin or Vin 270Vac CAUTION When inserting a power supply into the rac...

Страница 7: ...d for use in the following operation conditions Indoor use Pollution degree 2 Max operational altitude 3000m above sea level Ambient temperature 10 C 50 C at 100 load up to 70 C with output de rating...

Страница 8: ...ltage fluctuations should not exceed 10 of nominal voltage HEAT HAZARD WARNING Top bottom and side surfaces may become hot when operating the unit continuously To reduce the risk of injury from a hot...

Страница 9: ...1 2 Basic configuration Remote Sense For basic configuration SENSE have to be connected to the V terminals on the Load side prior to operating the supply ENABLE input must be connected to SIGNAL RETU...

Страница 10: ...Voltage of HFE2500 Series can be programmed by external voltage source between approximately 80 120 for 24V 48V and 80 110 for 12V of nominal output voltage For Output voltage limits see Graph enclose...

Страница 11: ...be decreased down to 40 of Nominal Output Current 1 8 1 CURRENT PROGRAMMING By PMBUS Optional Over Current Protection OCP can be programmed by PMBUS with a range of 50 110 of Nominal Output Current A...

Страница 12: ...ETs on the main output and the 12V Auxiliary output allow N 1 operation If Voltage programming is used Voltage Programming Pin of all units must be connected in parallel Referenced to SIGNAL RETURN fl...

Страница 13: ...shown Sense of positive unit and Sense of negative unit twisted pair to Load point or to V and V accordingly for Local Sense In case PMBus is used Connect PMBus signals in parallel PMBus is isolated f...

Страница 14: ...mming resolution 10 bits 3 3 Programming range V 50 110 of full scale 4 OUTPUT CURRENT MEASUREMENT HFE2500 12 S HFE2500 24 S HFE2500 48 S 4 1 Measurement accuracy 10 of full scale 4 2 Measurement reso...

Страница 15: ...e internally pulled up by resistors to 5V The address lines can be left open for 1 address or connected to S for 0 address So available Address Space contains 16 possible addresses from 0010000 to 001...

Страница 16: ...ion FAULT 1 Internal temperature higher than safe limit Output OFF Over Temperature Alarm WARNING 2 Internal temperature 10 C below safe limit Output ON Fan Fail FAULT 3 One or both Fans are not worki...

Страница 17: ...0 4263 0 3 Temperature monitoring C 0 100 1023 0 2 12 24 32 48 Current monitoring 50 110 146 5830 1 m b R coefficients can also be recovered from the EEPROM coefficients are stored in ASCII Format Com...

Страница 18: ...EMPERATURE_1 The accuracy of the Temperature reading is 5oC The read back supply temperature can be calculated using the Direct data Format Please refer to table 1 for the Coefficients for calculating...

Страница 19: ...refer to Fig 1 for the current limits at respective levels The output Current can be programmed using the Direct data Format Please refer to table 1 for the Coefficients to be used for calculating the...

Страница 20: ...IA689 04 01F 20...

Отзывы: