HGP Kit Manual
6.0 Troubleshooting
54
6.0
Troubleshooting
HarmonicGuard
®
Passive Filter Status Warning
If the desktop interface indicates a status warning, hover over the status detection for a brief
description. Depending on the condition there are multiple ways to try and clear the status
warnings.
Only qualified electricians should carry out all electrical installation & maintenance work on the
HGP.
Disconnect all sources of power to the and connected equipment before working on the
equipment. Do not attempt any work on a powered HGP.
This HGP unit contains high voltages and capacitors. Wait at least five minutes after
disconnecting power from the filter before attempting to service the conditioner. Check for zero
voltage between all terminals on the capacitors. Also, check for zero voltage between all phases
of the input and output lines. All maintenance and troubleshooting must be done by a qualified
electrician. Failure to follow standard safety procedures may result in death or serious injury.
Unless an external disconnect means has been provided everything ahead of the filter
circuit breaker, including the reactors, will still be energized.
Receiving Inspection
The connectivity board has been thoroughly inspected and functionally tested at the factory and
carefully packaged for shipment. After receiving the unit, immediately inspect the shipping
container and report any damage to the carrier that delivered the unit. Verify that the part number
of the unit received is the same as the part number listed on the purchase order.
Connectivity Board Problem
The HGP is comprised of five major components; the PQconnect connectivity board, the line
reactor, the tuning reactor, the contactor and the capacitors. The PQconnect PCB contains
diagnostic LEDs. The locations of the LEDs are shown in Figure 29 and their functions are listed
Warning