HE360A POWERED FLOW-THROUGH HUMIDIFIER
68-0273
4
Fig. 4. Humidifier components.
Fig. 5. Position securing clips.
7.
Position the humidifier housing in the hole (be sure it is
level), so the locking tabs are in place on the upper and
lower sheet metal edges of the hole.
8.
Push in the securing clips until completely seated.
9.
Drill holes and install the three sheet metal screws at
the top of the humidifier housing. Secure the housing
with the three remaining screws at the bottom of the
housing.
10.
Reinstall the humidifier pad assembly in the humidifier
housing.
IMPORTANT
For proper operation, be sure the mark on the end of
the humidifier pad is facing up. Check that the water
feed tube is placed in the guide slots of the humidifier
housing.
11.
Hook the top of the cover to the housing and secure
with the thumbscrew located at the bottom of the cover.
WIRING HUMIDIFIER
WARNING
Serious Personal Injury or Equipment Hazard.
Moving parts can cause electrical shock and
injury.
• Disconnect power supply before installation or
servicing.
• This device contains a moving fan blade; do not
operate the humidifier without the cover securely
attached.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
H8908 Humidistat Wiring Connections
IMPORTANT
• Select models of fan centers include humidifier taps
so the current sensing relay or sail switch is not
needed.
• If not using a current sensing relay or sail switch, the
120V humidifier plug must be energized during
blower motor cycles for proper operation.
1.
Wire the current sensing relay or sail switch.
2.
Connect only the two yellow wires to the humidity
control (red wire connections are not used for
mechanical humidity control).
NOTE: For additional mounting and wiring information, refer
to the humidity control installation instructions.
Plumbing Saddle Valve
Hot or cold water, either hard or softened, can be used in the
humidifier.
1.
Use the self-piercing saddle valve included to tap into
the water supply line at an appropriate location.
CAUTION
Equipment Hazard.
Improper installation can cause equipment
damage.
Do not use any line connected to an air conditioner.
IMPORTANT
• The saddle valve is not designed to regulate water
flow; the valve is either open or closed.
• Be sure to install the saddle valve handle pointing
toward the ceiling to prevent debris from clogging the
solenoid in-line filter.
NOTE: Lightly clean the copper tubing ends with fine
sandpaper before making any connections.
M20811
COVER
ASSEMBLY
HUMIDIFIER
PAD ASSEMBLY
FEED TUBE NOZZLE
WATER
DISTRIBUTION TRAY
HUMIDIFIER
HOUSING
THUMB
SCREW
M12813
CLIP
CLIP