04
TMAX Maximum Heatsink Temperature
60-100
85
C
3
45
0A
CFLT
Current Fault
---
---
---
3
45
11
STAT
Inverter Status Byte
BINARY (8)
---
---
3
45
22
FNCT
Inverter Operating Function
0-4
---
---
3
46
23
CNTL
Control Information Byte
BINARY (8)
---
---
3
47
25
FEXT1 External Speed #1
0.00-400
0
Hz
3
47
26
FEXT2 External Speed #2
0.00-400
0
Hz
3
47
28
TLEXT External Torque Limit Reference
0-150
0
%
3
47
29
COUT Control Output Status
BINARY (8)
---
---
3
47
7A
CIN
Control Board Terminal Status
BINARY (8)
---
---
3
48
7B
CIN2
Option Board Terminal Status
BINARY (8)
---
---
3
48
7C FIN
Control Board Analog Input Status
0-32768
0
---
3
48
7D FAUX
Option Board Analog Input Status
0-32768
0
---
3
48
7E
LIM
Analog Torque Limit Input Status
0-15000
15000
---
3
48
91
SIOC
SIO Communication BAUD Rate
0-7
0
---
3
48
92
SIOA
SIO Slave Address
1-94
1
---
3
48
93
SIOT
SIO Watchdog Timer
0.00-60.00
0.00
s
3
48
94
SIOF
SIO Fault Byte
BINARY (8)
---
---
3
49
95
SIOP
SIO Protocol
0-3
0
---
3
49
44
SECTION 5
LEVEL 3 PARAMETER DESCRIPTIONS AND PROGRAMMING
The following is a summary of the parameters associated with SIO communication. Consult Form 997 - SIO Serial
Link Protocol or the factory for more information on the use of WFC
HT
Series inverters in serial communication
applications.
5.1 Program Code Summary (Level 3)
#
Name
Description
Data
Factory Units Access See
Customer
Range
Setting
Level
Page
Setting
5.2 Programming
To change the default programming for a given parameter from the keypad:
A. Press the STOP key, if the inverter is running. Some parameters (see the
individual parameter description) can be changed while the inverter is
operating.
B. To enter Level 1 programming, press the PROGram key. To enter Level 3, hold the SHIFT key and press the
PROGram key.
C. Use the UP/DOWN arrow keys to select the program parameter for change.
D. Press the SHIFT key. The program number will blink indicating that the data value may be changed.
E. Use the UP/DOWN arrow keys to select the new data code.
F. Press the ENTER key. The display will indicate **STORED** for one second, then revert to the normal parameter
display.
G. Press the PROGram key to exit the programming mode or the UP/DOWN arrow keys to select a new parameter for
change.
S I O S L A V E A D D R
P R O G 9 2 :
1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание WFC1000 Series
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 5: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 77: ...69 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 80: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...