List of main parameters 

(see the manual for the complete list)

:

Code

Description

(unit of measure)

D - DISPLAY menu

This document is a quick guide to the installation and
operation of the inverter. For safe, advanced use, refer to
the complete manual which is available on request.

Introduction

The

 Serie V 

inverters allow an efficient and flexible

control of motor speed. In this way, the asynchronous
motor can be used in a wider range of applications.
The functioning interface is made of a panel consisting
of six keys, one display with five 7-segment digits and
seven leds.
The display and the keys allow you to change all the
inverter parameters so as to make it suitable to all
applications.
The drive display allows the monitoring of controlled
variables as frequency, current, output voltage, cos
phi, power and the storage of the last 4th alarms
attempted.

 

 Warning!

Electrical equipment can be a 

source of hazards.

 It is essential to fully understand

how to use this equipment and all relevant safety devices before attempting to
operate it.
The equipment must only be used by qualified technical personnel who are fully
aware of how to install and operate it in compliance with all relevant safety
standards, and who are perfectly able to understand all the associated
hazard warnings. The capacitors installed inside this equipment operate at
extremely high voltages. 

After switching off, wait for at least  5 minutes before

performing any work on the equipment.

 Even when the motor is switched off,

dangerous voltages can be present at the power terminals 

L1

L2

L3, -, R, +, U,

V, W.

The machine can re-start automatically after a power failure under certain
programmingconditions.
There are no user serviceable parts inside the equipment. Only the front panel
must be removed for installation.

Technical specifications

Configuring the programmable 

digital inputs 

(IN1..IN8) with:

 I-000 ... I-007.

Name

Action performed

Value

Open collector outputs 

OUT1

 and 

OUT2

 (terminals 

19

 and 

20

) are configured by

parameters 

I-100

 for 

OUT1

 and 

I-101 

 for 

OUT2

.

Relay output RLA  (terminals A1, A2, A3) is programmed with I-102.

Inverter ready status
Inverter alarm status
Inverter not in alarm status(negative logic)
Motor running
Motor not running
Anti-clockwise rotation (output off otherwise)
Inverter at full speed (end of ramp-up)
Ramping up or down.
Generic drive limit signal
Output frequency = programmed frequency 

P-440

 & 

P-441

Output frequency = programmed frequency 

P-440

 & 

P-441

Output frequency > programmed frequency 

P-440

 & 

P-441

Output frequency < programmed frequency 

P-440

 & 

P-441

Event signalled by digital output (output on)

0
1
2
3
4
5
6
7

12
29
30
31
32

Value

Digital (OUT1, OUT2) I-100, I-101;relay outputs (RLA, RLB)  I-102, I-103

None
Run
Reverse
EF NO
EF NC
Al res
Freq.Sel 1
Freq. Sel2

0
1
2
3
4
5
7
8

Not used
RUN (START) command
REVERSE command
External fault with NO contacts

External fault with NC contacts
Alarm reset command
Freq. selector 1
Freq. selector 2

External
Overcurrent
Overvoltage
Undervoltage
Overtemperature
Inverter overload
Motor overload

E

VENT

 

SIGNALLED

DISPLAY

EF
OC
OU
UU
OH
OLI
OLN

Resistance overload
Overtorque
Missing input phase
Not used
EEPROM error
Configuration error
Program error

E

VENT

 

SIGNALLED

OLr
Ot
PHI
-
Err
P.Err
C.Er

r

DISPLAY

Alarms

Parameter display menu.

P

ARA

METER

Description

S-000

S-000

S-000

S-000

S-000
S-001

S-001

S-001

S-001

S-001
S-100

S-100

S-100

S-100

S-100
S-101

S-101

S-101

S-101

S-101
S-150

S-150

S-150

S-150

S-150
S-151

S-151

S-151

S-151

S-151
S-152

S-152

S-152

S-152

S-152
S-153

S-153

S-153

S-153

S-153
S-200

S-200

S-200

S-200

S-200
S-201

S-201

S-201

S-201

S-201
S-202

S-202

S-202

S-202

S-202
S-203

S-203

S-203

S-203

S-203
S-300

S-300

S-300

S-300

S-300
S-301

S-301

S-301

S-301

S-301
S-400

S-400

S-400

S-400

S-400
S-401

S-401

S-401

S-401

S-401
S-450

S-450

S-450

S-450

S-450
S-451

S-451

S-451

S-451

S-451
S-900

S-900

S-900

S-900

S-900
S-901

S-901

S-901

S-901

S-901

Mains voltage (V)
Mains frequency (Hz)
Maximum output voltage (V)
Base frequency (Hz)
Nominal motor current
Pairs of motor poles
Plated motor 

cos

?

value

Motor stator resistance (ohm)
START & STOP  command source (1= terminals)
Maximum analog reference frequency
Reference channel source (1=AN IN1 +/-10V) (2=AN IN2 +/-10V)
Digital reference frequency
MOT-1 ramp-up time
MOT-1 ramp-down time
Manual boost
Automatic boost on/off ( 1=on)
Slip compensation
Compensation time constant
Stator resistance measure command
Parameter save command

S - START-UP menu

Basic drive start-up menu.

I - INTERFACE menu

Drive digital/analog input/output settings menu.

P

ARAMETER

Description

I-000

I-000

I-000

I-000

I-000

 a I-007

I-100

I-100

I-100

I-100

I-100

 a

I-103

I-103

I-103

I-103

I-103

I-200

I-200

I-200

I-200

I-200
I-210

I-210

I-210

I-210

I-210
I-300

I-300

I-300

I-300

I-300

Configure inputs IN1 to IN8
Configure outputs OUT 1 - OUT 2 - RLA - RLB
Configure input AN1 terminal 23 (default = 0  +/-10V)
Configure input AN2 terminal 11-12 (default = 0  +/-10V)
Configure analog output 1 terminal 21 (default = 0  Freq. out)

f-100

f-100

f-100

f-100

f-100

/

f-115

Digital  frequencies

  

f-116

   

           Jogging frequencies

Code

Description

Multi-speed and ramp settings menu.

F - FREQ& RAMP menu

Parameter save
Load previously stored parameters
Load default parameters
Reset alarm memory
Load and save parameters from external programming key

[from key to Inv.]

Save inverter parameters in external programming key

[from Inv.  to key]

Measure motor phase resistance and initialise parameter

 S-153

C-000

C-000

C-000

C-000

C-000
C-001

C-001

C-001

C-001

C-001
C-002

C-002

C-002

C-002

C-002
C-020

C-020

C-020

C-020

C-020
C-040

C-040

C-040

C-040

C-040

C-041

C-041

C-041

C-041

C-041

C-100

C-100

C-100

C-100

C-100

Action performed

Code

Control functions menu (Save parameters, Load defaults,
Autocalibrate, etc.).

C - COMMAND menu

P-001

P-001

P-001

P-001

P-001
P-002

P-002

P-002

P-002

P-002

Code

Description

Drive functioning parameter settings menu.

P - PARAMETER menu

1 = Reverse enabled without start command
1 = Reverse enabled

A - APPLICATION menu

PID functioning settings menu.

d-000 

d-000 

d-000 

d-000 

d-000        Output frequency                             (0.1 Hz)
d-001 

d-001 

d-001 

d-001 

d-001        Reference frequency                         (0.1 Hz)
d-002 

d-002 

d-002 

d-002 

d-002        Output current (rms)                          (0.1 A)
d-003 

d-003 

d-003 

d-003 

d-003        Output voltage (rms)                          (1 V)

SERIES

 DSV

 

DIGITAL

 

INVERTER

SIZE T1 - T2

QUICK START

Power
supply

voltage

Inverter

power

Nominal

output

current

Phase

current

@230V

Phase

current

@400V

Motor

Power

@400V

Size

Vac

kVA

A

A

A

kW

DSV-030

5,4

7,5

8,9

10,0

3,0

T1

DSV-040

6,5

9,0

10,7

12,0

4,0

T1

DSV-055

9,1

12,5

14,7

16,5

5,5

T1

DSV-075

12,3

17

20,0

22,5

7,5

T1

DSV-110

18,1

25,0

28,9

32,5

11,0

T2

DSV-150

23,9

33,0

38,3

43,0

15,0

T2

DSV-185

27,5

38,0

44,1

49,5

18,5

T2

230V-15%

460V+10%

50-60Hz

3-phase

PROGRAMMING KEY:   Operating instructions
Transferring parameters from the key to the inverter:

- Remove the key connector cover and insert the key.
- From the keyboard select parameter 

C - 040

,

 

select do then press 

E

.

The "done " message is displayed for 2 seconds to confirm that the operation has
terminated successfully.

MADSVX0030E0 V01

TDE Macno s.p.a.

Tel. +39-0444.343555

Via dell'Oreficeria, 41    

Fax. +39-044.343509

 36100 Vicenza (VI)  Italy

www.tdemacno.it

sw. 0D.07-xx.00