background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

13

Fan does not Come on

The fan is on whenever the fan LED is on. If the fan 

should be on, but the fan LED is off, check the fan and 

system switch modes, and the unoccupied fan mode 

in programming. If the fan is off but the fan LED is on, 

check wiring. Short terminals “R” to “G” and see if the 

fan comes on. This is a check for a mechanical relay 

failure. 

heating or Cooling does not Come on

At least one stage of heating is on whenever the  heat-

ing LED is on, and at least one stage of cooling is on 

whenever the cooling LED is on. If heating or cooling 

should be on but the heating or cooling LED is off, check 

the fan and system switch modes. Also, check the heat-

ing and cooling setpoints, offsets and differentials, and 

the room temperature to be sure heating or cooling 

should be on. If using outdoor air heating and cooling 

lockouts, or discharge air high and low limits, check 

their values to be sure heating or cooling is allowed. If 

heating or cooling is off, but the corresponding LED is 

on, check the wiring. Short terminals “R” to “Y/W1” or 

“Y/W2” and see if the heating or cooling comes on. This 

is a check for a mechanical relay failure. 

Wrong temperature display

If any of the temperatures are reading slightly high or low, 

there are three adjustment pots located in the cover to 

adjust them. “T1” is for the room temperature, “T2” is for 

the discharge air temperature, and “T3” is for the outdoor 

air temperature. If the temperature is at a minimum or maxi-

mum reading, check the sensor dipswitch positions. (See 

setup instructions.) Check for wiring problems (opens or 

shorts). A remote 1000 

 sensor  should read 108 to 109 

 

at room temperature. 

T1

T2
T3

1  2

1  2  3  4  5

adjust display contrast

Service led is on

If the service LED is on, it may be for monitoring purpos-

es or it may indicate a critical problem. The first monitor-

ing screen accessed by pressing the service status but-

ton will display why the light is on.

outputs Will not Shut off

First check the room temperature and the setpoints and 

determine whether the output should be on. There are 

delays and minimum on and off times for the fan and 

heating and cooling stages. Also, check the service 

status menus to verify that the outputs are on. Turning 

the system to “off” will instantly turn all outputs off. The 

thermostat can be reset by pressing the system switch 

button and the service status button simultaneously.  

the WARMER (up) button. The setpoint adjustment 

screen should now be showing. Press the WARMER 

button until the heating setpoint is greater than the 

current temperature by at least five degrees. The fan 

will come on. The heating stage(s) will sequence on 

after 30 seconds. 

7. Press the cooler (down) button until the heating set-

point is one degree less than the current tempera-

ture. The heating stage(s) will sequence off. The fan 

will turn off 2 minutes after the last heating stage. 

8.  Press the cooler button until the cooling setpoint is 

less than the current temperature by at least five 

degrees. The fan will come on.  The cooling stage(s) will 

sequence on after 2 minutes. 

9.  Press the warmer button until the cooling setpoint is 

greater than the current temperature by one degree. 

The cooling stage(s) will sequence off. The fan will 

turn off 2 minutes after the last cooling stage.

10. For a heating or cooling analog output: Take note 

of the room (and discharge) air temperatures. If the 

analog output is set for Cooling, press the Cooler but-

ton until the cooling setpoint is less than the current 

room temperature by at least 5°. The cooling device 

should start operating. If the analog output is set for 

Heating, press the Warmer button until the heating 

setpoint is greater than the current room temperature 

by at least 5°. The heating device should start operat-

ing.

11. For an economizer analog output: Take note of the 

discharge and outdoor air temperatures. Go to pro-

gramming step #42 and set the outdoor air setpoint 

5° greater than the outdoor air temperature. Go to 

programming step #43 and set the discharge air 

setpoint 10° less than the discharge air temperature. 

Press the Cooler button until the cooling setpoint is 

less than the current room temperature by at least 

5°. The damper should now be fully open. Raising 

the discharge air setpoint, will modulate the damper 

closed. Raising the cooling setpoint above the room 

temperature or lowering the outdoor air setpoint 

below the outdoor air temperature will shut the damp-

er to minimum position.

12. Go back to programming step #20 and set the set-

point adjust limit back to the desired value. Make any 

other changes in programming, clock, and schedule. 

Set the fan and system modes to their desired set-

tings. 

13. If using remote sensor(s), verify that the reading is 

correct. If not, see 

Wrong Temperature Display

 in 

troubleshooting

 section.

tRoUBleShooting
no display

Check for 24 VAC on terminals “+24” and “-24”. Check 

the cable connecting the cover to the base for a good 

connection.

Содержание SZ1041A

Страница 1: ...l time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 4 Setting Clock Schedule 8 Operation 9 Checkout Troubleshooting 12 LED Description 14 Limiting Occupant Access 15 User s Guide 15 Mounting The SZ1041A is designed for wall...

Страница 2: ...sensors Consult the TS Series Temperature Sensor Submittal Data sheet for a complete listing of packaging and application styles When using TCS Basys Controls three wire sensors use the black and red leads and either clip or twist off the white lead Make sure that the dip switches are set for the sensors you are using Powering the SZ1041A Superstats are powered from 24 VAC 20 If wiring for communi...

Страница 3: ... Using remote room sensor with both discharge and outdoor air sensors KEypad Access The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of programming and or to set the clock and sched ule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in programming The fan and sys...

Страница 4: ...re indication System Access Screen Choose whether or not to enable user s access to the sys tem switch to set the system mode System Mode Screen Choose from AUTO HEAT COOL or OFF for system mode In the OFF mode all outputs are off Fan Access Screen Choose whether or not to enable the user s access to the fan switch to set the occupied fan mode Occupied Fan Mode Screen Choose between ON continuous ...

Страница 5: ... if heat stage 2 is enabled as heat Heat Stage 2 Differential Screen Enter a differential value for heat stage 2 This screen only appears if heat stage 2 is enabled Cool Stage 1 Offset Screen Enter an offset value for cool stage 1 First stage is normally 0 offset Cool Stage 1 Differential Screen Enter a differential value for cool stage 1 Cool Stage 2 Offset Screen Enter an offset value for cool s...

Страница 6: ...isabled AO CONTROL BASED ON SPACE 48 program setup ENABLE HEATING LOW LIMIT YES 49 program setup ENABLE MOD OUT 1 MIN MAX POS YES 54 program setup MOD OUT 1 MIN POS 10 55 program setup MOD OUT 1 MAX POS 99 56 program setup Reset Ratio Factor Screen Enter a reset ratio factor This is the number of degrees that the discharge air setpoint is raised when the space tempetature falls by 1 degree for hea...

Страница 7: ...cess Screen Choose whether or not a code will be required to enter programming setup A dipswitch option to lock out access altogether is also avail able Clock and Schedule Access Screen Choose whether or not a code will be required to enter clock and schedule setup A dipswitch option to lock out access alto gether is also available Access Code Screen Enter an access 0 to 255 code that will be used...

Страница 8: ... next screen does not appear Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Occupied Times Screen Set hours or minutes of start and end times for up to two occupied periods Holiday Announcement Screen Announces the next screen Holidays 1 Screen Set holiday peri ods 1 through 12 month date and dura tion for the periods that will follow the holiday 1...

Страница 9: ...in the occupied mode whenever the DI3 contact is closed When using this option the timed override may still be activated The software allows you to override the thermostat by putting the override parameter into the remote mode and thus disabling the timed override Setback and Override Applications In most applications it is desired to maintain a regular schedule and allow timed override with the b...

Страница 10: ...ue to operate according to its occupied setting If you are using DI2 as monitor for another purpose make sure to set the setpoint shift value to zero R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsbasys com 10 Stage Output Parameters The SZ1041A will control up to two stages of either heat ing or cooling The SZ1041A will control two stages of heating and two stages of co...

Страница 11: ...41A has delays built into the programming sequences to protect equipment The fan has a mini mum on and off time of 30 seconds When the fan is in AUTO or COOL mode it will come on 30 seconds before the heating or cooling devices are allowed to sequence on and remain on for 2 minutes after the heating or cooling devices sequence off Each stage has a minimum on and off time of two minutes There is a ...

Страница 12: ... that the top LED is lit If not press the OVERRIDE button The LED should light up 6 Take note of the current temperature reading Press DIGITAL APPLICATION LED SERVICE SCREEN CONTROL SENSOR OR INPUT INDICATION DI STATUS SCREEN PROVIDED DEVICE NEEDED DI1 Fan Proving YES CHECK FAN YES turns system mode to off Differential FAN OK requires manual re start pressure or or FAIL set system to auto current ...

Страница 13: ...ystem switch button and the service status button simultaneously the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five degrees The fan will come on The heating stage s will sequence on after 30 seconds 7 Press the cooler down button until the heating set point is one degr...

Страница 14: ...ir limit has been reached when the fan interlock has indi cated failure or when the filter service or service input are closed PROGRAM DATA This LED will be lit when the thermostat is within the programming or clock setup menus It will blink when the unit is being accessed by a PC Additional monitoring is available by continually pressing the service key Main Monitoring Screen Press the service bu...

Страница 15: ...on to allow the occupant to change the system mode is allowed by factory default To lock out access to system switching see programming step 5 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 64 or access may be denied altogether using dipswitches described in the setup sec tion Programming The ...

Отзывы: