User Manual
Chapter 6 - Using the Drives Control Keys 37
6.5 Quick setup
N
OTA
!
See section 7.3 later in this manual for further information on enabling the automatic voltage boost function (
S.400
)
and setting motor slip compensation (
S.450
&
S.451
), .
Step Setup sequence
Go to the S - Startup menu
Set drive mains voltage
Set drive mains frequency
Set maximum drive output voltage
Set nominal frequency of motor
Set nominal current of motor
Set number of motor terminal pairs
Set the power factor of the motor
Set control mode
Set the maximum reference frequency
Set the reference source
Set drive acceleration and deceleration
ramp times
Set % manual voltage boost
Auto-calibrate motor stator resistance
Save parameters
What to do
Press the "M" key to access the Startup menu.
Got to parameter
S.000
and enter the drives mains voltage: 220V
or 240V.
Go to parameter
S.001
and enter the drives mains frequency: 50Hz
or 60Hz.
Go to parameter
S.100
and enter the maximum voltage the drive
can output to the motor (see data plate).
Go to parameter
S.101
and enter the nominal frequency of the
motor (see date plate).
Go to parameter
S.150
and enter the nominal current of the motor
(see data plate).
Go to parameter
S.151
and enter the number of motor terminal
pairs (terminals/2).
Go to parameter
S.152
and enter the motors power factor (cos phi)
(see data plate).
Go to parameter
S.200
and enter the drives control mode:
- selection [1] = START&STOP via terminals (default)
- selection [2] = START&STOP via serial line [see menu H]
Go to parameter
S.201
and enter the maximum threshold for the
drives reference frequency (analog and/or digital).
Go to parameter
S.202
and enter the source of the drives frequency
reference:
- selection [1] = Reference from analog input 1 (default)
- selection [3] = Digital reference from parameter
S.203
N
OTE
!
Go to parameter
S.203
and enter the digital reference
frequency (if relevant).
Go to parameter
S.300
and enter the acceleration ramp time
(default = 5 secs).
Go to parameter
S.301
and enter the deceleration ramp time
(default = 5 secs).
Go to parameter
S.400
and enter the % of manual low speed
voltage boost (if relevant)
Go to parameter
S.900
and activate the procedure for auto-
calibrating motor stator resistance:
- activate the procedure with "do" + E
Go to the parameter
S.901
and activate the procedure for saving
parameters in the drives non-volatile memory.
"
!
$
#
&
%
'
!
"
#