Registering Devices and Making Settings
26
Remote Unit Registration Items
Items that are registered into the Remote Unit include Group Name, Remote
Unit Name, Frequency Channel Settings, Recording Mode Settings, Warning
Monitoring Settings, Auto-Download Settings and so on.
If the screen does not change after connecting RTR-574/576,
the USB driver installation may not have been installed correctly. Please see
[Help for Unit Recognition Failure] and check the USB driver.
3. Base Unit Operational Settings
Next please make all Base Unit operational settings from the Menu of
the RTR-500W Settings Utility.
Settings Menu
The following operational settings are made here: Wireless Route Settings,
Clock Settings, Network Settings, E-Mail Settings, FTP Settings, Send Current
Readings Settings, Warning Report Settings, and Auto-Download Settings.
4. Repeater Registration (Only if necessary)
Repeaters can be registered to help increase range and improve
wireless communication. It is also possible to register a Repeater to a
Base Unit via a network connection.
1.
In the RTR-500W Settings Utility, open the [Repeater Unit Settings]
Menu.
2.
When the direction appears in the application window, connect
the Repeater with a USB communication cable to the computer.
USB Communication
Cable
USB or Network
Connection
PC into which software has
been installed
Repeater Registration Items
Settings are made for Group Name and Frequency Channel
After all registrations and settings have been completed, place the
Base Unit, Remote Units and Repeaters in their actual positions and
carry out signal strength tests to test transmission.