Operating Instructions 

TIO4  

SECURE 

Release version/date: R1.1 / December 2020 
© 2001-2020 TAPKO Technologies GmbH 
Im Gewerbepark A15, 93059 Regensburg, Germany 
Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved. 

Product description 

Connectors, buttons and LEDs description 

The TIO4-Sec Contact Interface is a 4-fold KNX input/output module to 
process binary signals and operate KNX devices via conventional push 
buttons, contact sensors and switches. KNX Data Secure is supported and 
Secure Commissioning can be activated. Input channels can be configured 
to output functionality. 
Due to its small size (50 mm diagonal), TIO4-Sec finds enough room in a 
flush-mounted box (Ø 60 mm) behind the switch. Cable pairs can be 
extended up to 10 m when twisted. Single channels can drive status LEDs. 
Designed for sensing NO/NC floating contacts, TIO4-Sec provides usual 
KNX input functions like switching, dimming, shutters, blinds control, 
counter and scenes. All kinds of potential-free contacts can be connected. 
LED blinking and brightness of connected status LEDs is configurable. For 
every single channel, it is possible to set brightness via object or use a 
night/day operation mode to set different day/night brightness values. 
Requirements of Directives EMC, RoHS and LVD are met. Standards for 
residential, commercial, and industrial environments are fulfilled. The full 
text of the EU declaration of conformity is available at the following 
internet address: 

www.tapko.de/ce

 

 

 

Cable pairs of Input/Output 
channels A B C D 

 

Programming button 

 

Programming LED 

red:  Programming Mode active

 

 

KNX TP connector 

Technical specifications 

Power input 

Power supply: 
Current consumption: 

Housing 

Dimensions (HxWxD): 
Flush mounting: 
KNX bus connection: 
Input/Output cables: 
 
Weight: 

Inputs 

Potential-free contacts: 
Sensing voltage: 
Sensing current: 

Outputs 

Rated voltage: 
Rated current: 

 

21…30 V DC SELV

 

< 10 mA 

 

43 x 42 x 11 mm 
Box of Ø 60 mm x 40 mm 
KNX connector (red/black) 
4 pairs of 28 cm length 
0.22 mm

2

 (Ø 0.56 mm) 

22 g 

 


3.3 V 
0.3 mA 

 

10 VDC (max., depends on load) 
1 mA (adjustable) 

Environmental conditions 

Operating temperature: 
Storage temperature: 
Ambient humidity: 

Electrical safety 

Pollution degree (IEC60664): 
Protection type (IEC60529): 
Protection class (IEC61140): 
Overvoltage category (IEC60664): 
Approbation (ISO/IEC14543-3): 

CE Marking 

EU Directives: 
 
 
Standards: 

 

  -

5…45 °C

 

-25...70 °C 
   

5…93 % (non

-condensing) 

 


IP20 
III 
III 
KNX-certified 

 

LVD  

(2014/35/EU) 

EMC 

(2014/30/EU) 

RoHS 

(2011/65/EU) 

EN50491-2 
EN50581 
EN61000-6-2/-3 

Mounting, commissioning and safety notes 

Installation and maintenance 

 

After connection to the KNX bus system, the device works with its default settings 
as intended 

 

Warning

: Do not connect to 230 V. The device is supplied by the KNX bus and 

does not require any additional external power supply

 

 

The device may only be installed and put into operation by a qualified electrician 
or authorized person 

 

For planning and construction of electric installations the appropriate 
specifications, guidelines and regulations in force of the respective country have to 
be complied 

 

The device must not be mounted in a box together with 230 V devices and/or  
230 V cables 

 

Combinations of a push button device connected to both the TIO4-Sec and a  
230 V device (or sockets) at the same time are not allowed 

 

Ensure that there is a safety separation (SELV) between connected signal cables 
(including extensions) and other current and voltage carrying devices and cables 

 

When connecting the TIO4-Sec, ensure that it can be isolated 

 

Prevailing safety and accident prevention rules must be heeded 

 

Connect the KNX bus line as for common KNX bus connections with a KNX bus 
cable, to be stripped and plugged into a KNX TP connector 

 

Connect either a LED or a switch / push button to a single channel 

 

Do not damage electrical insulations during connecting 

 

Installation only in dry locations 

 

Accessibility of the device for operation and visual inspection must be provided 

 

For configuring, use the ETS 

 

 

The housing must not be opened 

 

Protect the device from moisture, dirt and damage 

 

The device needs no maintenance 

 

If necessary, the device can be cleaned with a dry cloth 

 

In the case of damage (at storage, transport) no repairs may be carried out by 
unauthorized persons 

 

Configuration details and ETS database

www.tapko.de/tio4-sec

 

 

Device Certificate and Serial Number can be found on the label on the backside. 
For archiving, the certificate can be removed and identified by the Serial Number 
 
 

 

 

 