Operating Instructions
UIMip
SECURE
Release version/date: R1.1 / December 2019
© 2001-2019 TAPKO Technologies GmbH
Im Gewerbepark A15, 93059 Regensburg, Germany
Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved.
Product description
Connectors, buttons and LEDs description
The KNX IP (Secure) Interface UIMip-Sec provides an IP connection to
KNX TP. It is suitable for connection of KNX IP (Secure) devices, a PC with
ETS, and Ethernet networks. KNXnet/IP (Secure) Tunneling is supported.
Secure Tunneling, Secure Commissioning, and IP Backbone Security can
be activated.
For KNX devices, UIMip-Sec provides commissioning, configuring,
visualization, protocolling and diagnostic operation. Operational states,
malfunction and faulty communication are indicated by LEDs. With the
Function button UIMip-Sec can be reset to default settings. Long
messages with up to 240 byte APDU length are supported. For IP
(Secure) Tunneling, four (password-protected) Tunneling channels are
available.
UIMip-Sec is shown as UPnP network device. A disengageable web front-
end can be accessed to read out device settings, remotely activate
functions and watch a 60 min busload history diagram. The bootloader
function enables remote firmware updates via IP/Ethernet.
UIMip-Sec is suitable for 35 mm DIN rails and installation in distribution
boards. Supplied by the KNX bus line, it does not require an external
power supply. KNX IP devices can be connected directly and via Ethernet.
Requirements of Directives EMC, RoHS and LVD are met. Standards for
residential, commercial, and industrial environments are fulfilled. The full
text of the EU declaration of conformity is available at the following
internet address:
State IP
green:
Main line OK
Bus state KNX TP
green:
Subline OK
Telegram traffic IP
green (blinking):
Telegram traffic
Telegram traffic KNX TP
green (blinking):
Telegram traffic
red (blinking):
Transmission error
Programming LED
red:
Programming Mode active
red (blinking):
No IP connection
Ethernet connector
Programming button
Function button
KNX TP connector
Technical specifications
Power input
Power supply:
Current consumption:
Housing
Dimensions (HxWxD):
Mounting (IEC60715):
Width in space units:
KNX bus connection:
IP connector:
Weight:
Environmental conditions
Operating temperature:
Storage temperature:
Ambient humidity:
21…30 V DC SELV
< 20 mA
90 x 36 x 71 mm
35 mm top-hat rail (TH35)
2 modules at 18 mm
KNX connector (red/black)
Ethernet (RJ45, female)
68 g
-
5…45 °C
-20...60 °C
5…93 %
(non-condensing)
Electrical safety
Pollution degree (IEC60664):
Protection type (IEC60529):
Protection class (IEC61140):
Overvoltage category (IEC60664):
Approbation (ISO/IEC14543-3):
CE Marking
EU Directives:
Standards:
2
IP20
III
II
KNX-certified
LVD
(2014/35/EU)
EMC (2014/30/EU)
RoHS (2011/65/EU)
EN50491-5-1/-2/-3
EN50581
EN60950-1
EN61000-6-2/-3
IEC60950-1
Mounting, commissioning and safety notes
Installation and maintenance
•
After connection to the KNX bus system, the device works with its
default settings as intended
•
Warning
: Do not connect to 230 V. The device is supplied by the
KNX bus and does not require any additional external power supply
•
The device may only be installed and put into operation by a
qualified electrician or authorized person
•
For planning and construction of electric installations the appropriate
specifications, guidelines and regulations in force of the respective
country have to be complied
•
For mounting use an appropriate equipment according to IEC60715
•
Installation on a 35 mm DIN rail (TH35)
•
Connect the KNX bus line as for common KNX bus connections with a
KNX bus cable, to be stripped and plugged into a KNX TP connector
•
Do not damage electrical insulations during connecting
•
Installation only in dry locations
•
Accessibility of the device for operation and visual inspection must be
provided
•
For changing the configuration use the ETS
•
The housing must not
be opened
•
Protect the device from
moisture, dirt and
damage
•
The device needs no
maintenance
•
If necessary, the device
can be cleaned with a
dry cloth
•
In the case of damage
(at storage, transport)
no repairs may be
carried out by
unauthorized persons
•
Configuration details
and ETS database:
•
Device Certificate and Serial Number
are placed on a label sidely adhered.
For archiving, the certificate can be cut
off and removed. Afterwards, the cut-off
part can only be identified by
comparison of the Serial Number.
1
2
3
4
5
A
C
B
D