List of main parameters
(see the manual for the complete list)
:
Code
Description
(unit of measure)
D - DISPLAY menu
This document is a quick guide to the installation and
operation of the inverter. For safe, advanced use, refer to
the complete manual which is available on request.
Introduction
The
Serie V
inverters allow an efficient and flexible
control of motor speed. In this way, the asynchronous
motor can be used in a wider range of applications.
The functioning interface is made of a panel consisting
of six keys, one display with five 7-segment digits and
seven leds.
The display and the keys allow you to change all the
inverter parameters so as to make it suitable to all
applications.
The drive display allows the monitoring of controlled
variables as frequency, current, output voltage, cos
phi, power and the storage of the last 4th alarms
attempted.
Warning!
Electrical equipment can be a
source of hazards.
It is essential to fully understand
how to use this equipment and all relevant safety devices before attempting to
operate it.
The equipment must only be used by qualified technical personnel who are fully
aware of how to install and operate it in compliance with all relevant safety
standards, and who are perfectly able to understand all the associated
hazard warnings. The capacitors installed inside this equipment operate at
extremely high voltages.
After switching off, wait for at least 5 minutes before
performing any work on the equipment.
Even when the motor is switched off,
dangerous voltages can be present at the power terminals
L1
,
L2
,
L3, -, R, +, U,
V, W.
The machine can re-start automatically after a power failure under certain
programmingconditions.
There are no user serviceable parts inside the equipment. Only the front panel
must be removed for installation.
Technical specifications
Configuring the programmable
digital inputs
(IN1..IN8) with:
I-000 ... I-007.
Name
Action performed
Value
Open collector outputs
OUT1
and
OUT2
(terminals
19
and
20
) are configured by
parameters
I-100
for
OUT1
and
I-101
for
OUT2
.
Relay output RLA (terminals A1, A2, A3) is programmed with I-102.
Inverter ready status
Inverter alarm status
Inverter not in alarm status(negative logic)
Motor running
Motor not running
Anti-clockwise rotation (output off otherwise)
Inverter at full speed (end of ramp-up)
Ramping up or down.
Generic drive limit signal
Output frequency = programmed frequency
P-440
&
P-441
Output frequency = programmed frequency
P-440
&
P-441
Output frequency > programmed frequency
P-440
&
P-441
Output frequency < programmed frequency
P-440
&
P-441
Event signalled by digital output (output on)
0
1
2
3
4
5
6
7
12
29
30
31
32
Value
Digital (OUT1, OUT2) I-100, I-101;relay outputs (RLA, RLB) I-102, I-103
None
Run
Reverse
EF NO
EF NC
Al res
Freq.Sel 1
Freq. Sel2
0
1
2
3
4
5
7
8
Not used
RUN (START) command
REVERSE command
External fault with NO contacts
External fault with NC contacts
Alarm reset command
Freq. selector 1
Freq. selector 2
External
Overcurrent
Overvoltage
Undervoltage
Overtemperature
Inverter overload
Motor overload
E
VENT
SIGNALLED
DISPLAY
EF
OC
OU
UU
OH
OLI
OLN
Resistance overload
Overtorque
Missing input phase
Not used
EEPROM error
Configuration error
Program error
E
VENT
SIGNALLED
OLr
Ot
PHI
-
Err
P.Err
C.Er
r
DISPLAY
Alarms
Parameter display menu.
P
ARA
METER
Description
S-000
S-000
S-000
S-000
S-000
S-001
S-001
S-001
S-001
S-001
S-100
S-100
S-100
S-100
S-100
S-101
S-101
S-101
S-101
S-101
S-150
S-150
S-150
S-150
S-150
S-151
S-151
S-151
S-151
S-151
S-152
S-152
S-152
S-152
S-152
S-153
S-153
S-153
S-153
S-153
S-200
S-200
S-200
S-200
S-200
S-201
S-201
S-201
S-201
S-201
S-202
S-202
S-202
S-202
S-202
S-203
S-203
S-203
S-203
S-203
S-300
S-300
S-300
S-300
S-300
S-301
S-301
S-301
S-301
S-301
S-400
S-400
S-400
S-400
S-400
S-401
S-401
S-401
S-401
S-401
S-450
S-450
S-450
S-450
S-450
S-451
S-451
S-451
S-451
S-451
S-900
S-900
S-900
S-900
S-900
S-901
S-901
S-901
S-901
S-901
Mains voltage (V)
Mains frequency (Hz)
Maximum output voltage (V)
Base frequency (Hz)
Nominal motor current
Pairs of motor poles
Plated motor
cos
?
value
Motor stator resistance (ohm)
START & STOP command source (1= terminals)
Maximum analog reference frequency
Reference channel source (1=AN IN1 +/-10V) (2=AN IN2 +/-10V)
Digital reference frequency
MOT-1 ramp-up time
MOT-1 ramp-down time
Manual boost
Automatic boost on/off ( 1=on)
Slip compensation
Compensation time constant
Stator resistance measure command
Parameter save command
S - START-UP menu
Basic drive start-up menu.
I - INTERFACE menu
Drive digital/analog input/output settings menu.
P
ARAMETER
Description
I-000
I-000
I-000
I-000
I-000
a I-007
I-100
I-100
I-100
I-100
I-100
a
I-103
I-103
I-103
I-103
I-103
I-200
I-200
I-200
I-200
I-200
I-210
I-210
I-210
I-210
I-210
I-300
I-300
I-300
I-300
I-300
Configure inputs IN1 to IN8
Configure outputs OUT 1 - OUT 2 - RLA - RLB
Configure input AN1 terminal 23 (default = 0 +/-10V)
Configure input AN2 terminal 11-12 (default = 0 +/-10V)
Configure analog output 1 terminal 21 (default = 0 Freq. out)
f-100
f-100
f-100
f-100
f-100
/
f-115
Digital frequencies
f-116
Jogging frequencies
Code
Description
Multi-speed and ramp settings menu.
F - FREQ& RAMP menu
Parameter save
Load previously stored parameters
Load default parameters
Reset alarm memory
Load and save parameters from external programming key
[from key to Inv.]
Save inverter parameters in external programming key
[from Inv. to key]
Measure motor phase resistance and initialise parameter
S-153
C-000
C-000
C-000
C-000
C-000
C-001
C-001
C-001
C-001
C-001
C-002
C-002
C-002
C-002
C-002
C-020
C-020
C-020
C-020
C-020
C-040
C-040
C-040
C-040
C-040
C-041
C-041
C-041
C-041
C-041
C-100
C-100
C-100
C-100
C-100
Action performed
Code
Control functions menu (Save parameters, Load defaults,
Autocalibrate, etc.).
C - COMMAND menu
P-001
P-001
P-001
P-001
P-001
P-002
P-002
P-002
P-002
P-002
Code
Description
Drive functioning parameter settings menu.
P - PARAMETER menu
1 = Reverse enabled without start command
1 = Reverse enabled
A - APPLICATION menu
PID functioning settings menu.
d-000
d-000
d-000
d-000
d-000 Output frequency (0.1 Hz)
d-001
d-001
d-001
d-001
d-001 Reference frequency (0.1 Hz)
d-002
d-002
d-002
d-002
d-002 Output current (rms) (0.1 A)
d-003
d-003
d-003
d-003
d-003 Output voltage (rms) (1 V)
SERIES
DSV
DIGITAL
INVERTER
SIZE T1 - T2
QUICK START
Power
supply
voltage
Inverter
power
Nominal
output
current
Phase
current
@230V
Phase
current
@400V
Motor
Power
@400V
Size
Vac
kVA
A
A
A
kW
DSV-030
5,4
7,5
8,9
10,0
3,0
T1
DSV-040
6,5
9,0
10,7
12,0
4,0
T1
DSV-055
9,1
12,5
14,7
16,5
5,5
T1
DSV-075
12,3
17
20,0
22,5
7,5
T1
DSV-110
18,1
25,0
28,9
32,5
11,0
T2
DSV-150
23,9
33,0
38,3
43,0
15,0
T2
DSV-185
27,5
38,0
44,1
49,5
18,5
T2
230V-15%
460V+10%
50-60Hz
3-phase
PROGRAMMING KEY: Operating instructions
Transferring parameters from the key to the inverter:
- Remove the key connector cover and insert the key.
- From the keyboard select parameter
C - 040
,
select do then press
E
.
The "done " message is displayed for 2 seconds to confirm that the operation has
terminated successfully.
MADSVX0030E0 V01
TDE Macno s.p.a.
Tel. +39-0444.343555
Via dell'Oreficeria, 41
Fax. +39-044.343509
36100 Vicenza (VI) Italy
www.tdemacno.it
sw. 0D.07-xx.00
f-115
f-115
Ö
I-007