Chapter 2 Installation
System Configuration
TC8612 Rev 1.1 User Manual
2-4
2.7.2
Rear Panel
Figure 2-2 TC8612 Rear Panel
2.7.2.1
Rear Panel DIP Switch Functions
The DIP switch functions on the TC8612 are described below. To activate the
function, slide the appropriate switch to the On (Down) position.
•
LOCLB:
Local Loopback. This switch (SW1) initiates the Local Loopback
function. The dry contact detect status (RX) is looped back to the relay closure
pins (TX) for diagnostic testing.
•
RMTLB:
Remote Loopback. This switch (SW2) initiates the Remote
Loopback function. Enabling this function on the local unit triggers the remote
unit to loopback the received dry contact closure detect status.
Rear Panel Dip Switch Functions
SW1: LOCLB (Local Loopback)
x
Down (On): Enable local loopback.
x
Up (Off):
Disable local loopback.
SW2: RMTLB (Remote Loopback)
x
Down (On): Enable remote loopback.
x
Up (Off):
Enable remote loopback.
SW3: INT CLK (Internal Clock)
x
Down (On): Enable internal timing mode.
x
Up (Off):
Enable RX loop timing mode.
SW4: B8ZS / HDB3 (Line Code)
x
Down (On): B8ZS (T1) / HDB3 (E1)
x
Up (Off): AMI
SW5: DIS ALM (Disable Alarm)
x
Down (On): Disable alarm buzzer and dry
contact.
x
Up (Off):
Enable alarm buzzer and dry
contact.
SW6, SW7, SW8: L1, L2, L3 (Line Build-Out)
L1 L2 L3
T1
Up Up Up
0
–
133
feet
Down Up
Up
133
–
266
feet
Up
Down
Up
267 – 399 feet
Down
Down
Up
400 – 533 feet
Up
Up
Down
534 – 655 feet
Down Up Down -7.5dB
CSU
Up Down Down
-15dB
CSU
Down Down Down
-22.5dB
CSU
L1 L2 L3
E1
Up
Up
Up
75 ohm Normal
Down
Up
Up
120 ohm Normal
Up
Up
Down
75 ohm High Loss
Down
Up
Down
120 ohm High
Loss
AMI (Line Code) LED
x
Solid: Unit is set for AMI line-code.
x
Off:
Unit is set for B8ZS (T1) / HDB3 (E1)
line-code.
RAI (Remote Alarm Indicator) LED
x
Flash: Unit detected RAI (
Yellow Alarm
).
x
Off: Normal condition.
AIS (Alarm Indication Signal) LED
x
Flash: Unit detected AIS (
Blue Alarm
).
x
Off: Normal condition.
LOS (Loss of Signal) LED
x
Flash: No T1/E1 signal is detected.
x
Off:
Valid T1/E1 signal is detected.
Alarm Relay
NC (Normal Close)
x
Close: When power is on and the alarm is off.
x
Open: When power is off, or the alarm is on.
NO (Normal Open)
x
Open: When power is on and the alarm is off.
x
Close: When power is off, or the alarm is on.