Task Force Tips LIY-250 Скачать руководство пользователя страница 3

©Copyright Task Force Tips LLC 2010-2021

3

LIY-250 May 10, 2021 Rev03

1.0 MEANING OF SAFETY SIGNAL WORDS

A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a particular

hazard. Per ANSI Z535.6, the definitions of the four signal words are as follows:

2.0 SAFETY

3.0 GENERAL INFORMATION

The 4.5” Quick Connect allows a monitor or elbow to be quickly and easily installed, removed and replaced. Applications include front

bumper  mounts  for  tilt-cab  chassis  maintenance,  and  sharing  monitors  between  multiple  standpipes. A  ratcheting  pull  pin  prevents

loosening of 4.5”NH threads due to vibration. The elbow may be used to supply a fire pump in lieu of a hydrant. 
Maximum operating  pressure  for  elbow  is  300  psi  (20  bar),  with a  hydrostatic proof  test  pressure  of  900 psi  (62  bar).  See monitor

instruction manuals for maximum operating pressure of Monsoon, Typhoon, and Hurricane series monitors.

3.1 SPECIFICATIONS

.0

Table 3.1

3.2 USE WITH SALT WATER

Use with salt water is permissible provided the equipment is thoroughly cleaned with fresh water after each use. The service life of the

equipment may be shortened due to the effects of corrosion, and is not covered under warranty. 

DANGER

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious 

injury.

CAUTION

CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor

or moderate injury.

NOTICE

NOTICE is used to address practices not related to physical injury.

DANGER

An inadequate supply of pressure and/or flow will cause an ineffective stream and can result

in injury or death. Choose operating conditions to deliver adequate fire suppression. See flow

graphs. 

WARNING

This equipment is intended for use by trained personnel for firefighting. Use of this equipment for

other purposes may involve hazards not addressed by this manual. Seek appropriate guidance and 

training to reduce risk of injury. 

WARNING

The stream exiting a nozzle is very powerful and capable of causing injury and property damage.

Make sure the nozzle is securely attached and pointing in a safe direction before water is turned on.

Do not direct water stream to cause injury or damage to persons or property. 

WARNING

Equipment may be damaged if frozen while containing significant amounts of water. Such damage 

may be difficult to detect visually. Subsequent pressurization can lead to injury or death. Any time 

the equipment is subject to possible damage due to freezing, it must be tested and approved for 

use by qualified personnel before being considered safe for use. 

US

METRIC

Monitor Height Increase*

vs. model without Quick Connect

0.3 - 3.2”

0.7 - 8.1 cm

Monitor Weight Increase*

vs. model without Quick Connect

3.9 - 6.7 lb

1.8 - 3.0 kg

Elbow Dimensions** 

with 5” Storz

12.3 x 8.6 x 12.3”

31 x 21 x 31 cm

Elbow Weight**

with 5” Storz

13.7 lb

6.21 kg

Operating Temperature Range of Fluid

33°F to 120°F

1°C to 50°C

Storage Temperature Range

-40 to 150°F

-40 to 65°C

Materials

Hardcoat anodized and powder coated aluminum, 

316 Stainless Steel, Nylon, Nitrile rubber

* Monitor specifications assume same inlet adapter is installed for comparison.
** Elbow specifications do not include inlet adapter and vary by outlet coupling.
See LOT-022 Price List and Product Specifications for details of each inlet adapter option.

Содержание LIY-250

Страница 1: ...use Operation of this device without understanding the manual and receiving proper training is a misuse of this equipment Obtain safety information at tft com serial number This equipment is intended for use by trained and qualified emergency services personnel for firefighting All personnel using this equipment shall have completed a course of education approved by the Authority Having Jurisdicti...

Страница 2: ...d to familiarize firefighters and maintenance personnel with the operation servicing and safety procedures associated with this product This manual should be kept available to all operating and maintenance personnel Hurricane Dual Handwheel Hurricane Hurricane Extended Hurricane Tiller For 4 5 Quick Connect and Valve Under Monitor See Section 3 3 for Flow Pressure Operating Envelope Copyright Task...

Страница 3: ...elated to physical injury DANGER An inadequate supply of pressure and or flow will cause an ineffective stream and can result in injury or death Choose operating conditions to deliver adequate fire suppression See flow graphs WARNING This equipment is intended for use by trained personnel for firefighting Use of this equipment for other purposes may involve hazards not addressed by this manual See...

Страница 4: ...using injury and property damage if not properly supported Monitors should be securely installed by qualified individuals Mounting objects must be capable of withstanding maximum nozzle reaction force listed in SPECIFICATIONS The monitor must be securely mounted to rigid support members Do not use flanges or pipe made from plastic for monitor mounting Torque all fasteners to specified values WARNI...

Страница 5: ...ad trunnion between ports C2 and C3 serves as the Straight Ahead Reference Mark Travel ranges relative to the Straight Ahead Reference Mark can be modified by using Stop Bolts which are used to limit the travel See instruction manual for monitor for use of Stop Bolts Figure 4 2 TO USE 1 4 NPT PORT DRILL THRU USING 1 4 BIT MONITOR WITH 4 5 QUICK CONNECT TYPHOON SHOWN STRAIGHT AHEAD REFERENCE MARK E...

Страница 6: ... turn to clear the detents then release locking pin 2 Continue to rotate coupling until threads are no longer engaged 3 Lift the monitor out of the inlet adapter Figure 5 1 5 2 QUICK CONNECT ELBOWS Elbow is intended for temporary installation only so a locking pin is not needed see Figure 5 1 The full time swivel joint and tongues engaged into slots are able to prevent accidental disassembly due t...

Страница 7: ...e of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The original purchaser of the equipment any person to whom it is transferred and any person who is an intended or unintended beneficiary of the equipment shall not be entitled to recover from TFT any consequen...

Страница 8: ...g any part of this test must be removed from service repaired and retested upon completion of the repair 7 2 REPAIR Factory service is available with repair time seldom exceeding one day in our facility Factory serviced equipment is repaired by experienced technicians wet tested to original specifications and promptly returned Any returns should include a note as to the nature of the problem and w...