63
Figure 4-17: Output Bus-bars Terminals Location
Figure 4-18: Output Bus-bars Terminals
Use remote sense where the load regulation at the load end is critical. In remote sense, the power
system will compensate for voltage drop on the load wires.
Refer to the specifications for the maximum allowable voltage drop on load wires.
The voltage drop is subtracted from the total voltage available at the output. Follow the instructions
below to configure the power system for remote sensing:
1. Ensure that the Power system AC connection is Off.
2. Connect the negative sense lead to terminal J8 (-S) and the positive sense lead to terminal J8 (+S).
3. Set voltage sensing setting to remote sense via front panel or communication.
4. Turn On the power system.
NOTE
In order to ensure correct operation in remote sense mode, ensure that the voltage drop on the
sensing wires meets product specifications.