 Fail Mode  

Prg

Set

c5

c5 

 PID Control Mode 

This value can be set to 1 or 0. The default setting is 1 for all PowerAire 
units where a value of 0 should be enter for all SmartAire units. This will 

ensure that if the temperature tree or other errors occur that the fan will 

increase it’s fan speed to maximum

, or that the damper will open to 

100%.

P1

P1 

 Proportional Term

This term is the proportional gain constant, and take the value of 1/P1, a 

larger P1 will slow the speed of reaction to temperature change. The default 

value is 45, which produces a conservative response, for faster acting fan 

control, decrease the value. Instant fan speed response can be achieve by 

setting this value to 1. 

c62

c62 

 Integral Term 

This value adjusts the effect of the integral term of the PID controller, this 

value examines the current difference in the set point, as well as historic 

error, to determine the change in set point. Increasing this value increases 

the time the controller examines older data, decreasing it shortens the 

window of data examined

c33

Prg

Set

Prg

Set

Prg

Set

Prg

Set

c33 

 Special Control 

Functions

This value must be set to 1 to enter the following configuration variables. 

Press set to edit the variable, adjust the value to 1, and press set to store the 

value.

F38

Prg

Set

F38 

 Min/Max Control

Setting this value to 1 will enable the minimum and maximum fan speed or 

damper positions values.

d40

Prg

Set

d40 

 Minimum Control Value

This variable assigns, as a percentage, the minimum fan speed or damper 

positions that the SmartAire S or PowerAire S will settle to when the set point 

has been satisfied. This can be useful to ensure a minimum desired airflow 

from the fan or damper at all times.

Please continue to the next page

This value enables the PID control mode. The value should always be 

set to 1 to ensure continuous PID controller operation.