72
Figure 73
Downloading protection settings via TELARM
6.6.1.2
Protection Settings Modification
Protection settings can be changed locally (via the MMI or the PCI) or remotely via the TDI interface.
Protection settings modifications using the MMI:
Main menu -> Settings -> Protection -> Group #
Protection settings can be changed in each protection group independently.
NOTE!
To apply updated settings it is required to upload them to the controller. Uploading settings is
de
scribed in “Uploading protection settings”.
To edit protection locally (PCI) the following actions should be performed:
1) Open the model in the database where settings shall be changed (Figure 74)
2) Double click on “Group 1” submenu (or other protection settings group) of the model
Database browser -> Model -> Protection settings -> Group 1
3) “Protection settings” window will popup
After “Protection settings window Group 1” (or other protection settings group) appears it is possible to:
1) Change protection settings;
2) For your convenience you may hide or show protection element settings by using “+” and “–“ buttons. You
may plot the TCC curve of the protection element by pushing the TCC button (Figure 74).
Содержание Rec15/25 Al1 5p
Страница 1: ......
Страница 8: ......
Страница 9: ...1 Product Description...
Страница 15: ...15 Figure 11 CPM control and indication functions...
Страница 25: ...2 Nameplates and Seals...
Страница 29: ...3 Product Handling...
Страница 42: ......
Страница 43: ...4 Installation...
Страница 57: ...5 Commissioning...
Страница 60: ......
Страница 61: ...6 Operation...
Страница 78: ...78...
Страница 79: ...7 Maintenance and Troubleshooting...
Страница 93: ...8 Disposal...
Страница 95: ...9 Appendices...
Страница 98: ...98 Appendix 2 RC5_4 Drawings Figure 97 Dimensions of RC5_4...
Страница 100: ...100 Figure 100 Dimensions of substation recloser package Figure 101 Placement of substation recloser components in a box...
Страница 102: ...102 Figure 103 Dimensions of standard OSM mounting kit arrangement for lateral installation...
Страница 103: ...103 Figure 104 Dimensions of interface bracket...
Страница 104: ...104 Figure 105 Dimensions of OSM mounting kit with M16 pole interface front installation...
Страница 105: ...105 Figure 106 Dimensions of OSM mounting kit with M16 pole interface lateral installation...
Страница 106: ...106 Figure 107 Dimensions of OSM mounting kit with M20 pole interface front installation...
Страница 107: ...107 Figure 108 Dimensions of OSM mounting kit with M20 pole interface lateral installation...
Страница 108: ...108 Figure 109 Dimensions of OSM mounting kit for installation through the pole front installation...
Страница 109: ...109 Figure 110 Dimensions of OSM mounting kit for installation through the pole lateral installation...
Страница 118: ...118 Figure 119 Dimensions of OSM substation mounting kit...
Страница 119: ...119 Figure 120 Dimensions of OSM substation mounting kit...
Страница 120: ...120 Figure 121 Dimensions of RC mounting kit for around the pole installation 500 mm U profiles 450 mm M16 threaded rods...
Страница 122: ...122 Figure 123 Dimensions of RC mounting kit for through the pole installation...
Страница 123: ...123 Figure 124 Dimensions of RC substation mounting kit...
Страница 124: ...124 Figure 125 Dimensions of VT mounting kit One VT holder...
Страница 129: ...129 Figure 134 Dimenssions of VT pole mounting kit Two VT holders two 700 mm U profiles base holder...
Страница 132: ...132 Appendix 5 RC5_4 Wiring Diagram Figure 139 RC5_4 wiring diagram...
Страница 135: ...135...
Страница 136: ......