Fail Mode
Prg
Set
c5
c5
–
PID Control Mode
This value can be set to 1 or 0. The default setting is 1 for all PowerAire
units where a value of 0 should be enter for all SmartAire units. This will
ensure that if the temperature tree or other errors occur that the fan will
increase it’s fan speed to maximum
, or that the damper will open to
100%.
P1
P1
–
Proportional Term
This term is the proportional gain constant, and take the value of 1/P1, a
larger P1 will slow the speed of reaction to temperature change. The default
value is 45, which produces a conservative response, for faster acting fan
control, decrease the value. Instant fan speed response can be achieve by
setting this value to 1.
c62
c62
–
Integral Term
This value adjusts the effect of the integral term of the PID controller, this
value examines the current difference in the set point, as well as historic
error, to determine the change in set point. Increasing this value increases
the time the controller examines older data, decreasing it shortens the
window of data examined
c33
Prg
Set
Prg
Set
Prg
Set
Prg
Set
c33
–
Special Control
Functions
This value must be set to 1 to enter the following configuration variables.
Press set to edit the variable, adjust the value to 1, and press set to store the
value.
F38
Prg
Set
F38
–
Min/Max Control
Setting this value to 1 will enable the minimum and maximum fan speed or
damper positions values.
d40
Prg
Set
d40
–
Minimum Control Value
This variable assigns, as a percentage, the minimum fan speed or damper
positions that the SmartAire S or PowerAire S will settle to when the set point
has been satisfied. This can be useful to ensure a minimum desired airflow
from the fan or damper at all times.
Please continue to the next page
This value enables the PID control mode. The value should always be
set to 1 to ensure continuous PID controller operation.