Product description
Connectors, buttons and LEDs description
The TIO4-Sec Contact Interface is a 4-fold KNX input/output module to
process binary signals and operate KNX devices via conventional push
buttons, contact sensors and switches. KNX Data Secure is supported and
Secure Commissioning can be activated. Input channels can be configured
to output functionality.
Due to its small size (50 mm diagonal), TIO4-Sec finds enough room in a
flush-mounted box (Ø 60 mm) behind the switch. Cable pairs can be
extended up to 10 m when twisted. Single channels can drive status LEDs.
Designed for sensing NO/NC floating contacts, TIO4-Sec provides usual
KNX input functions like switching, dimming, shutters, blinds control,
counter and scenes. All kinds of potential-free contacts can be connected.
LED blinking and brightness of connected status LEDs is configurable. For
every single channel, it is possible to set brightness via object or use a
night/day operation mode to set different day/night brightness values.
Requirements of Directives EMC, RoHS and LVD are met. Standards for
residential, commercial, and industrial environments are fulfilled. The full
text of the EU declaration of conformity is available at the following
internet address:
Cable pairs of Input/Output
channels A B C D
Programming button
Programming LED
red: Programming Mode active
KNX TP connector
Technical specifications
Power input
Power supply:
Current consumption:
Housing
Dimensions (HxWxD):
Flush mounting:
KNX bus connection:
Input/Output cables:
Weight:
Inputs
Potential-free contacts:
Sensing voltage:
Sensing current:
Outputs
Rated voltage:
Rated current:
21…30 V DC SELV
< 10 mA
43 x 42 x 11 mm
Box of Ø 60 mm x 40 mm
KNX connector (red/black)
4 pairs of 28 cm length
0.22 mm
2
(Ø 0.56 mm)
22 g
4
3.3 V
0.3 mA
10 VDC (max., depends on load)
1 mA (adjustable)
Environmental conditions
Operating temperature:
Storage temperature:
Ambient humidity:
Electrical safety
Pollution degree (IEC60664):
Protection type (IEC60529):
Protection class (IEC61140):
Overvoltage category (IEC60664):
Approbation (ISO/IEC14543-3):
CE Marking
EU Directives:
Standards:
-
5…45 °C
-25...70 °C
5…93 % (non
-condensing)
2
IP20
III
III
KNX-certified
LVD
(2014/35/EU)
EMC
(2014/30/EU)
RoHS
(2011/65/EU)
EN50491-2
EN50581
EN61000-6-2/-3
Mounting, commissioning and safety notes
Installation and maintenance
•
After connection to the KNX bus system, the device works with its default settings
as intended
•
Warning
: Do not connect to 230 V. The device is supplied by the KNX bus and
does not require any additional external power supply
•
The device may only be installed and put into operation by a qualified electrician
or authorized person
•
For planning and construction of electric installations the appropriate
specifications, guidelines and regulations in force of the respective country have to
be complied
•
The device must not be mounted in a box together with 230 V devices and/or
230 V cables
•
Combinations of a push button device connected to both the TIO4-Sec and a
230 V device (or sockets) at the same time are not allowed
•
Ensure that there is a safety separation (SELV) between connected signal cables
(including extensions) and other current and voltage carrying devices and cables
•
When connecting the TIO4-Sec, ensure that it can be isolated
•
Prevailing safety and accident prevention rules must be heeded
•
Connect the KNX bus line as for common KNX bus connections with a KNX bus
cable, to be stripped and plugged into a KNX TP connector
•
Connect either a LED or a switch / push button to a single channel
•
Do not damage electrical insulations during connecting
•
Installation only in dry locations
•
Accessibility of the device for operation and visual inspection must be provided
•
For configuring, use the ETS
•
The housing must not be opened
•
Protect the device from moisture, dirt and damage
•
The device needs no maintenance
•
If necessary, the device can be cleaned with a dry cloth
•
In the case of damage (at storage, transport) no repairs may be carried out by
unauthorized persons
•
Configuration details and ETS database:
•
Device Certificate and Serial Number can be found on the label on the backside.
For archiving, the certificate can be removed and identified by the Serial Number