49
Figure 42
RC through the pole installation example
RC installation example at substation mounting kit is shown in figure below.
Figure 43
RC substation installation example
Auxiliary VT Installation
4.2.3
Auxiliary voltage transformer should be installed on the separate mounting bracket, providing a reliable and
robust attachment of the transformer at the pole or at the substation mounting structure.
Line connections to the auxiliary voltage transformer should be performed in accordance to the VT technical
manual by trained personnel who are familiar with the equipment.
Earthing
4.2.4
ATTENTION!
The OSM, it’s mounting frame and RC5_4 should be connected to the same earthing bar
using 12mm nuts and bolts tightened to 50 Nm. Do not violate this. For more details see the Handling and
Installation guide.
Earthing points on the OSM and RC5_4 are shown below.
Содержание Rec15/25 Al1 5p
Страница 1: ......
Страница 8: ......
Страница 9: ...1 Product Description...
Страница 15: ...15 Figure 11 CPM control and indication functions...
Страница 25: ...2 Nameplates and Seals...
Страница 29: ...3 Product Handling...
Страница 42: ......
Страница 43: ...4 Installation...
Страница 57: ...5 Commissioning...
Страница 60: ......
Страница 61: ...6 Operation...
Страница 78: ...78...
Страница 79: ...7 Maintenance and Troubleshooting...
Страница 93: ...8 Disposal...
Страница 95: ...9 Appendices...
Страница 98: ...98 Appendix 2 RC5_4 Drawings Figure 97 Dimensions of RC5_4...
Страница 100: ...100 Figure 100 Dimensions of substation recloser package Figure 101 Placement of substation recloser components in a box...
Страница 102: ...102 Figure 103 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Страница 103: ...103 Figure 104 Dimensions of interface bracket...
Страница 104: ...104 Figure 105 Dimensions of OSM mounting kit with M16 pole interface front installation...
Страница 105: ...105 Figure 106 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Страница 106: ...106 Figure 107 Dimensions of OSM mounting kit with M20 pole interface front installation...
Страница 107: ...107 Figure 108 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Страница 108: ...108 Figure 109 Dimensions of OSM mounting kit for installation through the pole front installation...
Страница 109: ...109 Figure 110 Dimensions of OSM mounting kit for installation through the pole lateral installation...
Страница 118: ...118 Figure 119 Dimensions of OSM substation mounting kit...
Страница 119: ...119 Figure 120 Dimensions of OSM substation mounting kit...
Страница 120: ...120 Figure 121 Dimensions of RC mounting kit for around the pole installation 500 mm U profiles 450 mm M16 threaded rods...
Страница 122: ...122 Figure 123 Dimensions of RC mounting kit for through the pole installation...
Страница 123: ...123 Figure 124 Dimensions of RC substation mounting kit...
Страница 124: ...124 Figure 125 Dimensions of VT mounting kit One VT holder...
Страница 129: ...129 Figure 134 Dimenssions of VT pole mounting kit Two VT holders two 700 mm U profiles base holder...
Страница 132: ...132 Appendix 5 RC5_4 Wiring Diagram Figure 139 RC5_4 wiring diagram...
Страница 135: ...135...
Страница 136: ......