HGP Kit Manual
5.0 PQconnect
26
Table 10: Form C Relay Contacts/ Customer Inputs/Outputs
Terminal
Pin
Description
Label
Tightening Torque
Wire Range
J7
1, 2
Multi-functional
digital Input 1
Customer contact,
normally open
3.5 lb-in (0.4 Nm)
28-12 AWG
J8
1, 2
Multi-
functional
digital Input 1
Customer contact,
normally open
3.5 lb-in (0.4 Nm)
28-12 AWG
J11
1
Digital output
form C Contact
1
Normally Closed (NC)
4.4 lb-in (0.5 Nm)
28-14 AWG
2
Common (COM)
3
Normally Open (NO)
J10
1
Digital output
form C Contact
2
Normally Closed (NC)
4.4 lb-in (0.5 Nm)
28-14 AWG
2
Common (COM)
3
Normally Open (NO)
Note
: Form-C relay contacts are gold plated with a load rating of 5.0A @ 120VAC
The filter is set to control the contactor pickup/drop-out at 30% of load current by factory
default. This setting can be changed in the tech access page from the settings menu.
Multi-functional digital inputs
have the following functions:
•
3 = Reset Command
•
4 = External Control Input
Digital Output form C Contact
•
J11 reserved for contactor control
•
J10 used for status detection
PQconnect PCB Calibration
Once the PQconnect connections are made the PCB must be calibrated to the HGP filter
components to ensure proper accuracy and operation of the completed filter. The following steps
will allow for units to be properly calibrated.
Note:
Instillation of the PQvision desktop interface is required for calibration. Please see next
section “PQvision Software” before proceeding with PCB calibration.
Equipment:
Calibrated current clamp meter, laptop, RS485 to USB converter
Step 1:
After assembling HGP with PQconnect, ground the filter and install
only the line side
connections
to the appropriate phases first.
Do not install the load side connections for
calibration process
.
Ensure communication connections and voltage sense wires are made, follow Table 8: Power &
Communications Terminals for further detail.
Step 2:
Energize filter
Step 3:
Open PQvision interface and connect to a communication port
•
A “CONNECTED” message will appear verifying that the RS485 converter is connected
to the board.
•
If there are any difficulties communicating to the desktop interface, a “NO COM” message
will appear. Refer to the Trouble Shooting section for possible solutions.
•
DEFAULT: 0 = Disabled
•
1 = Tuning Reactor Thermal Switch Input
•
2 = Line Reactor Thermal Switch Input