Analog output not Working Properly

Check wiring. A separate transformer should be used 

for the SZ1041A and a separate transformer should be 

used for the motor(s). Check to make sure that the ana-

log output is programmed correctly.
Check the Service Menu. The Mod Out Screen will tell 

you what the SZ1041A is trying to put out. Compare this 

with the actual position on the heating or cooling device.
There are two conditions that must be met before the 

economizer analog output will modulate. First, there 

must be a call for cooling. Second, the outdoor air tem-

perature must be less than the setting set in program-

ming step #38.
Put the SZ1041A into occupied mode. You should be 

able to adjust the output by going to programming step 

#46 or 55 (depending on AO1 mode in step 41) and 

varying the minimum position setting. You need to exit 

programming before the change will take effect. 

SeRviCe SCReenS

Continually pressing the service status button allows 

more extensive monitoring. The screens are shown on 

the following page.

LED Description                      

Six LEDs on the face allow the occupant to view the cur-

rent operating status of the thermostat. 

oCCUPied

This LED will be lit whenever the unit is 

operating in the occupied mode.

heAting

This LED will be lit when any heat output is 

operating.

Cooling

This LED will be lit when any cooling output is operating. 

FAn

This LED will be lit when the fan output is closed.

SeRviCe

This LED will be lit when the high or low discharge air 

limit has been reached, when the fan interlock has indi-

cated failure, or when the filter service or service input 

are closed. 

PRogRAm/dAtA

This LED will be lit when the thermostat is within the 

programming or clock setup menus. It will blink when the 

unit is being accessed by a PC.
Additional monitoring is available by continually pressing 

the service key. 

main monitoring Screen

. Press the 

service button to access the following 

screens. 

Service Screen.

 This message may 

be followed by any or all of the follow-

ing: CHECK FILTER, CHECK FAN, 

DISCHARGE HIGH, DISCHARGE LOW, 

or CHECK DI2.

 

 

 

 

discharge Air temperature Screen

Shows discharge air temperature if sen-
sor is used. 

outdoor Air temperature Screen.

 

Shows outdoor air temperature if sensor 

is used.  

 

 

 

 

override Status Screen.

 Shows wheth-

er the override is active and if so, how 

many minutes remaining. 

 

 

 

heat or Cool Stages Status Screen. 

Shows the status of the first and second 

stages of heating or cooling.  

heat or Cool Stages Status Screen. 

Shows the status of the first and second 

stages of heating or cooling. 

service

status

MOD  OUT                25% 

DI1                    OPEN

7.

service

status

HEAT STAGE 1        OFF

HEAT STAGE 2        ON

5.

service

status

OVERRIDE                ON 

178 MINUTES            

4.

service

status

OUTDOOR AIR          

TEMP                    75F

3.

service

status

DISCHARGE AIR    

TEMP                    55F

2.

service

status

SERVICE STATUS 

                    OK

1.

service

status

MON                11-19-01 

12:00 AM                    72F

modulating output 1 and di1 

Status Screen.

 Shows the percent-

age of modulating output 1 and sta-

tus for DI1.  

 

 

 

di2 and di3 Status Screen.

Shows DI2 status and filter status or 

DI3 status. 

 

 

 

 

main monitoring Screen.

 (Date not 

shown on SZ1017a & SZ1017aW.)

service

status

DI2  SERVICE        OFF

FILTER 

OK

8.

service

status

COOL STAGE 1     ON

COOL STAGE 2     OFF

6.

MON 

08-08-08

12:00AM 

72F

Occupied

Heating

C ooling

Fan

S ervice

Program/

Data

Содержание SZ1041A

Страница 1: ...l time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 4 Setting Clock Schedule 8 Operation 9 Checkout Troubleshooting 12 LED Description 14 Limiting Occupant Access 15 User s Guide 15 Mounting The SZ1041A is designed for wall...

Страница 2: ...sensors Consult the TS Series Temperature Sensor Submittal Data sheet for a complete listing of packaging and application styles When using TCS Basys Controls three wire sensors use the black and red leads and either clip or twist off the white lead Make sure that the dip switches are set for the sensors you are using Powering the SZ1041A Superstats are powered from 24 VAC 20 If wiring for communi...

Страница 3: ... Using remote room sensor with both discharge and outdoor air sensors KEypad Access The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of programming and or to set the clock and sched ule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in programming The fan and sys...

Страница 4: ...re indication System Access Screen Choose whether or not to enable user s access to the sys tem switch to set the system mode System Mode Screen Choose from AUTO HEAT COOL or OFF for system mode In the OFF mode all outputs are off Fan Access Screen Choose whether or not to enable the user s access to the fan switch to set the occupied fan mode Occupied Fan Mode Screen Choose between ON continuous ...

Страница 5: ... if heat stage 2 is enabled as heat Heat Stage 2 Differential Screen Enter a differential value for heat stage 2 This screen only appears if heat stage 2 is enabled Cool Stage 1 Offset Screen Enter an offset value for cool stage 1 First stage is normally 0 offset Cool Stage 1 Differential Screen Enter a differential value for cool stage 1 Cool Stage 2 Offset Screen Enter an offset value for cool s...

Страница 6: ...isabled AO CONTROL BASED ON SPACE 48 program setup ENABLE HEATING LOW LIMIT YES 49 program setup ENABLE MOD OUT 1 MIN MAX POS YES 54 program setup MOD OUT 1 MIN POS 10 55 program setup MOD OUT 1 MAX POS 99 56 program setup Reset Ratio Factor Screen Enter a reset ratio factor This is the number of degrees that the discharge air setpoint is raised when the space tempetature falls by 1 degree for hea...

Страница 7: ...cess Screen Choose whether or not a code will be required to enter programming setup A dipswitch option to lock out access altogether is also avail able Clock and Schedule Access Screen Choose whether or not a code will be required to enter clock and schedule setup A dipswitch option to lock out access alto gether is also available Access Code Screen Enter an access 0 to 255 code that will be used...

Страница 8: ... next screen does not appear Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Holiday Announcement Screen Announces the next screen Holidays 1 Screen Set holiday peri ods 1 through 12 month date and dura tion for the periods that will follow the holiday 1...

Страница 9: ...in the occupied mode whenever the DI3 contact is closed When using this option the timed override may still be activated The software allows you to override the thermostat by putting the override parameter into the remote mode and thus disabling the timed override Setback and Override Applications In most applications it is desired to maintain a regular schedule and allow timed override with the b...

Страница 10: ...ue to operate according to its occupied setting If you are using DI2 as monitor for another purpose make sure to set the setpoint shift value to zero R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 10 Stage Output Parameters The SZ1041A will control up to two stages of either heat ing or cooling The SZ1041A will control two stages of heating and two stages of co...

Страница 11: ...41A has delays built into the programming sequences to protect equipment The fan has a mini mum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling devices are allowed to sequence on and remain on for 2 minutes after the heating or cooling devices sequence off Each stage has a minimum on and off time of two minutes There is a ...

Страница 12: ... that the top LED is lit If not press the OVERRIDE button The LED should light up 6 Take note of the current temperature reading Press DIGITAL APPLICATION LED SERVICE SCREEN CONTROL SENSOR OR INPUT INDICATION DI STATUS SCREEN PROVIDED DEVICE NEEDED DI1 Fan Proving YES CHECK FAN YES turns system mode to off Differential FAN OK requires manual re start pressure or or FAIL set system to auto current ...

Страница 13: ...ystem switch button and the service status button simultaneously the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five degrees The fan will come on The heating stage s will sequence on after 30 seconds 7 Press the cooler down button until the heating set point is one degr...

Страница 14: ...ir limit has been reached when the fan interlock has indi cated failure or when the filter service or service input are closed PROGRAM DATA This LED will be lit when the thermostat is within the programming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is available by continually pressing the service key Main Monitoring Screen Press the service bu...

Страница 15: ...on to allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 64 or access may be denied altogether using dipswitches described in the setup sec tion Programming The ...

Отзывы: