25
83532002 Rev H
2.9. Digitial Programming And Readback
1. Vout programming accuracy
---
+/-0.5% of rated Output voltage
2. Iout programming accuracy
---
+/-0.5% of rated Output current for units with Io <187.5; +/-0.7% of rated output current for Io
≥
187.5
3. Vout programming resolution
---
0.02% of full scale
4. Iout programming resolution
---
0.04% of full scale
5. Vout readback accuracy
---
+/- (0.1% of Vo(actual) + 0.2% of Vo(rated))
6. Iout readback accuracy
---
+/- (0.1% of Io(actual) + 0.4% of Io(rated))
7. Vout readback resolution
---
0.02% of full scale
8. Iout readback resolution
---
0.02% of full scale
9. OV Response Time
mS
20mS maximum between output V exceeding IEEE limit and supply inhibit turning on.
10. Other Functions
---
Set OVP/UVL Limits, Set Local/Remote, Identity, Calibration
2.10. Mechanical Construction
V
7.5
10 12.5 20
25
30
40
50
60
80 100 125 150 200 250 300 400 500 600
1. Cooling
---
Fan driven (variable speed), Airflow from Front to Rear. Supplemental vents on side that shall not be
blocked. EIA Rack mounting, stackable. “Zero Stackable” top and bottom. Slides or suitable rear support
required.
2. Weight
Kg/Lb
43/97 for Vout < 30V; 40/90 for 30
≤
Vout
≤
600V
3. Dimensions
---
W: 429mm/16.9”, H: 3U – 133mm/5.22”
D: 564mm/22.2” (excluding connectors, encoders, handles, etc.)
4. Types of connectors
---
1) AC Input: 4xM6x1” threaded studs (L1, L2, L3 and Chassis GND) and terminal cover.
2) Output: Iout
≥ 50A: bus
-bars, Iout < 37.5: threaded stud terminal
3) Analog programming: DB25, plastic connector, AMP, 747461-5, Female on Power Supply, Male on
Mating connector 747321. Standard 25 pin Sub-D connector.
4) RS-232/RS-485, STD RJ-45 Phone Jack connector
5) Isolated Analog Option: refer to Isolated Analog Option Spec. 08-030-200
6) IEMD Option: refer to IEMD Option Spec. 08-030-100.
7) LAN Option: refer to LAN Option Spec. 08-034-100
8) USB Option: refer to USB Option spec
5. Front panel material & finish
---
RAL7035, Textured finish.
6. Mounting method
---
Standard 19” Rack Mount, provision for standard slides. Side/Rear Support is required; do not mount by
Front Panel only.
7. Mounting positions
---
Horizontal
8. Output ground connection
---
M5x0.9” threaded stud
9. Color and finish
---
Chassis (Top/Sides/Bottom): Clear Iridite, Front Panel RAL7035 painted.
10. Output Terminal covers
---
Standard for all models with bus-bars. Closed connection for models with output connector.
2.11. Environmental Conditions
1. Operating temp
C
0
∼
50°C, 100% load. No operation > 50°C
2. Start up temp.
C
0
3. Storage temp
C
-20°C to +70°C
4. Operating humidity
%
20
∼
80% RH (non-condensing)
5. Storage humidity
%
10
∼
90% RH (non-condensing)
6. Altitude
---
Operating: 50
o
C up to 7500ft (2500m), 45
o
C from 7501 to 10,000ft (2501m – 3000m)
Non Operating 40,000 ft (12,000m)
7. Vibration & Shock (208/400/480VAC)
G
ASTM D4169, Standard Practice for performance Testing of Shipping Containers and Systems, Distribution
Cycle: Cy Air (intercity) and motor freight (local, single package up to 100lbs.). Shipping Unit: Single
Package Assurance Level: Level II; Acceptance Criteria: Criterion 1 – No product damage, Criterion 2 –
Package is intact.
8. Audible Noise
db
Less than 70dBA at Full Load, measured 1m from Front Panel