HGP Kit Manual
5.0 PQconnect
21
Installation
Installation Checklist
The following are the key points to be followed for a successful installation of the PQconnect
board.
Make sure that the installation location will not be exposed to direct sunlight, corrosive
or combustible airborne contaminants, excessive dirt or liquids.
Select a mounting area that will allow adequate cooling air and maintenance access.
Make sure that all wiring conforms to the requirements of the National Electrical Code
(NEC) and/or other applicable electrical codes.
Connect the HGP equipment-grounding lug to the system ground of the premises
wiring system. Use a properly sized grounding conductor.
Connect three-phase power from the KDR Line reactor to the input terminals of the
PQconnect board, J1, J2, and J3.
Connect 120VAC Power (customer supplied) to the input power supply header J12 on
the PCB
Connect RS 485 to USB serial converter to the Modbus RTU header J5.
Use PQvision software from TCI website to calibrate PQconnect PCB.
Ensure all component connections are torqued before energizing filter.
NOTE:
PQvision software is required to calibrate the PQconnect PCB
Mounting
Selecting a Suitable Location
When mounting the PQconnect board, provide an adequately ventilated location to prevent
overheating. Refer to the applicable kit drawings for PCB dimensions. The maximum temperature
of the air around the HGP filter components should not exceed 50°C (122°F). Consult the watts
loss columns above in Filter Wire Sizing for Watts Loss when planning enclosure ventilation.
When selecting a mounting location for the PQconnect PCB, plan for the routing of the power
wiring. Figure 11 Shows a representative schematic of power wiring. Note that there are direct
connections from the KDR line reactor to the PQconnect PCB.