KMS-2/Exia/Exd Transmitter
Installation and Operating Manual
Page 12 of 16 KMS-2:Exia/Exd IOM
Rev H 18/05/10
ATEX
TECHNICAL DATA
Materials
Measuring probe: -
316L
Housing: -
Epoxy coated aluminium or 316L Stainless steel
Cable entry
Thread Size: -
M20x1.5mm
Connection conductor size: -
0.5mm² - 2.5mm²
Supply voltage (Nominal 24VDC)
Minimum
12V
Maximum
28V
Current Output
Measured Current range: -
4-20mA ± 0.1%
Alarm Current: -
3.8mA…. 22mA
Upscale
22mA (Fault)
Downscale
3.8mA (Low level)
Fixed Output
4 or 20mA ± 0.1%
(For loop calibration)
Operating Temperatures
(See certification section for details when used in a potentially explosive atmosphere)
Ambient range: -
-50°C / + 60°C (-5°C / +60°C When LCD Fitted)
Process range: -
-50°C/ +250°C
Fig 7
Ambient verses process temperature for standard transmitter